Energy Tech Laboratories EDP70 manual Remote Alarms, 11.2 RS232

Page 61

11.2RS232

The EDP70 PLUS UPS is fitted with a 9 pin male ‘D’ type plug which enables a communication link to be established between a computer and the microprocessor controller in the EDP70 PLUS UPS. The link allows the Chloride ‘EASY PLUS’ and ‘LIFE 2000’ software to be run on an IBM compatible PC. The link also allows the communications with a Master JBUS and Multicom/LIFE 2000 adapter.

The function of the pins on the socket are shown below:

The function of each pin is the following :

 

 

Pin 1

DCD

(Data Carrier Detect)

Pin 2

RXD

(Received data)

Pin 3

TXD

(Transmitted data)

Pin 4

DTR

(Data terminal ready)

Pin 5

GND

(Ground)

Pin 6

DSR

(Data Set Ready)

Pin 7

RTS

(Request To Send)

Pin 8

CTS

(Clear To Send)

The signals applied on each pin follows the standard EIA RS232.

12.0REMOTE ALARMS

Remote indication of the state of the EDP70 PLUS UPS is provided by a 15 pin female ‘D’ type socket and is designed to be used in conjunction with the Chloride EDP Remote Alarm Unit. The function of the pins on the socket are shown below:

Fig.22: EDP70 PLUS Remote Alarms Pin Layout

Pin 1 System normal signal

Pin 2 System normal and system summary alarm ground

Pin 3 Inverter fail signal

Pin 4 Inverter fail ground

Pin 5 Reserve to load signal

Pin 6 Reserve to load ground

Pin 7 Primary supply failure signal

Pin 8 Primary supply failure ground

Pin 9 Shutdown imminent signal

Pin 10 Shutdown imminent ground

Pin11, 12 supply: 18V/200mA nominal AC output

Pin 15 Summary alarm signal

Pins 1,2 and15 are available for use as a remote summary alarm indicator in alternative to the Chloride Remote Alarm Unit. All pins are volt free contacts which are capable of carrying a current of 0.5 A and switching 30 V.

MI00/10056 rev.1--05/2001-- page 61

Image 61
Contents EDP70 Plus Important Safety Instructions Read Before Installing ALL CASES, Seek Medical Attention Immediately Contents Figures Introduction Block diagramSummary of the manual Summary of the equipment24kVA Standard Configuration 480V Functions24/36kVA Ratings Operational modes10 --MI00/10056 rev.1--05/2001 General safety SafetySymbols Battery precautions Electrical precautionsBattery safety equipment Mechanical characteristics InstallationStorage ALL Measurements are Millimeters and Inches NR4 16 --MI00/10056 rev.1--05/2001 Battery Cabinet Drawing for 24/36kVA Ratings 18 --MI00/10056 rev.1--05/2001 Battery Cabinet Drawing for 50/80kVA Ratings 20 --MI00/10056 rev.1--05/2001 Installation Recommended wire sizes Supply Output Reserve Supply UPS Type = 2770 - - - ∙ e 0.125 h Tk / T0 Tr Tk VentilationOutput ConnectionUninterruptible Power System No Unauthorized Operation MI00/10056 rev.1--05/2001-- Electrical connections Table of T& B’s cat.no.s for terminals and crimp tools24 12/18/24kVA Battery CompartmentOutput, Reserve, Input Reserve Ground Primary Input Output External Batteries 36 24/30/36kVA Observe Polarities and Orientations RS232 Female EDP70 Plus 50/80kVA 36 --MI00/10056 rev.1--05/2001 QS1 QS2 QS3 QS4 QS5 Emergency Power Off Signal connectionsBattery charge inhibited Thermostick connector 50/80kVA onlyControls Display indicatorsUser Controls LCD Control PanelStart UP Installing the EPO Maintenance BypassSHUT-DOWN MI00/10056 rev.1--05/2001-- Silencing Audible Alarm Visual and Audible AlarmsMimic Liquid Crystal DisplaySystem Normal Display Page HeadingsBattery Test Weekly Power History Down to Access Load Time on Reserve xxg xxh xxm xxs Inverter Load System Alarm Abnormal operating mode messagesStop DUE to Overload RECTIFIER/BATTERY Alarms Message Condition Inverter Alarms Message Condition LOAD/RESERVE Alarms Message Condition Power History Matrix Power HistoryBattery Autonomy Test Battery TestResetting data loss manually MI00/10056 rev.1--05/2001-- 11.1 AS400 Computer Interface11.2 RS232 Remote AlarmsBatteries 13.1 EDP70 PLUS/24/18/12 Battery Installation/Start-up13.2 EDP70 PLUS/24/18/12 Optional Battery Cubicle = EDP70 PLUS/24/18/12 Internal Battery Shelves13.3 EDP70 Plus above 20kVA Battery Installation/Start-up Maintenance and Spare Parts13.4 EDP70 Plus above 20kVA Battery Cubicle EDP70 Plus System LOG