Simplicity 514067-UAD-A-0509 manual Lowsupvolt

Page 8

514067-UAD-A-0509

TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)

 

BACnet

BACnet

 

 

 

 

 

Read/

Object

Object

 

 

 

 

 

Write

Type

Inst

Descriptor

Default

Min

Max

Point Description

R

(5) BV

14

LOW_SUP_VOLT

Low Supply Voltage (0=comps not overrid-

 

 

 

 

 

 

 

den by LSV, 1=comps overridden)

R/W

(5) BV

96

MANUAL_WRITE

Manual Write Command to ModlINC

R/W

(2) AV

28

MAX_TH_OFSET

3

0

5

Max Temperature/Humidity Setpoint Offset

R/W

(2) AV

30

MAX_DMV_ECON

50

0

100

Maximum Demand Ventillation Economizer

 

 

 

 

 

 

 

Position

R

(5) BV

11

MODBUS_ALARM

Modbus Communication Alarm

R

(5) BV

9

MOD_EX_INST

Modulating Exhaust Installed

R/W

(2) AV

61

MWU_RAT_STPT

70

50

85

Morning Warm-Up and VAV Heating: Return

 

 

 

 

 

 

 

Air Temperature Setpoint (degrees F)

R

(5) BV

6

MORN_WARM-UP

Morning Warm-Up Enabled

R

(2) AV

16

NUMBER_COMPS

Number of Compressors Available

R

(2) AV

48

NUMBER_HEAT

Number of Heat Stages Available

R/W

(2) AV

1

OCC_COOL_SP

72

45

99

Occupied Cooling Setpoint

R/W

(5) BV

1

OCCUPIED_ENA

Occupied Enabled

R/W

(2) AV

50

OCC_HEAT_SP

68

45

99

Occupied Heating Setpoint

R

(5) BV

93

OCC_COMS_ENA

Occupied Thermostat or Communication

 

 

 

 

 

 

 

Input Enabled

R

(2) AV

17

OP_COOL_STPT

Operating Cooling Setpoint

R

(2) AV

49

OP_HEAT_STPT

68

45

99

Operating Heating Setpoint

R/W

(2) AV

69

OP_STPT_DIF

1

1

5

Operating Setpoint Differential

R/W

(2) AV

74

OAT_COOL_L_O

45

0

100

Outdoor Air Temperature Cooling Lockout

 

 

 

 

 

 

 

Temperature

R/W

(2) AV

54

OAT_HEAT_L_O

75

0

100

Outdoor Air Temperature HeatingLockout

 

 

 

 

 

 

 

Temperature

R

(2) AV

11

AMB_AIR_ENTH

Outside Air Enthalpy

R

(2) AV

10

AMB_AIR_HUM

Outside Air Humidity

R

(5) BV

37

OAH_SENSOR

Outside Air Humidity Sensor Enabled

R

(2) AV

7

AMB_TEMP

Outside Air Temperature

R

(2) AV

9

OAQ_VALUE

1000

0

5000

Outside Demand Ventilation (OAQ) Value

 

 

 

 

 

 

 

(PPM)

R

(5) BV

8

PWR_EX_INST

Power Exhaust Installed

R

(5) BV

20

POP_ENABLED

Pre-Occupancy Purge Enabled

R/W

(2) AV

81

POP_HOURS

4

0

23

Pre-Occupancy Purge Time (hours)

R/W

(2) AV

82

POP_MINUTES

0

0

59

Pre-Occupancy Purge Time (minutes)

R

(5) BV

17

PURGE_SWITCH

Purge Switch Status (0=open,1=closed)

R/W

(5) BV

12

REDLINE

Redline (0=clear redline, 1=set redline

 

 

 

 

 

 

 

operation)

R

(5) BV

4

REM_CONT_ENA

Remote Control Enabled

R

(2) AV

13

RET_AIR_ENTH

Return Air Enthalpy

R

(2) AV

12

RET_AIR_HUM

Return Air Humidity

R

(2) AV

5

RET_AIR_TEMP

Return Air Temperature

R

(5) BV

38

RAH_SENSOR

Return/Inside Air Humidity Sensor Enabled

R

(2) AV

6

SPACE_TEMP

Space (Indoor) Air Temperature

8

Johnson Controls Unitary Products

Image 8
Contents Wire Connections OverviewModbus Connection Baud Rate Selection SettingsConnection Modbus Communication Alarm Flash Memory ManagementDefault Min Max Point Description Points List in Description OrderBACnet Read Object InstInst Descriptor Default Min Max Point Description BACnet Read Object WriteMax Point Description Efreezest Lowsupvolt Default Min Max Point Description Read Object WritePoints List in Object Order ALARM3 Spcealmtim Points List in Object Order Descriptor Default Min Max Point Description Iifanstat Troubleshooting Simplicitylinc GatewayPWR Simplicitylinc Gateway LED LocationJohnson Controls Unitary Products York Drive Norman, OK