Using Features and Options
6.6 Relay Interface Module
An optional RIM uses relay contact closures to indicate the operating status and alarm condition of the UPS system. A maximum of two monitoring accessories (RMPs, RIMs, or SCMs) can be installed. See Table
Figure 6-4. Relay Interface Module
The RIM can provide the following signals:
UPS AVAILABLE | Pins 1 and 12 | Contacts are closed when the UPS is operating in |
|
| Normal mode or ready to supply the load. |
|
|
|
UPS OFF LINE | Pins 3 and 13 | Contacts are open when the UPS is offline. |
|
| Contacts are closed when the UPS is operating in |
|
| Normal mode. |
|
|
|
BATTERY WEAK | Pins 5 and 14 | Contacts are closed when approximately two |
|
| minutes of battery time is remaining, before the |
|
| critical load is lost. |
UTILITY FAILURE | Pins 6 and 15 | Contacts are closed when Utility Failure is detected. |
|
|
|
EATON Powerware® 9315 UPS |