Eaton Electrical Powerware 9315 operation manual To Shut Down the UPS from Normal Mode

Page 25

Starting and Stopping the UPS

When the inverter reaches full voltage, it turns on and supplies power to the critical load. It takes less than one minute for the UPS to achieve Normal mode.

If a bypass source is available when you turn the START switch on, the critical load is immediately supplied by the bypass source in Bypass mode until the inverter turns on and the UPS transfers to Normal mode. The status indicators on the Monitor Panel indicate when the UPS is in Bypass mode or Normal mode as appropriate.

4.1.2To Shut Down the UPS from Normal Mode

1.Turn the MODE switch to BYPASS.

The UPS switches to Bypass mode. If the bypass source is not available, the power processor remains on and an alarm sounds.

2.When the transfer is complete (the LCD screen reads “On Bypass”), move the CB1 switch to OFF.

The bypass source supplies the critical load and the power processor de-energizes. The Bypass mode indicator illuminates on the Monitor Panel.

4.1.3To Start the UPS in Bypass Mode

If the PPU of the UPS is not available and you need to energize the critical load right away, you can energize the critical load without the benefit of backup. To turn the UPS on in Bypass mode:

1.Turn the MODE switch to BYPASS. (The remaining switches can be in any position.)

2.Turn the START switch to the right momentarily.

Power to the critical load is supplied by the bypass source. No backup is available.

4.1.4To Shut Down Power to the Critical Load While in Bypass Mode

To perform maintenance or service on the critical load, you must shut it down first:

1.Turn off all equipment that is being powered through the UPS.

2.Press the LOAD OFF button on the Monitor Panel.

EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com

4-3

Image 25
Contents Page Important Safety Instructions Table of Contents Starting and Stopping the UPS Maintaining the UPS System List of Figures Conventions Used in This Manual IntroductionGetting Help For More InformationGetting Started Safety WarningsTypical Powerware 9315 UPS System Typical Powerware 9315 UPS SystemLooking Inside the UPS Power Processing Unit PPUMonitor Panel UPS Standard FeaturesControl Panel Communication BaysOptions and Accessories Upgrade Capability Power Distribution Module LV models onlyRemote Monitor Panel Relay Interface ModuleModem Output TransformerCustomer Convenience Outlet Symbols, Controls, and Indicators Understanding UPS Operation Normal ModePath of Current Through the UPS in Normal Mode Path of Current Through the UPS in Bypass Mode Bypass ModePath of Current Through the UPS in Battery Mode Battery ModeLocation of the Monitor Panel and the Control Panel Monitoring and Controlling UPS OperationThis page intentionally left blank Starting and Stopping the UPS Using the Control PanelTo Place the UPS in Normal Mode To Start the UPS in Bypass Mode To Shut Down the UPS from Normal ModeThis page intentionally left blank UPS Monitor Panel Using the Monitor PanelSystem Normal 04 MAY 142345 Alarm Using the LCD ScreenAdjusting the Contrast Using the ButtonsUsing the Load Off Button Using the Menu Options Reading the Status IndicatorsShows the Load Amps Meters screen Load Amps Meters Screen Event History Log Screen Active System Events Screen Unit Statistics Screen Mimic Screen Time Setup Screen 10. Setup Serial Port 1 Screen Building Alarm Monitoring Using Features and OptionsSummary Alarm Contacts Summary Alarm ContactsRemote Monitor Panel Remote Monitor PanelOptional Monitoring Accessories External Battery Disconnect Battery CabinetsUPS Available Relay Interface ModuleOn Generator Supervisory Contact ModuleThis page intentionally left blank Locating the Communication Bays CommunicationSlot Cards Location of Communication Bays on the UPS Powerware 9315Connecting Equipment to a Serial Port LanSafe Power Management SoftwarePin Assignments for Port 1 DB-9 Pin Assignments for Port 2 DB-25 Setup Serial Port 1 Screen Configuring the Serial PortsRate ModeData/Stop Default SettingsHandshaking SavePrinting Selected Information Terminal ModeEvent History Log Entire Log Ctrl+PSystem Meters Meters Printout Ctrl+MSystem Information Printout Ctrl+A Battery Test Printout Ctrl+BSystem Configuration Mode Main Menu System ConfigurationProgram Building Alarms Enable/Disable Default Functions Customize Alarm Messages Change Password Adjust Output VoltageProgram Unit Name WK DAY MON Hrmn Battery Test SetupComputer Mode Calibration ModeRemote Monitor Mode Modify Low Battery TimeRemote Notification This page intentionally left blank Maintaining the UPS System Important Safety InstructionsE R T I S S E M E N T Performing Preventive MaintenanceMaintenance Training This page intentionally left blank Model Numbers Product SpecificationsSystem Output Battery Specifications This page intentionally left blank System Event Horns Responding to System EventsSystem Event Lights System Event Messages10-2 Rectifier Messages Alarms Rectifier Messages Notices Monitor Panel Alarms Monitor Panel Notices Using the Load OFF Button Resetting the UPS System after Load Off Limited Factory Warranty for THREE-PHASE Powerware Products WarrantyWarranty Page 164201036F