Eaton Electrical Powerware 9315 Path of Current Through the UPS in Bypass Mode

Page 19

Understanding UPS Operation

3.2 Bypass Mode

The UPS automatically switches to Bypass mode if it detects an overload, load fault, or internal failure. The bypass source supplies the commercial AC power to the load directly.

C A U T I O N

The critical load is not protected while the UPS is in Bypass mode.

Figure 3-2 shows the path of electrical power through the UPS system when the UPS is operating in Bypass mode.

Bypass

Bypass

Input

K4

 

Rectifier

Inverter

Rectifier

CB1

 

 

 

Input

 

 

K3 Output

(Open)

Transformer

Path of electrical power

Battery

Figure 3-2. Path of Current Through the UPS in Bypass Mode

You can transfer the UPS from Normal mode to Bypass mode manually. However, the UPS switches automatically to Bypass mode whenever the inverter can no longer supply the critical load. If the UPS transfers to Bypass mode from Normal mode due to any reason other than operator intervention, the UPS automatically attempts to transfer back to Normal mode (up to three times within a 10-minute period). The fourth transfer will lock the critical load on the bypass source and requires operator intervention to transfer.

Bypass mode is a normal operating mode, and not an alarm condition. However, if the UPS is unable to return to Normal mode following an automatic transfer to Bypass mode, an alarm condition is recorded.

EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com

3-3

Image 19
Contents Page Important Safety Instructions Table of Contents Starting and Stopping the UPS Maintaining the UPS System List of Figures Conventions Used in This Manual IntroductionGetting Help For More InformationGetting Started Safety WarningsTypical Powerware 9315 UPS System Typical Powerware 9315 UPS SystemLooking Inside the UPS Power Processing Unit PPUCommunication Bays UPS Standard FeaturesMonitor Panel Control PanelOptions and Accessories Relay Interface Module Power Distribution Module LV models onlyUpgrade Capability Remote Monitor PanelModem Output TransformerCustomer Convenience Outlet Symbols, Controls, and Indicators Understanding UPS Operation Normal ModePath of Current Through the UPS in Normal Mode Path of Current Through the UPS in Bypass Mode Bypass ModePath of Current Through the UPS in Battery Mode Battery ModeLocation of the Monitor Panel and the Control Panel Monitoring and Controlling UPS OperationThis page intentionally left blank Starting and Stopping the UPS Using the Control PanelTo Place the UPS in Normal Mode To Start the UPS in Bypass Mode To Shut Down the UPS from Normal ModeThis page intentionally left blank UPS Monitor Panel Using the Monitor PanelSystem Normal 04 MAY 142345 Alarm Using the LCD ScreenAdjusting the Contrast Using the ButtonsUsing the Load Off Button Using the Menu Options Reading the Status IndicatorsShows the Load Amps Meters screen Load Amps Meters Screen Event History Log Screen Active System Events Screen Unit Statistics Screen Mimic Screen Time Setup Screen 10. Setup Serial Port 1 Screen Building Alarm Monitoring Using Features and OptionsSummary Alarm Contacts Summary Alarm ContactsRemote Monitor Panel Remote Monitor PanelOptional Monitoring Accessories External Battery Disconnect Battery CabinetsUPS Available Relay Interface ModuleOn Generator Supervisory Contact ModuleThis page intentionally left blank Locating the Communication Bays CommunicationSlot Cards Location of Communication Bays on the UPS Powerware 9315Connecting Equipment to a Serial Port LanSafe Power Management SoftwarePin Assignments for Port 1 DB-9 Pin Assignments for Port 2 DB-25 Setup Serial Port 1 Screen Configuring the Serial PortsRate ModeSave Default SettingsData/Stop HandshakingPrinting Selected Information Terminal ModeEvent History Log Entire Log Ctrl+PSystem Meters Meters Printout Ctrl+MSystem Information Printout Ctrl+A Battery Test Printout Ctrl+BSystem Configuration Mode Main Menu System ConfigurationProgram Building Alarms Enable/Disable Default Functions Customize Alarm Messages Change Password Adjust Output VoltageProgram Unit Name WK DAY MON Hrmn Battery Test SetupModify Low Battery Time Calibration ModeComputer Mode Remote Monitor ModeRemote Notification This page intentionally left blank Maintaining the UPS System Important Safety InstructionsE R T I S S E M E N T Performing Preventive MaintenanceMaintenance Training This page intentionally left blank Model Numbers Product SpecificationsSystem Output Battery Specifications This page intentionally left blank System Event Messages Responding to System EventsSystem Event Horns System Event Lights10-2 Rectifier Messages Alarms Rectifier Messages Notices Monitor Panel Alarms Monitor Panel Notices Using the Load OFF Button Resetting the UPS System after Load Off Limited Factory Warranty for THREE-PHASE Powerware Products WarrantyWarranty Page 164201036F