Liebert RAC2-8 manual Installation

Page 42

Section 5: Installation

Refer to Figure i on Page iv in the beginning of this manual for a typical system configuration. Refer to the following drawings (including notes) for details of wire terminations and switch settings for inputs and outputs used at your installation.

Call Liebert Environmental Support at 1-800-543-2778if you require any assistance for the installation or operation of your RAC2-8 Autochangeover controller.

Select a location for the RAC2-8 that is convenient for both operation and cable routing. If the application at your installation is critical, the location should also provide limited access to the controller.

The RAC2-8 enclosure is surface mounted using four 1/4 in. bolts. The power cord is factory wired. Note that the use of a 220 VAC 50/60 Hz power source must be selected when the unit is ordered. This is not a field selectable option. Two EIA-232 ports are available at the bottom of the enclosure. All other customer cables enter through knockouts at the bottom of the enclosure.

The RAC2-8 includes a lithium backup battery for control memory. The battery is disconnected from the system for storage and shipment. Set DIP switch 2-8 to ON to connect the battery.

The RAC2-8 may show an alarm from a Liebert DataMate, mini- MATE, and/or mini-MATE Plus unit when an alarm condition does not, in fact, exist. If you are using or plan to use the RAC2-8 with the Liebert DataMate, mini-MATE, and/or mini-MATE Plus, remove the

C5 capacitor at the K5 common alarm relay to avoid false alarms:

Installation (cont’d.)

1.Put on an anti-static wrist strap.

2.Turn the main disconnect switch OFF.

Liebert RAC2-8 37

Image 42
Contents $XWRð&KDQJHRYHUý&RQWUROOHU Table of Contents Table of Figures RAC2-8 UnitPage Introduction Page Installation To start up the RAC2-8Operation Page Operation Glossary of Control Functions for more detailsSequencing Status Screens cont’d Status Sub-menuDelay UnitsStatus Sub-menu cont’d Set Options Sub-menuSet Options Sub-menu cont’d Function Delays TEMP/HUM Password StandbyAlarm Sub-menu Time Set Clock Sub-menuDate DAY of WeekUnit 01 Forced on Force OFF Restore Return Terminal LOG onStatus Screen Number of ZONES/NUMBER of Units PER Zone Setup Zones/Units OptionsSetup Zones/Units Options cont’d Unit StatusUnit Shutdown on Alarm Emergency Power Units08 0 no Alarms Review and Alarms Clear Unit LabelsSet Clock Override a Unit Set Modem Options Setup Temp/Humid Options Setup Temp/Humid Options cont’dSet Modem Options cont’d Setup Standby Unit Options Display SS Alarm Block Set New PasswordAlarms List of AlarmsAlarm Delay Alarm AnnunciationAlarm Communications AutochangeoverAutosequencing Common Alarm-Output Clear AlarmsCommon Alarm-Inputs KeyEmergency Power Operation DelayEmergency Power OFF EPO Hold DelayInactive Unit Humidity AlarmsHumidity Lockout IntervalPower Failure Mode Normal TemperaturePassword OverrideStandby Testing Restart DelayRestore Running UnitsTemperature Staging Temperature AlarmsTemperature Sensitivity TerminalZones Installation TB2 RAC2-8 Dimensional Enclosure Diagram RAC2-8 Component Arrangement RAC2-8 Connection Diagram RAC2-8 Switch and Jumper Settings