Simplicity 514067-UAD-A-0509 manual Overview, Wire Connections

Page 1

APPLICATION GUIDE

Simplicity®LINC GATEWAY

OVERVIEW

The Simplicity®LINC Gateway operates as a Modbus® Client providing an interface between a BACnet® MS/TP control system and devices that communicate using the Modbus RTU protocol. The Simplicity®LINC allows monitoring and control by a third-party BACnet Building Automation System (BAS).

The Simplicity®LINC is preconfigured to provide an interface to UP products equipped with Simplicity® controllers manufactured after 4/2/2008 as well as prior Simplicity®Elite™ and Simplicity® with Intelli-Comfort™ controllers.

R

C

The Simplicity®LINC mounts inside the control panel of the UP unit and utilizes 24 VAC power from the unit’s control transformer. One port is connected to the UP controller. The other port must be connected to the BACnet MS/TP network.

The Simplicity®LINC Gateway is preconfigured to obtain operational data points from the controller and expose them on a BACnet MS/TP network.

NOTE: Not all Simplicity® operating parameters are controlled/ monitored by the Simplicity®LINC.

24 — must be grounded close to the Simplicity®LINC

24V power is polarity sensitive, incorrect wiring could result in board damage.

FIGURE 1: WIRE CONNECTIONS

The shield must be connected to ground at each device.

514067-UAD-A-0509

Image 1
Contents Overview Wire ConnectionsConnection Baud Rate Selection SettingsModbus Connection Flash Memory Management Modbus Communication AlarmPoints List in Description Order Default Min Max Point DescriptionBACnet Read Object InstBACnet Read Object Write Inst Descriptor Default Min Max Point DescriptionMax Point Description Efreezest Lowsupvolt Read Object Write Default Min Max Point DescriptionPoints List in Object Order ALARM3 Spcealmtim Points List in Object Order Descriptor Default Min Max Point Description Iifanstat Simplicitylinc Gateway TroubleshootingSimplicitylinc Gateway LED Location PWRJohnson Controls Unitary Products York Drive Norman, OK