13.3EDP70 PLUS above 20kVA: Battery Installation/Start-up
SAFETY
-Ensure the Equipment ON/OFF Switch is turned to OFF before starting to install the batteries. If the Equipment ON/OFF Switch is not turned to OFF the equipment and battery may be damaged. It is also essential for safety reasons that the battery connectors are disconnected before to remove the fuse of the battery cubicle.
-Stand on a rubber mat and use insulated tools.
-Remove all personal effects, rings, watches, pens, which might cause a short circuit when working on the battery. Batteries are live at all times and short circuits can melt metals and cause injury, damage or fire.
-DO NOT smoke or use naked flames and avoid creating arcs or sparks when working on the equipment; do not wear clothes which may generate static electricity.
-The sealed
13.4EDP70 PLUS above 20kVA: Battery Cubicle
For these sizes of EDP70 PLUS, the batteries are housed in battery cubicles. Both the UPS and battery cubicles are similar in appearance, however, the battery cubicle does not have a dusplay.
The battery cubicle has a separate fuse, located internally. To connect the battery cubicle to the EDP70 PLUS UPS follow the following procedure:
1.Shutdown the UPS using the procedure set out in section 9. Access the terminal rail.
2.Be sure that all the batteries in the cubicle(s) are disconnected. Remove the fuses from the battery cubicle(s).
4.Wire the cubicle according to the extension battery cubicle wiring instructions and the relevant battery layout diagram.
5.Replace the fuses on all the cubicles then connect all the
14.0 MAINTENANCE AND SPARE PARTS
The EDP70 PLUS UPS is designed to be virtually user maintenance free, requiring | only | the occasional wipe |
with a damp cloth or |
|
|
Spares kits are available for the EDP70 PLUS series, please contact a Chloride | Power | Electronics service |
center for details. |
|
|