Briggs & Stratton 071019 manual System Setup, Supervisory Control Wiring

Page 7

System Setup

You must perform the following on the control module before operating the system:

If generator is installed in an area regularly subjected to temperatures below 40°F (4°C), select a 50 second warm up time by moving jumper installed on JP2 from ‘20’ position to ‘50’ position.

Place 2 position switch in ‘NG’ or ‘LP’ position, whichever is appropriate for your system.

Place 3 position switch to match KW rating of installed generator.

3 Position

JP2

2 Position

Switch

 

Switch

Supervisory Control Wiring

1.Terminal strip on control module in transfer switch has four connections for customer use. There are two sets of “Normally Closed” contacts available. They will be activated when generator power is required. These can be used for supervisory control of large connected loads on generator. Loads will be allowed to operate if there is enough generator power available.

NOTE: There are two wireways provided to keep the supervisory loads separated from each other.

2.Terminals “A-A” on control module are rated for 24 VAC and air conditioner contactor control. Contacts are connected in series with the air conditioner contactor control circuit.

Air Conditioner Contactor

A A

24 VAC

CT1 & CT2

Connectors

Supervisory

Contacts

3.Terminals “B-B” on control module are rated for 1 Amp 125 VAC and installer supplied contactor to control a large load. Example: electric hot water heater. Contacts are connected in series with the contactor control circuit.

Contactor

B

Neutral

B

115 VAC

 

4.Tighten all wire connections/fasteners to proper torque. See inside transfer switch enclosure for proper torque values.

7

Image 7
Contents 100/200 Amp Automatic Transfer Switch Transfer Switch Where to Find UsDate Purchased Table of Contents Certain components in this product and related Safety RulesOwner Orientation Installer ResponsibilitiesIntroduction For the Home OwnerUnpacking InstallationMounting Guidelines Supervisory Control Wiring System SetupHigh Voltage Wiring Wiring InterconnectionsLow Voltage Wiring To Utility Meter For Models 071020 Operation MaintenanceTesting the Automatic Transfer Switch ControlsProblem Cause Correction TroubleshootingSchematic and Wiring Diagram, Models 071018 Schematic and Wiring Diagram, Models 071020 Limited Warranty Model Product Specifications800 Manual de Instalación y del Operario Conectador Automático Dónde puede encontrarnosFecha de compra Mandos Sistema Funcionamiento Reglas de seguridadDeterminados componentes en este producto y los Reglas de seguridadResponsabilidades del Instalador IntroducciónPara el Propietario Doméstico Orientación para el PropietarioTípico InstalaciónDesempaque Pautas de MontajeCableado de Control de Supervisión Configuración del SistemaCableado de alta tensión Interconexiones de cableadoCableado de baja tensión Para modelos 071018 Para modelos 071020 Prueba del Conectador Automático MandosSistema Funcionamiento MantenimientoReparacion de Averias Garantía Limitada Modelo Especificaciones del productoGuide dInstallation et dUtilisation Commutateur de Transfert Où nous trouverDate d’achat Règles de sécurité Commandes FonctionnementCertains composants de ce produit ainsi que les Règles de sécuritéDescription de léquipement Responsabilités de linstallateurAu propriétaire résidentiel Conseils au propriétaireFonctionnement Entretien Dépannage Garantie Typique Consignes dinstallationSécurité Instalación Commandes DéballageFonctionnement Entretien Dépannage Configuration du systèmeCâblage de contrôle Sécurité InstalaciónCâblage haute tension Interconnexions du câblageCâblage basse tension Pour les modèles 071018 Sécurité Instalación CommandesFonctionnement Entretien DépannagePour les modèles 071020 Mise à lessai du commutateur de transfert automatique CommandesFonctionnement EntretienDépannage Garantie Limitée Modéle Caractéristiques du produitModèle