NCR 7883 manual Electrical Wiring, Installation Type Input Voltage L1, L2 Circuit Breakers

Page 38

NCR RealScan 7883 Installation and Owner Guide

Electrical Wiring

Input

Voltage

Neutral and Ground Bus

L3

Main Service

Panel

 

Belt Control

Belt

G N

Lighting

Motor

Misc. Equip.

Conduit

Circuit A: Checkstand

Checkstand

Frame

Note: The electrical wiring must meet all electrical codes, laws, and regulations.

Feeder wiring and insulated ground from main service panel to distribution panel to be run in metal conduit.

Isolated/Insulated

Circuit Breakers

 

Ground Bus

NCR circuits should be run in

 

separate metal Conduits.

 

Note: NCR circuits must be dedicated to

L1

NCR equipment or other logically

connected electronic equipment

 

 

(modems, DAA, bridges, etc.)

 

Circuit B: Terminal

L2

 

Neutral

Circuit C: Scanner

Receptacle should be easily

Bus

accessible and near the scanner

Distribution Panel

 

 

Isolated Ground Receptacles

Installation Type

Input Voltage

L1, L2

Circuit Breakers

U.S., Canada, &

100Vac to 120Vac

100Vac to 120Vac

Standard single-pole; value

Japan

 

 

determined by type of device

 

 

 

International

220Vac to 240Vac

220Vac to 240Vac

branch and by electrical code.

 

 

 

 

European

220Vac

220Vac

European double-pole.

20254

38 of 75

04/04

497-0424789 Release F

Image 38
Contents RealScan Installation and Owner Guide Information Products RSD-AtlantaContents Laser Safety Label Laser Module Label Laser Power Revision Record Obtaining Additional Information Obtaining Technical AssistanceNCR RealScan 7883 Mountings Installation Instructions StepStandard Interface Connection Installing Power Supply and Interface CablesConnecting the Cables to an NCR RealScan USB Interface Connection IBM HID Auxiliary RS-232 Port NCR RealScan 7835/7836RealScan 7892 Bi-Modal Presentation Scanner Special InstallationsRS-232 Peripherals RealScan 7837 Programming Programming the RealScanRealScan 7832 Programming Factory Default RS232, 7 DATA, 1 STOP, Space Parity Flash Latest Firmware Programming the RealScan Setting Program Parameters and Verifying Host ConnectionTurning on the RealScan Programming Defaults UPC/EANBaud Rate IBM Communications Programming for USB ConnectionRS-232 Communications RSS Expanded Reduced Space SymbologyRSS-14 Stacked RSS Expanded StackedDisabling RSS Making Other Program ChangesEnabling RSS Scan Sample Tags UPC-ADetermining Label Quality 01234 5 678 9Setting RealScan 7883 Scan Zone Scan Zone Adjusting ScrewHorizontal Pass-by Scanning Vertical Pass-by ScanningVertical Presentation Scanning from Top Vertical Presentation Scanning from BottomPlastic Top Plate Mounting the RealScanRubber Feet Plastic Top Plate ScannerC Latch Clip Mounting Screw Vertical Mounting Bracket Cable Clamps Checkstand CutoutCheckpoint Cable Operating the Scanner Cleaning the Scanner Correcting Scanner Problems Green Status Tones Problem IndicatorThen supply again Most Common Interface Cables Interface ConnectorInterface Information Communications Protocol Options 4 and B not supported yet Communications Protocol Programming Worksheet Features Checkstand Hole RealScan 7883 Horizontal MountCheckstand Hole RealScan 7883 Flat Mount Ventilation RequirementsElectrical Wiring Installation Type Input Voltage L1, L2 Circuit BreakersNCR RealScan Mettler Toledo Scale, & Sensormatic ScanMaxTMHS NCR ComponentsMettler Toledo Components Sensormatic ComponentsLeft-To-Right Scanning System ConstructionRight-TO-Left Scanning Configuring the Scale Installing the Scanner Connecting Sensormatic Components Routing the Cables Completing the Installation Calibrating the Mettler Toledo Scale NCR RealScan 7883 Installation and Owner Guide Sensormatic Deactivation Indicators Sensormatic Programmable FunctionsScale Problems TroubleshootingScanner Problems Sensormatic Deactivation Good Read Tone Programming WorksheetsCommunications Protocol Timers Bar CodesCode Bar Codes Label Identifiers Unique Identifier20 RS-232 Parameters 21 RS-232 Parameters24 RS-232 Communications Options 22 RS-232 Prefix Byte23 RS-232 Terminator Byte Miscellaneous Parameters RealScan Ascii Code Chart Regulatory Information Identification LabelsCE Mark Applicability NCR Corporation Duluth, GaDeclaration of Conformity Laser Module Label Laser SafetyLaser Safety Label Laser Power Default Volume AdjustmentReset Programming TagsEnd Programming ModeSave and Reset Abort Diagnostic ModeRS-232 Temporary Service Mode Reset Tallies ModeFirmware Flashing HexR0050 R0053 Hex a Hex D Hex BHex C Hex E Hex F