Eaton Electrical Powerware 9315 operation manual Battery Test Setup, WK DAY MON Hrmn

Page 63

Communication

7.7.8 Battery Test Setup

If Battery Test Setup is selected from the main menu, the following menu is displayed:

Battery Test Setup

1.Setup One-time Delayed Battery Test

2.Setup Monthly Battery Test

3.Setup Quarterly Battery Test

4.Cancel Pending Battery Test

5.Display Next Scheduled Battery Test

6.Return to Main Menu

Enter Selection:

This menu allows you to schedule, review schedule, or cancel pending battery tests. The following menu is displayed when 1-3 is selected:

Enter Starting Month (1-12):

Enter Day of Week, Sunday = 1, (1-7):

Enter Week of Month (1-5):

Enter Hour of Test (0-23):

Enter Minute of Test (0-59):

NOTE Press <ENTER> after each entry.

<CR> with no entry will return to Battery Test Setup Menu.

Enter the information at the prompt with a carriage return to schedule the battery test.

If entry 4 is selected from the Battery Test Setup menu, you are prompted to enter “Y” to cancel all pending tests. This selection cancels only pending tests and does not stop a test currently in progress.

If entry 5 is selected from the Battery Test Setup menu, and if a Battery Test is scheduled, the following menu is displayed:

Next Battery Test Scheduled

WK DAY MON HR:MN

4 FRI MAR 15:34

NOTE Press <ENTER> to return to the Battery Test Setup Menu.

If entry 5 is selected and there are no tests scheduled, the following text appears:

No Battery Test Scheduled

Enter <CR> to return to Battery Test Setup Menu

NOTE The UPS performs only one battery test in any 24-hour period.

EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com

7-17

Image 63
Contents Page Important Safety Instructions Table of Contents Starting and Stopping the UPS Maintaining the UPS System List of Figures Conventions Used in This Manual IntroductionGetting Help For More InformationGetting Started Safety WarningsTypical Powerware 9315 UPS System Typical Powerware 9315 UPS SystemLooking Inside the UPS Power Processing Unit PPUCommunication Bays UPS Standard FeaturesMonitor Panel Control PanelOptions and Accessories Relay Interface Module Power Distribution Module LV models onlyUpgrade Capability Remote Monitor PanelOutput Transformer ModemCustomer Convenience Outlet Symbols, Controls, and Indicators Understanding UPS Operation Normal ModePath of Current Through the UPS in Normal Mode Path of Current Through the UPS in Bypass Mode Bypass ModePath of Current Through the UPS in Battery Mode Battery ModeLocation of the Monitor Panel and the Control Panel Monitoring and Controlling UPS OperationThis page intentionally left blank Starting and Stopping the UPS Using the Control PanelTo Place the UPS in Normal Mode To Start the UPS in Bypass Mode To Shut Down the UPS from Normal ModeThis page intentionally left blank UPS Monitor Panel Using the Monitor PanelSystem Normal 04 MAY 142345 Alarm Using the LCD ScreenUsing the Buttons Adjusting the ContrastUsing the Load Off Button Using the Menu Options Reading the Status IndicatorsShows the Load Amps Meters screen Load Amps Meters Screen Event History Log Screen Active System Events Screen Unit Statistics Screen Mimic Screen Time Setup Screen 10. Setup Serial Port 1 Screen Building Alarm Monitoring Using Features and OptionsSummary Alarm Contacts Summary Alarm ContactsRemote Monitor Panel Remote Monitor PanelOptional Monitoring Accessories External Battery Disconnect Battery CabinetsUPS Available Relay Interface ModuleOn Generator Supervisory Contact ModuleThis page intentionally left blank Locating the Communication Bays CommunicationSlot Cards Location of Communication Bays on the UPS Powerware 9315Connecting Equipment to a Serial Port LanSafe Power Management SoftwarePin Assignments for Port 1 DB-9 Pin Assignments for Port 2 DB-25 Setup Serial Port 1 Screen Configuring the Serial PortsRate ModeSave Default SettingsData/Stop HandshakingPrinting Selected Information Terminal ModeEvent History Log Entire Log Ctrl+PSystem Meters Meters Printout Ctrl+MSystem Information Printout Ctrl+A Battery Test Printout Ctrl+BSystem Configuration System Configuration Mode Main MenuProgram Building Alarms Enable/Disable Default Functions Customize Alarm Messages Adjust Output Voltage Change PasswordProgram Unit Name WK DAY MON Hrmn Battery Test SetupModify Low Battery Time Calibration ModeComputer Mode Remote Monitor ModeRemote Notification This page intentionally left blank Maintaining the UPS System Important Safety InstructionsE R T I S S E M E N T Performing Preventive MaintenanceMaintenance Training This page intentionally left blank Model Numbers Product SpecificationsSystem Output Battery Specifications This page intentionally left blank System Event Messages Responding to System EventsSystem Event Horns System Event Lights10-2 Rectifier Messages Alarms Rectifier Messages Notices Monitor Panel Alarms Monitor Panel Notices Using the Load OFF Button Resetting the UPS System after Load Off Limited Factory Warranty for THREE-PHASE Powerware Products WarrantyWarranty Page 164201036F