Instructional Booklet
Page 6 | Effective: June 2007 |
Instruction Manual for the Eaton
2.7 Specification Summary
Table 1. RTC-50 Controller Specifications
INPUT VOLTAGE | 240 VAC | 50/60 HZ |
Voltage Measurements of | Utility | Generator |
Voltage Measurement Range | 0 to 300 Vac RMS (50/60 Hz) | |
|
|
|
Voltage Measurement Accuracy | ± 6 Vac |
|
|
| |
Undervoltage Dropout | 70% of the Nominal 240 Vac Input Voltage | |
|
| |
Undervoltage Pickup | 80% of the Nominal 240 Vac Input Voltage | |
|
| |
Operating Temperature Range | ||
|
| |
Storage Temperature Range | ||
|
| |
Operating Humidity | 0 to 95% Relative Humidity | |
|
| |
Operating Environment | Resistant to Ammonia, Methane, Nitrogen, Hydrogen, | |
| and Hydrocarbons |
|
|
|
|
Utility Close and Gen Close Outputs | 5 amps @ 250 Vac |
|
| 5 amps @ 30 Vdc |
|
|
|
|
Load Shed Contacts #1 and #2 | 5 amps @ 250 Vac |
|
| 5 amps @ 30 Vdc |
|
Applicable Testing | UL Recognized Component | |
| UL 1008, UL 991 Environmental |
IEC
CISPR 11, Class B FCC Part 15, Class B
SECTION 3: OPERATION
3.1 General
This section specifically describes the operation and functional use of the
The
3.2 Operating Voltage and Measurements
The
The
All voltage monitoring and measurements are true RMS measure- ments.
3.3 Typical Transfer Operation
A typical transfer request will begin with a Utility outage (Utility voltage falls below the 70% dropout level).
When the Generator source meets the requirements to be consid- ered available, the TDNE (Time Delay Normal to Emergency) timer will start timing. TDNE is
When the Utility becomes available (Utility voltage is above the 80% pickup level), the TDEN (Time Delay Emergency to Normal) timer will start timing. TDEN is a fixed delay of 10 seconds. After TDEN times out, the Gen Close Outputs will open, the Utility Close Outputs will close, and the Load Shed Contacts will be closed. This will connect all loads to the Utility source.
For more information visit: www.eaton.com |