Section 3: Operation
Set Modem Options (cont’d)
Hang up on DTR
Model 1200: SW1 up and SW10 down
Model 2400: &D3
Track status of carrier detect
Model 1200: SW6 up
Model 2400: &C1
Enable
Model 1200: SW5 up
Model 2400: S0=1
Setup Temp/Humid Options
Press 8 from the Main Menu to display the Setup Temp/Humid Options screen.
RAC2-8 MAIN MENU
** SET TEMP/HUMIDITY OPTIONS **
1. | High Temperature Alarm = | 00 | ||
2. | Low Temperature Alarm | = | 00 | |
3. | High Humidity Alarm | = | 00 | |
4. | Low Humidity Alarm | = | 00 | |
5. | Temperature Staging | = | OFF | |
6. | Normal Temperature | = | 70 | |
7. | Sensitivity | = 02 |
|
|
8. | Temp Display (F/C) | = | F | |
9. | High Humidity Lockout | = | 60 | |
A. Low Humidity Lockout | = | 00 |
<ESC> TO EXIT
High Temperature Alarm =
** SET TEMP/HUMIDITY OPTIONS **
1. | High Temperature Alarm = | 80 | ||
2. | Low Temperature Alarm | = | 00 | |
3. | High Humidity Alarm | = | 00 | |
4. | Low Humidity Alarm | = | 00 | |
5. | Temperature Staging | = | OFF | |
6. | Normal Temperature | = | 70 | |
7. | Sensitivity | = 02 |
|
|
8. | Temp Display (F/C) | = | F | |
9. | High Humidity Lockout | = | 60 |
A. Low Humidity Lockout = 00
<ESC> TO EXIT
Temperature Staging = (ENTER 1 for ON, 0 for OFF) >ON
Setup Temp/Humid Options (cont’d)
Temperature and humidity options apply to Zone 1. The system inputs come from a remote temp/hum sensor. Each alarm can be disabled by entering 00 as the alarm
24 • User Manual (9/97)