Eaton Electrical RTC-50 Programming, Introduction, Fixed and Jumper-Selectable Settings

Page 7

Instructional Booklet

Instruction Manual for the Eaton RTC-50 Automatic Transfer Switch Controller

Effective: June 2007

Page 7

SECTION 4: PROGRAMMING

4.1 Introduction

The RTC-50 controller is programmable via the two programming jumpers shown in Figure 2.

The TDNE jumper enables the end-user to select a Time Delay Nor- mal to Emergency setting of either 20 seconds or 50 seconds.

TDNE is a time delay that starts timing when the Generator source becomes available either after the Utility becomes unavailable or after the Go To Generator input is activated. The 50 second set- ting may be used to allow for a longer warm-up period of the Gen- erator.

The FREQ jumper enables the end-user to program the RTC-50 for an operating frequency of either 50 or 60 hertz.

Figure 2. RTC-50 Programming Jumpers.

Table 2 is a summary of the Fixed and Jumper-selectable settings that are available in the RTC-50.

Table 2. Fixed and Jumper-Selectable Settings

DESCRIPTION

RANGE

FACTORY DEFAULT

FIXED/JUMPER

 

 

 

 

Time Delay Normal to Emergency

20 or 50 seconds

20 seconds

Jumper-selectable

 

 

 

 

Time Delay Emergency to Normal

10 seconds

10 seconds

Fixed setting

 

 

 

 

Time Delay Emergency Fail Timer

6 seconds

6 seconds

Fixed setting

 

 

 

 

Nominal Frequency

50 or 60 Hz

60 Hz

Jumper-selectable

 

 

 

 

Nominal Voltage

240 Vac

240 Vac

Fixed setting

 

 

 

 

Utility Undervoltage Dropout

70% of 240 Vac Nominal Voltage

70% of 240 Vac Nominal Voltage

Fixed setting

 

 

 

 

Generator Undervoltage Dropout

70% of 240 Vac Nominal Voltage

70% of 240 Vac Nominal Voltage

Fixed setting

 

 

 

 

Utility Undervoltage Pickup

80% of 240 Vac Nominal Voltage

80% of 240 Vac Nominal Voltage

Fixed setting

 

 

 

 

Generator Undervoltage Pickup

80% of 240 Vac Nominal Voltage

80% of 240 Vac Nominal Voltage

Fixed setting

 

 

 

 

IB00405004E-70-8664

For more information visit: www.eaton.com

Image 7
Contents Eaton RTC-50 Automatic Transfer Switch Controller Product Overview Preliminary Comments and Safety PrecautionsIntroduction General InformationGlossary Functions/FeaturesGeneral LED IndicatorsInput/Output Connectors Hardware DescriptionOutput Connections Go To Generator InputTypical Transfer Operation Specification Summary RTC-50 Controller SpecificationsOperation Operating Voltage and MeasurementsProgramming Fixed and Jumper-Selectable SettingsIntroduction RTC-50 Replacement Maintenance and CareRTC-50 Controller Troubleshooting Troubleshooting GuideUtility is powering the load Appendix a Operational FlowchartGenerator is powering the load Instructional Booklet Effective June IB00405004E-70-8664 Effective June Descripción Información General Sección 1 Introducción PrecauciónAdvertencia Comentarios preliminares y precauciones de seguridadGlosario Conectores de entrada/salida Sección 2 Descripción DEL EquipoIndicadores con diodos emisores de luz LED Programación con los puentesConexiones de salida Entrada para ir al generadorVoltaje operativo y mediciones Sección 3 OperaciónOperación de transferencia típica Introducción Sección 4 ProgramaciónTabla 2. Selecciones fijas y seleccionables con puente Mantenimiento y cuidado Resolución de problemas del controlador RTC-50Tabla 3. Guía para la resolución de problemas Manual de instrucciones para el controlador RTC-50El servicio está alimentando a la carga Apéndice a Diagrama OperativoEl generador está alimentando a la carga Folleto instructivo Folleto instructivo Página Efectivo Junio Sommaire Présentation du matériel Mise EN GardeCommentaires préliminaires et précautions de sécurité GénéralitésFonctions/Particularités GlossaireConnecteurs dentrée et de sortie Description DU MatérielVoyants DEL Programmation des cavaliersConnexions de sortie Entrée du transfert vers la génératriceTension dutilisation et mesures FonctionnementOpération type de transfert Tableau 2. Réglages fixes et à choisir avec cavaliers ProgrammationENTRETIEN, Dépannage ET Remplacement Le courant secteur alimente la charge Annexe a Ordinogramme DE FonctionnementLe courant de génératrice alimente la charge Livret dinstructions Livret dinstructions Mode demploi de la commande RTC-50 pour