Liebert RAC2-8 manual Set Modem Options cont’d, Setup Temp/Humid Options

Page 29

Section 3: Operation

Set Modem Options (cont’d)

Hang up on DTR on-off transition

Model 1200: SW1 up and SW10 down

Model 2400: &D3

Track status of carrier detect

Model 1200: SW6 up

Model 2400: &C1

Enable Auto-answer

Model 1200: SW5 up

Model 2400: S0=1

Setup Temp/Humid Options

Press 8 from the Main Menu to display the Setup Temp/Humid Options screen.

RAC2-8 MAIN MENU

** SET TEMP/HUMIDITY OPTIONS **

1.

High Temperature Alarm =

00

2.

Low Temperature Alarm

=

00

3.

High Humidity Alarm

=

00

4.

Low Humidity Alarm

=

00

5.

Temperature Staging

=

OFF

6.

Normal Temperature

=

70

7.

Sensitivity

= 02

 

 

8.

Temp Display (F/C)

=

F

9.

High Humidity Lockout

=

60

A. Low Humidity Lockout

=

00

<ESC> TO EXIT

High Temperature Alarm = (50-90) >80

** SET TEMP/HUMIDITY OPTIONS **

1.

High Temperature Alarm =

80

2.

Low Temperature Alarm

=

00

3.

High Humidity Alarm

=

00

4.

Low Humidity Alarm

=

00

5.

Temperature Staging

=

OFF

6.

Normal Temperature

=

70

7.

Sensitivity

= 02

 

 

8.

Temp Display (F/C)

=

F

9.

High Humidity Lockout

=

60

A. Low Humidity Lockout = 00

<ESC> TO EXIT

Temperature Staging = (ENTER 1 for ON, 0 for OFF) >ON

Setup Temp/Humid Options (cont’d)

Temperature and humidity options apply to Zone 1. The system inputs come from a remote temp/hum sensor. Each alarm can be disabled by entering 00 as the alarm trip-point. Temperature Staging turns on a Standby unit when the room temperature exceeds the Normal Temperature by the number of degrees entered in Sensitivity. Also note that temperature can be displayed in either degrees F or degrees C.

24 User Manual (9/97)

Image 29
Contents $XWRð&KDQJHRYHUý&RQWUROOHU Table of Contents Table of Figures Unit RAC2-8Page Introduction Page Operation InstallationTo start up the RAC2-8 Page Glossary of Control Functions for more details OperationStatus Sub-menu Sequencing Status Screens cont’dUnits DelaySet Options Sub-menu cont’d Status Sub-menu cont’dSet Options Sub-menu Function Delays TEMP/HUM Standby PasswordAlarm Sub-menu Date Set Clock Sub-menuTime DAY of WeekUnit 01 Forced on Force OFF Restore Return LOG on TerminalStatus Screen Setup Zones/Units Options cont’d Setup Zones/Units OptionsNumber of ZONES/NUMBER of Units PER Zone Unit StatusEmergency Power Units Unit Shutdown on Alarm08 0 no Set Clock Alarms Review and Alarms ClearUnit Labels Override a Unit Set Modem Options Set Modem Options cont’d Setup Temp/Humid OptionsSetup Temp/Humid Options cont’d Setup Standby Unit Options Set New Password Display SS Alarm BlockList of Alarms AlarmsAlarm Communications Alarm AnnunciationAlarm Delay AutochangeoverAutosequencing Common Alarm-Inputs Clear AlarmsCommon Alarm-Output KeyEmergency Power OFF EPO DelayEmergency Power Operation Hold DelayHumidity Lockout Humidity AlarmsInactive Unit IntervalPassword Normal TemperaturePower Failure Mode OverrideRestore Restart DelayStandby Testing Running UnitsTemperature Sensitivity Temperature AlarmsTemperature Staging TerminalZones Installation TB2 RAC2-8 Dimensional Enclosure Diagram RAC2-8 Component Arrangement RAC2-8 Connection Diagram RAC2-8 Switch and Jumper Settings