Eaton Electrical Powerware 9315 operation manual To Place the UPS in Normal Mode

Page 24

Starting and Stopping the UPS

The following describes the switches on the Control Panel (see Figure 4-1):

￿The MODE switch is a two-position rotary switch that controls the manual transfer of the UPS to and from Bypass mode. The MODE switch is used to:

-Place the critical load in Bypass mode when the UPS is operating in Normal mode and the bypass source is within acceptable limits. If the transfer does not occur within two seconds, an alarm sounds.

-Prevent transfer to Normal mode when the UPS is in Bypass mode.

-Shut down the power processing unit (inverter and rectifier) of the UPS.

￿The BATTERY switch is a two-position rotary switch that allows you to manually shunt trip the battery breakers in remote cabinets.

￿The circuit breaker (CB1) switch controls the operation of the rectifier and inverter. If CB1 is on (closed), the rectifier turns on when the START switch is activated and the proper voltage is at the input terminals.

￿The PUSH TO RESET button is described in “Resetting the UPS System after Load Off” on page 11-2.

￿The START switch activates the power controls on the Control Panel. The START switch is center-biased (the key will rest only in the upright position). Its operation is similar to that of an automobile ignition switch. After setting the operator controls, you turn the START switch to the right momentarily to activate the controls. When you release it, it returns to the upright position.

The following sections describe how to operate these controls to start, stop, or change the operating mode of the UPS.

4.1.1To Place the UPS in Normal Mode

1.Close the Input Power Feeder breaker.

2.Verify that the Load Off PUSH TO RESET button is pressed in.

3.Turn the BATTERY switch to NORMAL.

4.Turn the MODE switch to NORMAL.

5.Move the CB1 switch to ON.

6.Turn the START switch to the right momentarily.

The rectifier turns on, then the inverter turns on. The UPS display and alarm alert you to close the battery breaker.

7.Close the battery breaker(s).

4-2

EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com

Image 24
Contents Page Important Safety Instructions Table of Contents Starting and Stopping the UPS Maintaining the UPS System List of Figures Introduction Conventions Used in This ManualFor More Information Getting HelpSafety Warnings Getting StartedTypical Powerware 9315 UPS System Typical Powerware 9315 UPS SystemPower Processing Unit PPU Looking Inside the UPSUPS Standard Features Monitor PanelControl Panel Communication BaysOptions and Accessories Power Distribution Module LV models only Upgrade CapabilityRemote Monitor Panel Relay Interface ModuleOutput Transformer ModemCustomer Convenience Outlet Symbols, Controls, and Indicators Normal Mode Understanding UPS OperationPath of Current Through the UPS in Normal Mode Bypass Mode Path of Current Through the UPS in Bypass ModeBattery Mode Path of Current Through the UPS in Battery ModeMonitoring and Controlling UPS Operation Location of the Monitor Panel and the Control PanelThis page intentionally left blank Using the Control Panel Starting and Stopping the UPSTo Place the UPS in Normal Mode To Shut Down the UPS from Normal Mode To Start the UPS in Bypass ModeThis page intentionally left blank Using the Monitor Panel UPS Monitor PanelUsing the LCD Screen System Normal 04 MAY 142345 AlarmUsing the Buttons Adjusting the ContrastUsing the Load Off Button Reading the Status Indicators Using the Menu OptionsShows the Load Amps Meters screen Load Amps Meters Screen Event History Log Screen Active System Events Screen Unit Statistics Screen Mimic Screen Time Setup Screen 10. Setup Serial Port 1 Screen Using Features and Options Building Alarm MonitoringSummary Alarm Contacts Summary Alarm ContactsRemote Monitor Panel Remote Monitor PanelOptional Monitoring Accessories Battery Cabinets External Battery DisconnectRelay Interface Module UPS AvailableSupervisory Contact Module On GeneratorThis page intentionally left blank Communication Locating the Communication BaysLocation of Communication Bays on the UPS Powerware 9315 Slot CardsLanSafe Power Management Software Connecting Equipment to a Serial PortPin Assignments for Port 1 DB-9 Pin Assignments for Port 2 DB-25 Configuring the Serial Ports Setup Serial Port 1 ScreenMode RateDefault Settings Data/StopHandshaking SaveTerminal Mode Printing Selected InformationEntire Log Ctrl+P Event History LogMeters Printout Ctrl+M System MetersBattery Test Printout Ctrl+B System Information Printout Ctrl+ASystem Configuration System Configuration Mode Main MenuProgram Building Alarms Enable/Disable Default Functions Customize Alarm Messages Adjust Output Voltage Change PasswordProgram Unit Name Battery Test Setup WK DAY MON HrmnCalibration Mode Computer ModeRemote Monitor Mode Modify Low Battery TimeRemote Notification This page intentionally left blank Important Safety Instructions Maintaining the UPS SystemPerforming Preventive Maintenance E R T I S S E M E N TMaintenance Training This page intentionally left blank Product Specifications Model NumbersSystem Output Battery Specifications This page intentionally left blank Responding to System Events System Event HornsSystem Event Lights System Event Messages10-2 Rectifier Messages Alarms Rectifier Messages Notices Monitor Panel Alarms Monitor Panel Notices Using the Load OFF Button Resetting the UPS System after Load Off Warranty Limited Factory Warranty for THREE-PHASE Powerware ProductsWarranty Page 164201036F