Briggs & Stratton 071019 manual Wiring Interconnections, High Voltage Wiring, Low Voltage Wiring

Page 8

Wiring Interconnections

All wiring must be the proper size, properly supported and protected by conduit.

Complete the following connections between the transfer switch, main distribution panel, utility power and generator, as shown on the next pages.

WARNING

Low voltage wire cannot be installed in same conduit as power voltage wiring.

Failure to follow above warning could cause personal injury, damage and/or malfunction of equipment.

High Voltage Wiring

1.Ensure utility power is turned OFF. Connect utility feeder conductors to transfer switch terminals marked

“UTILITY CONNNECTION”.

2.Connect utility Neutral conductor to the transfer switch “NEUTRAL” terminal.

3.Connect main breaker panel feeder conductors to transfer switch terminals marked “LOAD

CONNECTION”.

4.Connect main breaker panel Neutral conductor to transfer switch “NEUTRAL” terminal.

5.Connect main breaker panel Ground conductor to the transfer switch “GND” terminal.

NOTE: Assure grounding electrode conductor is connected and bonded per applicable federal, state and local codes, standards and regulations.

6.Connect generator feeder conductors from the generator control panel to transfer switch terminals marked “GENERATOR CONNECTION” Each conductor should pass through hole of current transformer before making connection.

7.Plug in current transformer leads into “CT1” and “CT2” on control module.

8.Connect Neutral conductor from the generator control panel to the transfer switch “NEUTRAL” terminal.

9.Connect generator Ground conductor from the control panel to the transfer switch “GND” terminal.

NOTE: Assure generator equipment grounding conductor is connected per applicable federal, state and local codes, standards and regulations.

10.Connect generator “UTILITY 240 VAC” terminals to transfer switch “UTILITY 240 VAC” terminals. Use minimum #14 AWG conductors.

11.Tighten all wire connections/fasteners to proper torque. See inside transfer switch enclosure for proper torque values.

Low Voltage Wiring

1.Using #18 AWG twisted pair conductors, no greater than 200 ft in length, connect Tx Rx and Tx Rx Ground from the generator control panel to the GND and T/R on the transfer switch control board.

2.Tighten all wire connections/fasteners to proper torque. See inside transfer switch enclosure for proper torque values.

8

BRIGGSandSTRATTON.COM

Image 8
Contents 100/200 Amp Automatic Transfer Switch Date Purchased Where to Find UsTransfer Switch Table of Contents Safety Rules Certain components in this product and relatedInstaller Responsibilities IntroductionFor the Home Owner Owner OrientationMounting Guidelines InstallationUnpacking System Setup Supervisory Control WiringLow Voltage Wiring Wiring InterconnectionsHigh Voltage Wiring To Utility Meter For Models 071020 Maintenance Testing the Automatic Transfer SwitchControls OperationTroubleshooting Problem Cause CorrectionSchematic and Wiring Diagram, Models 071018 Schematic and Wiring Diagram, Models 071020 Limited Warranty 800 Product SpecificationsModel Manual de Instalación y del Operario Fecha de compra Dónde puede encontrarnosConectador Automático Reglas de seguridad Mandos Sistema FuncionamientoReglas de seguridad Determinados componentes en este producto y losIntroducción Para el Propietario DomésticoOrientación para el Propietario Responsabilidades del InstaladorInstalación DesempaquePautas de Montaje TípicoConfiguración del Sistema Cableado de Control de SupervisiónCableado de baja tensión Interconexiones de cableadoCableado de alta tensión Para modelos 071018 Para modelos 071020 Mandos Sistema FuncionamientoMantenimiento Prueba del Conectador AutomáticoReparacion de Averias Garantía Limitada Especificaciones del producto ModeloGuide dInstallation et dUtilisation Date d’achat Où nous trouverCommutateur de Transfert Commandes Fonctionnement Règles de sécuritéRègles de sécurité Certains composants de ce produit ainsi que lesResponsabilités de linstallateur Au propriétaire résidentielConseils au propriétaire Description de léquipementConsignes dinstallation Sécurité Instalación CommandesDéballage Fonctionnement Entretien Dépannage Garantie TypiqueConfiguration du système Câblage de contrôleSécurité Instalación Fonctionnement Entretien DépannageCâblage basse tension Interconnexions du câblageCâblage haute tension Instalación CommandesFonctionnement Entretien Dépannage Pour les modèles 071018 SécuritéPour les modèles 071020 Commandes FonctionnementEntretien Mise à lessai du commutateur de transfert automatiqueDépannage Garantie Limitée Modèle Caractéristiques du produitModéle