Instructional Booklet
Instruction Manual for the Eaton
Effective: June 2007 | Page 5 |
2.5 Go To Generator Input
The
The Control Input “State” definitions are as follows.
Connected - When the input is shorted by an external contact or connection.
Unconnected - When the input is NOT shorted by an external con- tact or connection.
The Go To Generator Input operations are defined as follows.
When this input (J6, pins 1 and 2) is in the “Connected” state, the
2.6 Output Connections
The
•Customer Connections
•Transfer Operation Connections.
2.6.1Customer Connections Load Shed Contacts
There are two sets of load shed contacts for customer use on con- nector J7, Load Shed Contacts #1 and Load Shed Contacts #2. Both sets of contacts are closed when the transfer switch is in the Utility position and both sets are open when the transfer switch is in the Generator position. The output contacts are rated for 5 amps @ 250 VAC. The DC rating is 5 amps @ 30 VDC.
Generator Service Indicator Light
The Generator Service Indicator Light is wired to connector J8, pins 1 and 2. A 5mm
The LED is polarity sensitive. The red lead must be wired to J8, pin 1 and the black lead must be wired to J8, pin 2. If the wiring is reversed, the LED will not light.
The
The
The
Generator Service Reset Switch
The Generator Service Reset Switch is wired to connector J8, pins
3and 4. A momentary
50mA at 24 V. When the pushbutton is pressed, the contacts will close across J8, pins 3 and 4. The pushbutton can be located up to 1000 feet away from the
The Generator Service Reset Switch will enable the
For example, a Generator run time of 450 hours would be shown as four
Pressing the Generator Service Reset Switch will also turn off the Generator Service Indicator Light if it had been lit.
2.6.2 Transfer Operations Connections
The Utility Close and Gen Close outputs are factory wired to oper- ate the transfer switch. The relay contacts for each output are rated for 5 amps @ 250 VAC. The DC rating is 5 amps @ 30 VDC.
Utility Close Outputs
This output is used to transfer to Utility. The Utility Close Outputs are on J6, pins 5 and 6.
Generator Close Outputs
This output is used to transfer to Generator. The Generator Close Outputs are on J6, pins 3 and 4.