Eaton Electrical Powerware 9315 System Information Printout Ctrl+A, Battery Test Printout Ctrl+B

Page 58

Communication

7.6.4 System Information Printout – [Ctrl]+[A]

This key sequence prints a listing of all available serial data. This printout contains the information shown on the Event History Log and System Meters screens of the UPS (both Figure 7-6 and Figure 7-7).

7.6.5 Battery Test Printout – [Ctrl]+[B]

This key sequence prints the Battery Test Log. The log consists of a history of the last

30 battery tests that were run and the results of those tests. The most recent test appears at the bottom of the log. Figure 7-8 shows a sample of the Battery Test Log.

Uninterruptible Power System

 

UPS # 1

 

 

 

UPS System Normal

 

12 NOV 1997 15:39:31

Alarm: None

 

 

 

 

Notice:

None

 

 

 

 

Battery Test Log

 

 

Date/Time

Volts

Health

Data

AUG 14

23:45

498.0

1.00

0000

SEP 11

23:45

498.0

1.00

0000

OCT

9

23:45

498.0

1.00

0000

NOV 13

23:45

498.0

0.99

0000

DEC 11

23:45

498.0

0.99

0000

JAN

8

23:45

498.0

0.98

0000

FEB 12

23:45

498.0

0.98

0000

MAR 12

23:41

000.0

0.00

0003

APR

9

23:45

496.2

0.98

0000

Figure 7-8. Battery Test Log

The Date/Time field is the date and time of the battery test.

The Volts field is a measured value of the battery voltage during the test. This field displays 000.0 if the test did not run to completion.

The Health field is a relative measurement of the battery condition. This number can be used to chart the condition of the batteries. If a sudden change of this number occurs relative to the previous test results, it is an indication that the batteries may need attention. This display is 0.00 if the test does not run to completion.

The Data field is a value to be used by your field service engineer to gain more information about the battery tests.

If the battery test does not complete, the Volts and Health field reads zero and the UPS Event History Log reports either Battery Test Failed, Battery Test Aborted (Load), or Battery Test Aborted (Utility). If the test ran to completion, Battery Passed Test appears in the UPS Event History Log.

7-12

EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com

Image 58
Contents Page Important Safety Instructions Table of Contents Starting and Stopping the UPS Maintaining the UPS System List of Figures Introduction Conventions Used in This ManualFor More Information Getting HelpSafety Warnings Getting StartedTypical Powerware 9315 UPS System Typical Powerware 9315 UPS SystemPower Processing Unit PPU Looking Inside the UPSControl Panel UPS Standard FeaturesMonitor Panel Communication BaysOptions and Accessories Remote Monitor Panel Power Distribution Module LV models onlyUpgrade Capability Relay Interface ModuleModem Output TransformerCustomer Convenience Outlet Symbols, Controls, and Indicators Normal Mode Understanding UPS OperationPath of Current Through the UPS in Normal Mode Bypass Mode Path of Current Through the UPS in Bypass ModeBattery Mode Path of Current Through the UPS in Battery ModeMonitoring and Controlling UPS Operation Location of the Monitor Panel and the Control PanelThis page intentionally left blank Using the Control Panel Starting and Stopping the UPSTo Place the UPS in Normal Mode To Shut Down the UPS from Normal Mode To Start the UPS in Bypass ModeThis page intentionally left blank Using the Monitor Panel UPS Monitor PanelUsing the LCD Screen System Normal 04 MAY 142345 AlarmAdjusting the Contrast Using the ButtonsUsing the Load Off Button Reading the Status Indicators Using the Menu OptionsShows the Load Amps Meters screen Load Amps Meters Screen Event History Log Screen Active System Events Screen Unit Statistics Screen Mimic Screen Time Setup Screen 10. Setup Serial Port 1 Screen Using Features and Options Building Alarm MonitoringSummary Alarm Contacts Summary Alarm ContactsRemote Monitor Panel Remote Monitor PanelOptional Monitoring Accessories Battery Cabinets External Battery DisconnectRelay Interface Module UPS AvailableSupervisory Contact Module On GeneratorThis page intentionally left blank Communication Locating the Communication BaysLocation of Communication Bays on the UPS Powerware 9315 Slot CardsLanSafe Power Management Software Connecting Equipment to a Serial PortPin Assignments for Port 1 DB-9 Pin Assignments for Port 2 DB-25 Configuring the Serial Ports Setup Serial Port 1 ScreenMode RateHandshaking Default SettingsData/Stop SaveTerminal Mode Printing Selected InformationEntire Log Ctrl+P Event History LogMeters Printout Ctrl+M System MetersBattery Test Printout Ctrl+B System Information Printout Ctrl+ASystem Configuration Mode Main Menu System ConfigurationProgram Building Alarms Enable/Disable Default Functions Customize Alarm Messages Change Password Adjust Output VoltageProgram Unit Name Battery Test Setup WK DAY MON HrmnRemote Monitor Mode Calibration ModeComputer Mode Modify Low Battery TimeRemote Notification This page intentionally left blank Important Safety Instructions Maintaining the UPS SystemPerforming Preventive Maintenance E R T I S S E M E N TMaintenance Training This page intentionally left blank Product Specifications Model NumbersSystem Output Battery Specifications This page intentionally left blank System Event Lights Responding to System EventsSystem Event Horns System Event Messages10-2 Rectifier Messages Alarms Rectifier Messages Notices Monitor Panel Alarms Monitor Panel Notices Using the Load OFF Button Resetting the UPS System after Load Off Warranty Limited Factory Warranty for THREE-PHASE Powerware ProductsWarranty Page 164201036F