Energy Tech Laboratories EDP70 manual Abnormal operating mode messages, System Alarm

Page 52

10.5Abnormal operating mode messages

Under abnormal operating conditions, the normal functioning heading on the main page

UPS xx KVA

SYSTEM NORMAL

is replaced with the alarm page:

UPS xx KVA

SYSTEM ALARM

If at least 1 alarm is activated for each block; the »NO ALARMS ACTIVE» message in the second line on the display is replaced with the first active alarm. Whenever there is more than one active alarm, they can be scrolled

through using the

and

keys.

Each message is associated with one of the following conditions:

NORMAL

Conditions which do not adversely affect the normal functioning of the machine are identified under this heading.

No action is required on the part of the operator.

WARNING

Transitory conditions which can either return to normal condition or result in a permanent fault are identified under this heading. No action is required on the part of the operator.

FAULT

Faults are identified under this heading. The intervention of a qualified technician is required.

Alarms which do not come under any of these headings do not require any action if arising separately.

MAIN PAGE HEADING ALARMS

MESSAGE

CONDITION

TESTING BATTERY

NORMAL

 

 

EPO ACTIVE

WARNING

 

 

NOT CALIBRATED

FAULT

 

 

TESTING AUTONOMY

WARNING

 

 

SYSTEM TEST MODE

FAULT

 

 

page 52 --MI00/10056 rev.1--05/2001

Image 52
Contents EDP70 Plus Important Safety Instructions Read Before Installing ALL CASES, Seek Medical Attention Immediately Contents Figures Block diagram IntroductionSummary of the manual Summary of the equipment24kVA Standard Configuration Functions 480VOperational modes 24/36kVA Ratings10 --MI00/10056 rev.1--05/2001 General safety SafetySymbols Battery precautions Electrical precautionsBattery safety equipment Mechanical characteristics InstallationStorage ALL Measurements are Millimeters and Inches NR4 16 --MI00/10056 rev.1--05/2001 Battery Cabinet Drawing for 24/36kVA Ratings 18 --MI00/10056 rev.1--05/2001 Battery Cabinet Drawing for 50/80kVA Ratings 20 --MI00/10056 rev.1--05/2001 Installation Recommended wire sizes Supply Output Reserve Supply UPS Type Ventilation = 2770 - - - ∙ e 0.125 h Tk / T0 Tr TkConnection OutputUninterruptible Power System No Unauthorized Operation MI00/10056 rev.1--05/2001-- Table of T& B’s cat.no.s for terminals and crimp tools Electrical connectionsBattery Compartment 24 12/18/24kVAOutput, Reserve, Input Reserve Ground Primary Input Output External Batteries 36 24/30/36kVA Observe Polarities and Orientations RS232 Female EDP70 Plus 50/80kVA 36 --MI00/10056 rev.1--05/2001 QS1 QS2 QS3 QS4 QS5 Signal connections Emergency Power OffBattery charge inhibited Thermostick connector 50/80kVA onlyControls Display indicatorsUser Controls Control Panel LCDStart UP Installing the EPO Maintenance BypassSHUT-DOWN MI00/10056 rev.1--05/2001-- Visual and Audible Alarms Silencing Audible AlarmMimic Liquid Crystal DisplayDisplay Page Headings System NormalBattery Test Weekly Power History Down to Access Load Time on Reserve xxg xxh xxm xxs Inverter Load Abnormal operating mode messages System AlarmStop DUE to Overload RECTIFIER/BATTERY Alarms Message Condition Inverter Alarms Message Condition LOAD/RESERVE Alarms Message Condition Power History Power History MatrixBattery Autonomy Test Battery TestResetting data loss manually MI00/10056 rev.1--05/2001-- Computer Interface 11.1 AS400Remote Alarms 11.2 RS23213.1 EDP70 PLUS/24/18/12 Battery Installation/Start-up Batteries= EDP70 PLUS/24/18/12 Internal Battery Shelves 13.2 EDP70 PLUS/24/18/12 Optional Battery Cubicle13.3 EDP70 Plus above 20kVA Battery Installation/Start-up Maintenance and Spare Parts13.4 EDP70 Plus above 20kVA Battery Cubicle EDP70 Plus System LOG