Appendix A: Technical Specifications

 

 

Table 13-2. XPress DR+ and XPress DR+W Specifications

 

 

 

 

 

 

 

Category

Description

 

 

 

CPU

Lantronix DSTNI-EX 48 MHz clock

 

 

 

Internal CPU Memory

256 KB SRAM

 

 

 

Flash

2 MB Flash

 

 

 

EEPROM

2 KB EEPROM

 

 

 

Serial Interface

2 RJ45 RS232 Serial Ports

 

 

 

 

Baud rate selectable from 300 to 230 Kbaud

 

 

 

1 Screw terminal RS-422/485 interface on Serial Port 2 (2 and 4 wire support)

 

 

 

LED indicators for TXD and RXD activities

 

 

Serial Line Formats

Characters: 7 or 8 data bits

 

 

 

 

Stop bits: 1 or 2

 

 

 

 

Parity: odd, even, none

 

 

 

Modem Control

DTR, DSR

 

 

 

Flow Control

Hardware: CTS/RTS

 

 

 

 

Software: XON/XOFF

 

 

 

Reset (warm boot)

Front panel recessed push button. (This is not a reset to factory settings.)

 

 

Power Input

Removable screw terminal block connector

 

 

 

9-30 VDC or 9-24 VAC with chassis ground

 

 

 

2.3 Watts maximum

 

 

 

 

 

 

 

Network Interface

2 RJ45 10Base-T/100Base-TX Ethernet ports

 

 

 

Embedded unmanaged fully compliant 802.3u non-blocking Ethernet switch

 

 

 

Store and forward architecture with 1K MAC address lookup table

 

 

 

Automatic MDI/MDI-X crossover

 

 

 

 

Full duplex IEEE 802.3x flow control

 

 

 

Half-duplex back pressure flow control

 

 

 

IEEE 802.1d spanning tree

 

 

 

Dimensions

123 x 57 x 88 mm (4.85 x 2.25 x 3.45 in), terminal blocks included

 

 

Weight

0.21 kg (0.46 lb)

 

 

 

Temperature

Operating range: -40°C to +70° C

(-40 to 158 degrees F)

 

 

Humidity

20% to 90% relative humidity, non-condensing

 

 

Case

High-impact plastic case with integrated DIN-rail (35 mm) mount

 

 

 

IP30 enclosure rating

 

 

 

Protocols Supported

ARP, UDP/IP, TCP/IP, Telnet, ICMP, SNMP, DHCP, BOOTP, TFTP, and HTTP

 

 

Installable Industrial

ModBus TCP, ModBus ASCII/RTU, Multi-Master DF1

 

 

Protocols

 

 

 

 

Management

Internal web server (Standard Tunneling firmware only)

 

 

 

SNMP (read only)

 

 

 

 

Serial login

 

 

 

 

Telnet login

 

 

 

 

DeviceInstaller software

 

 

 

System Software

DeviceInstaller, Windows® 95/98/ME/NT/2000/XP-based configuration software

 

 

 

 

 

 

 