Section 8 - Troubleshooting/Maintenance

8.1 Conditions Requiring Troubleshooting

Four conditions may occur, which require operators or service personnel to troubleshoot the function of the power conditioner. Each may be individually evaluated. These four occurrences include:

1.Source circuit breaker (at switchgear or distribution panelboard) trips out

2.Front panel circuit breaker trips out

3.TVSS Fault LED (one or more) illuminate

4.Harmonic filter circuit breaker trips out (if equipped with harmonic filter option)

8.1.1 Source Circuit Breaker Trip

The power conditioner utilizes a low-impedance isolation transformer. When first energized, transformers of this kind typically exhibit a high "inrush" current that may approach 10-15 times the nominal rating. While inrush currents quickly decay to nominal, it is possible to occasionally experience "nuisance" tripping of the source circuit breaker. If this occurs, consult the manufacturer for direct assistance in troubleshooting this condition.

8.1.2 Input Circuit Breaker Trips

In the event the front panel breaker on the power conditioner trips out, one of five conditions is likely at fault. You may effectively troubleshoot this condition by checking each of the following five areas. They are listed in order or probability.

8.1.2.1Electrical Load Has Exceeded Capacity - If the amount of electrical load has exceeded the capacity of the power conditioner, the front panel circuit breaker is designed to trip. Load may exceed capacity as a result of a short circuit in the load or too much load having been added to the power conditioner. In either event, turn off all load power switches and recycle power to the conditioner by turning the circuit breaker handle to the extreme counter-clockwise position and then rotating back to the clockwise “On” position. If this restores the power conditioner to normal operation (with no loads powered up) it will be necessary to either remove load from the conditioner or troubleshoot the load to determine if a short circuit condition exists.

8.1.2.2Phase Loss or Low Voltage Occurrence - This condition will cause the front panel circuit breaker to trip only if the power conditioner is equipped with the power management option. To troubleshoot this condition, rotate the circuit breaker handle to the extreme counter-clockwise position and then rotate clockwise to the “On” position. If the phase loss/low voltage condition was temporary the power conditioner will once again be operating and the 7500 ION monitor can be used to retrieve the phase loss or low voltage data from the log files. If after resetting the circuit breaker it immediately trips out once again, this is an indication that the phase loss or low voltage condition is still present. If a phase loss or low voltage is found not to exist consult the following sections for information on further troubleshooting on additional failure conditions.

30

Conditioned Power Center

Image 30
Contents CPC Series Conditioned Power Center Table of Contents Service and Support E a S E General Inherent Hazards SafetyAnsi Warning Notices Alerts and LabelsLine Voltage Present With Machine Power OFF Wear protective gear before servicing internal partsSafety Interlocks Lockout/TagoutConformance with Applicable Laws and Regulations Product LiabilityEmergency Contact Information Product Overview Product PurposeStandard Features Optional FeaturesFeature Preparation UnpackagingPreparation Figure D Shipping Crate Disassembly 10 to 20 kVA Installation Main Input Circuit Breaker Outer Panel RemovalAlternate Conduit Landing Locations Fixed Input Circuit BreakersIsolation Transformer Programmable Circuit BreakersTransformer Primary Voltage Adjustment Figure GOutput Voltage Fine Adjustment GroundingLockout/Tagout Procedure Figure JInput Power Connections Output Power ConnectionsModels With Optional Line Cord/Output Receptacles Restoring For Service Energizing the Power ConditionerOperation Energizing the Load Orderly ShutdownConditioned Power Center External EMO Phase Loss/Low Voltage Detection and ProtectionOptions Seismic AnchorageInput Power Conductor Restraints Semi S2-0200 CertificationSemi S2-0200 Compliant EMO Options Source Circuit Breaker Trip Troubleshooting/MaintenanceConditions Requiring Troubleshooting Input Circuit Breaker TripsTvss Fault LEDs Illuminate Routine Maintenance Harmonic Filter Circuit Breaker Trips OutService and Support Technical and Service Assistance Customer ServiceProduct Warranty Specifications CPC Series SchematicGPI Series 2000 Standard EMO GPI Series 2000 Semi S2 EMO Output Voltage Fine Adjustment Important ALL Work to be Done By a Licensed ElectricianDocument Revision History Title Rev. Letter Rel. Date Next Rev. LevelSM5505- Rev. a 03/01/2006, 2006 ETA Systems39