Eaton Electrical Powerware 9315 Using Features and Options, Building Alarm Monitoring

Page 39

Chapter 6

Using Features and Options

You can add available options and accessories to enhance the performance of your UPS system. This chapter provides detailed descriptions of some of the features and options introduced earlier in this manual.

6.1 Building Alarm Monitoring

This standard feature lets you connect the UPS to your building alarms, such as smoke detectors or overtemperature alarms. The terminals for external connections are located inside the UPS on the customer interface panel (see Figure 6-1).

TB1

1BLDG ALARM 1

2BLDG ALARM 1 RTN

3BLDG ALARM 2

4BLDG ALARM 2 RTN

5BLDG ALARM 3

6BLDG ALARM 3 RTN

7 BLDG ALARM 4

8 BLDG ALARM 4 RTN

9BLDG ALARM 5

10 BLDG ALARM 5 RTN

11 BLDG ALARM 6

12 BLDG ALARM 6 RTN

13

14

15

TB2

1REMOTE EPO

2REMOTE EPO RTN

3

4ON INV

5ON INV RTN

6ON BYPASS

7ON BYPASS RTN

8BATTERY CONTACTOR CLOSED

9 BATTERY CONT RTN

10RELAY 1 NO

11RELAY 1 NC

12ALARM RTN

13 RELAY 2 NO

14RELAY 2 NC

15NOTICE RTN

RS-485

NOTE:

All building alarm inputs or remote features require an isolated, normally open contact or switch (rated at

24 Vdc 20 mA minimum) connected between the alarm input terminal and common terminal as shown. All control wiring, relay, and switch contacts are customer-provided.

RS-232

Figure 6-1. External Connections for Building Alarm Monitoring

Regardless of how you assign the building alarms, they display as Building Alarm 1, Building Alarm 2, Building Alarm 3, etc., on the LCD screen of the Monitor Panel. You should use twisted-pair wires for each alarm input and common.

EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com

6-1

Image 39
Contents Page Important Safety Instructions Table of Contents Starting and Stopping the UPS Maintaining the UPS System List of Figures Conventions Used in This Manual IntroductionGetting Help For More InformationGetting Started Safety WarningsTypical Powerware 9315 UPS System Typical Powerware 9315 UPS SystemLooking Inside the UPS Power Processing Unit PPUCommunication Bays UPS Standard FeaturesMonitor Panel Control PanelOptions and Accessories Relay Interface Module Power Distribution Module LV models onlyUpgrade Capability Remote Monitor PanelOutput Transformer ModemCustomer Convenience Outlet Symbols, Controls, and Indicators Understanding UPS Operation Normal ModePath of Current Through the UPS in Normal Mode Path of Current Through the UPS in Bypass Mode Bypass ModePath of Current Through the UPS in Battery Mode Battery ModeLocation of the Monitor Panel and the Control Panel Monitoring and Controlling UPS OperationThis page intentionally left blank Starting and Stopping the UPS Using the Control PanelTo Place the UPS in Normal Mode To Start the UPS in Bypass Mode To Shut Down the UPS from Normal ModeThis page intentionally left blank UPS Monitor Panel Using the Monitor PanelSystem Normal 04 MAY 142345 Alarm Using the LCD ScreenUsing the Buttons Adjusting the ContrastUsing the Load Off Button Using the Menu Options Reading the Status IndicatorsShows the Load Amps Meters screen Load Amps Meters Screen Event History Log Screen Active System Events Screen Unit Statistics Screen Mimic Screen Time Setup Screen 10. Setup Serial Port 1 Screen Building Alarm Monitoring Using Features and OptionsSummary Alarm Contacts Summary Alarm ContactsRemote Monitor Panel Remote Monitor PanelOptional Monitoring Accessories External Battery Disconnect Battery CabinetsUPS Available Relay Interface ModuleOn Generator Supervisory Contact ModuleThis page intentionally left blank Locating the Communication Bays CommunicationSlot Cards Location of Communication Bays on the UPS Powerware 9315Connecting Equipment to a Serial Port LanSafe Power Management SoftwarePin Assignments for Port 1 DB-9 Pin Assignments for Port 2 DB-25 Setup Serial Port 1 Screen Configuring the Serial PortsRate ModeSave Default SettingsData/Stop HandshakingPrinting Selected Information Terminal ModeEvent History Log Entire Log Ctrl+PSystem Meters Meters Printout Ctrl+MSystem Information Printout Ctrl+A Battery Test Printout Ctrl+BSystem Configuration System Configuration Mode Main MenuProgram Building Alarms Enable/Disable Default Functions Customize Alarm Messages Adjust Output Voltage Change PasswordProgram Unit Name WK DAY MON Hrmn Battery Test SetupModify Low Battery Time Calibration ModeComputer Mode Remote Monitor ModeRemote Notification This page intentionally left blank Maintaining the UPS System Important Safety InstructionsE R T I S S E M E N T Performing Preventive MaintenanceMaintenance Training This page intentionally left blank Model Numbers Product SpecificationsSystem Output Battery Specifications This page intentionally left blank System Event Messages Responding to System EventsSystem Event Horns System Event Lights10-2 Rectifier Messages Alarms Rectifier Messages Notices Monitor Panel Alarms Monitor Panel Notices Using the Load OFF Button Resetting the UPS System after Load Off Limited Factory Warranty for THREE-PHASE Powerware Products WarrantyWarranty Page 164201036F