Energy Tech Laboratories EDP70 manual Storage, Installation, Mechanical characteristics

Page 13

3.0STORAGE

If the EDP70 PLUS UPS cannot be installed within sixty days of delivery, there is a danger of the integral battery becoming discharged thereby sustaining permanent damage and affecting the standby period available and battery life. The date the battery was last recharged and the date the battery is due for its next recharge are both stamped on the packaging accompanying the unit. If you intend to store the unit, please refer to the recharge date.

When the EDP70 PLUS is due to be recharged, refer to the Installation instructions and connect the EDP70 PLUS UPS to a temporary AC supply. The battery MUST be recharged for at least 24 hours every 3 months.

4.0INSTALLATION

4.1Mechanical characteristics

-

Ambient temperature

 

 

 

18°F[-10°C] to 104°F [+40°C ]

 

- Relative Humidity (w/out condensing @ 68°F[20°C])

< 90%

 

 

- Max altitude (w/out derating)

 

3300 feet [1000 m] above sea-level

 

- Protection degree (panel fitted)

 

 

 

 

 

 

-

Input cables

 

 

 

 

bottom

 

-

Air inlet

 

 

 

 

 

bottom

 

-

Air outlet

 

 

 

 

 

rear

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS model

 

 

 

Description

u.m.

 

24

36

 

 

50

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Size

width

In

 

27.5 [700]

27.5 [700]

 

 

35.4 [900]

35.4 [900]

 

 

 

depth

[mm]

 

28.7 [730]

28.7 [730]

 

 

28.7 [730]

28.7 [730]

 

 

 

height

 

 

56 [1420]

56 [1420]

 

 

63 [1600]

63 [1600]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total

w/out cells

Lbs

 

880 [400]

1300 [590]

 

1342 [610]

1800 [818]

 

 

Weight

25 Ah cells

[kg]

 

1342 [610]

n.a.

 

 

n.a.

n.a.

 

 

(UPS +

30 Ah cells

 

 

1456 [662]

n.a.

 

 

 

 

 

 

 

 

n.a.

n.a.

 

 

Battery)

35 Ah cells

 

 

1526 [694]

n.a.

 

 

 

 

 

 

 

 

n.a.

n.a.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Floor Area

In2[m2]

 

789 [0.511]

789 [0.511]

 

1019 [0.657]

1019 [0.657]

 

 

Floor

w/out cells

Lbs/in2

 

1.12 [782]

1.65 [1155]

 

1.32 [930]

1.77 [1245]

 

 

Loading

25 Ah cells

[kg/m2]

 

1.70 [1194]

n.a.

 

 

n.a.

n.a.

 

 

(UPS +

30 Ah cells

 

 

1.85 [1296]

n.a.

 

 

 

 

 

 

 

 

n.a.

n.a.

 

 

Battery)

35 Ah cells

 

 

1.93 [1358]

n.a.

 

 

 

 

 

 

 

 

n.a.

n.a.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air-Flow

cfm

 

235

647

 

 

 

 

 

 

 

 

[mc/h]

 

[400]

[1100]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Acoustic Noise

dBA

 

52

55

 

 

 

 

 

 

100% Linear Load

 

 

 

 

 

 

 

 

Notes:

1)

n.a. = not applicable

 

 

 

 

 

 

2)Longer autonomies, and battery for EDP above 20 kVA are available with external battery cubicles.

MI00/10056 rev.1--05/2001-- page 13

Image 13
Contents EDP70 Plus Important Safety Instructions Read Before Installing ALL CASES, Seek Medical Attention Immediately Contents Figures Introduction Block diagramSummary of the manual Summary of the equipment24kVA Standard Configuration 480V Functions24/36kVA Ratings Operational modes 10 --MI00/10056 rev.1--05/2001 General safety SafetySymbols Battery precautions Electrical precautionsBattery safety equipment Mechanical characteristics InstallationStorage ALL Measurements are Millimeters and Inches NR4 16 --MI00/10056 rev.1--05/2001 Battery Cabinet Drawing for 24/36kVA Ratings 18 --MI00/10056 rev.1--05/2001 Battery Cabinet Drawing for 50/80kVA Ratings 20 --MI00/10056 rev.1--05/2001 Installation Recommended wire sizes Supply Output Reserve Supply UPS Type = 2770 - - - ∙ e 0.125 h Tk / T0 Tr Tk VentilationOutput ConnectionUninterruptible Power System No Unauthorized Operation MI00/10056 rev.1--05/2001-- Electrical connections Table of T& B’s cat.no.s for terminals and crimp tools24 12/18/24kVA Battery CompartmentOutput, Reserve, Input Reserve Ground Primary Input Output External Batteries 36 24/30/36kVA Observe Polarities and Orientations RS232 Female EDP70 Plus 50/80kVA 36 --MI00/10056 rev.1--05/2001 QS1 QS2 QS3 QS4 QS5 Emergency Power Off Signal connectionsBattery charge inhibited Thermostick connector 50/80kVA onlyControls Display indicatorsUser Controls LCD Control PanelStart UP Installing the EPO Maintenance BypassSHUT-DOWN MI00/10056 rev.1--05/2001-- Silencing Audible Alarm Visual and Audible AlarmsMimic Liquid Crystal DisplaySystem Normal Display Page HeadingsBattery Test Weekly Power History Down to Access Load Time on Reserve xxg xxh xxm xxs Inverter Load System Alarm Abnormal operating mode messagesStop DUE to Overload RECTIFIER/BATTERY Alarms Message Condition Inverter Alarms Message Condition LOAD/RESERVE Alarms Message Condition Power History Matrix Power HistoryBattery Autonomy Test Battery TestResetting data loss manually MI00/10056 rev.1--05/2001-- 11.1 AS400 Computer Interface11.2 RS232 Remote AlarmsBatteries 13.1 EDP70 PLUS/24/18/12 Battery Installation/Start-up13.2 EDP70 PLUS/24/18/12 Optional Battery Cubicle = EDP70 PLUS/24/18/12 Internal Battery Shelves13.3 EDP70 Plus above 20kVA Battery Installation/Start-up Maintenance and Spare Parts13.4 EDP70 Plus above 20kVA Battery Cubicle EDP70 Plus System LOG