Eaton Electrical Powerware 9315 Reading the Status Indicators, Using the Menu Options

Page 30

Using the Monitor Panel

5.5 Reading the Status Indicators

The six symbols on the left side of the monitor panel are status indicators. They are backlit by colored light emitting diodes (LEDs), and they work in conjunction with the alarm horn to let you know the operating status of the UPS.

Indicator

Indicator

Description

Symbol

Name

 

 

Normal

This green symbol is lit when the UPS is operating in Normal mode.

 

 

The PPU is supplying power to the critical load.

 

Battery

This yellow symbol is lit when the UPS is operating in Battery mode.

 

 

Because Battery mode is a normal condition of the UPS, the Normal

 

 

indicator also remains lit.

 

Bypass

This yellow symbol is lit when the UPS is operating in Bypass mode.

 

 

The critical load is supported by the bypass source. The Normal

 

 

indicator is not lit when the system is in Bypass mode.

 

Notice

This yellow symbol is lit when the system needs attention. The LCD

 

 

screen shows all active notices. Some notices may be accompanied by

 

 

an audible horn. To silence the horn, press the and buttons

 

 

simultaneously. The Notice indicator may be lit along with other

 

 

indicators.

 

Alarm

This red symbol is lit when a situation requires immediate attention.

 

 

The LCD screen shows the highest priority active alarms. All alarms are

 

 

accompanied by an audible horn. To silence the horn, press the

 

 

and buttons simultaneously. The Alarm indicator may be lit along

 

 

with other indicators.

 

Standby

This yellow symbol is lit when electricity is present in the PPU of the

 

 

UPS and the Normal indicator is not lit. During normal startup, this

 

 

indicator illuminates until the the UPS transfers to Normal mode, at

 

 

which point the Normal indicator is lit. During normal shutdown, the

 

 

Standby indicator is lit until all energy in the UPS is dissipated and

 

 

shutdown is complete.

For more information about audible horns, see “System Event Horns” on page 10-1.

To test the LEDs behind the status indicators, press the and buttons simultaneously for three seconds. All the indicators should illuminate while you hold down these buttons. If any indicator does not illuminate, its LED may need to be replaced. Contact your Eaton service representative if you have a problem with the indicator LEDs.

5.6 Using the Menu Options

The UPS menus allow you to display data in the information area to help you monitor and control UPS operation. The following menus and options are available:

￿Meters - Displays UPS performance meters for the system or critical load.

￿Events - Displays the list of Active System Events and a historical log of system events.

￿Statistics - Displays statistical information about UPS operations for the battery, load, or line.

5-4

EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com

Image 30
Contents Page Important Safety Instructions Table of Contents Starting and Stopping the UPS Maintaining the UPS System List of Figures Introduction Conventions Used in This ManualFor More Information Getting HelpSafety Warnings Getting StartedTypical Powerware 9315 UPS System Typical Powerware 9315 UPS SystemPower Processing Unit PPU Looking Inside the UPSControl Panel UPS Standard FeaturesMonitor Panel Communication BaysOptions and Accessories Remote Monitor Panel Power Distribution Module LV models onlyUpgrade Capability Relay Interface ModuleOutput Transformer ModemCustomer Convenience Outlet Symbols, Controls, and Indicators Normal Mode Understanding UPS OperationPath of Current Through the UPS in Normal Mode Bypass Mode Path of Current Through the UPS in Bypass ModeBattery Mode Path of Current Through the UPS in Battery ModeMonitoring and Controlling UPS Operation Location of the Monitor Panel and the Control PanelThis page intentionally left blank Using the Control Panel Starting and Stopping the UPSTo Place the UPS in Normal Mode To Shut Down the UPS from Normal Mode To Start the UPS in Bypass ModeThis page intentionally left blank Using the Monitor Panel UPS Monitor PanelUsing the LCD Screen System Normal 04 MAY 142345 AlarmUsing the Buttons Adjusting the ContrastUsing the Load Off Button Reading the Status Indicators Using the Menu OptionsShows the Load Amps Meters screen Load Amps Meters Screen Event History Log Screen Active System Events Screen Unit Statistics Screen Mimic Screen Time Setup Screen 10. Setup Serial Port 1 Screen Using Features and Options Building Alarm MonitoringSummary Alarm Contacts Summary Alarm ContactsRemote Monitor Panel Remote Monitor PanelOptional Monitoring Accessories Battery Cabinets External Battery DisconnectRelay Interface Module UPS AvailableSupervisory Contact Module On GeneratorThis page intentionally left blank Communication Locating the Communication BaysLocation of Communication Bays on the UPS Powerware 9315 Slot CardsLanSafe Power Management Software Connecting Equipment to a Serial PortPin Assignments for Port 1 DB-9 Pin Assignments for Port 2 DB-25 Configuring the Serial Ports Setup Serial Port 1 ScreenMode RateHandshaking Default SettingsData/Stop SaveTerminal Mode Printing Selected InformationEntire Log Ctrl+P Event History LogMeters Printout Ctrl+M System MetersBattery Test Printout Ctrl+B System Information Printout Ctrl+ASystem Configuration System Configuration Mode Main MenuProgram Building Alarms Enable/Disable Default Functions Customize Alarm Messages Adjust Output Voltage Change PasswordProgram Unit Name Battery Test Setup WK DAY MON HrmnRemote Monitor Mode Calibration ModeComputer Mode Modify Low Battery TimeRemote Notification This page intentionally left blank Important Safety Instructions Maintaining the UPS SystemPerforming Preventive Maintenance E R T I S S E M E N TMaintenance Training This page intentionally left blank Product Specifications Model NumbersSystem Output Battery Specifications This page intentionally left blank System Event Lights Responding to System EventsSystem Event Horns System Event Messages10-2 Rectifier Messages Alarms Rectifier Messages Notices Monitor Panel Alarms Monitor Panel Notices Using the Load OFF Button Resetting the UPS System after Load Off Warranty Limited Factory Warranty for THREE-PHASE Powerware ProductsWarranty Page 164201036F