Simplicity 514067-UAD-A-0509 manual Points List in Description Order, BACnet Read Object, Inst

Page 4

514067-UAD-A-0509

TABLE 2: POINTS LIST IN DESCRIPTION ORDER

 

BACnet

BACnet

 

 

 

 

 

Read/

Object

Object

 

 

 

 

 

Write

Type

Inst

Descriptor

Default

Min

Max

Point Description

R

(2) AV

14

ACC_OVER_TME

Accumulated Unoccupied Override Time

 

 

 

 

 

 

 

(in hours)

R

(2) AV

15

ACTIVE_ALARM

Active Alarm

R

(5) BV

16

AIR_PROOF_SW

Air Proving Switch Status (1=closed,

 

 

 

 

 

 

 

0=open/no air flow)

R/W

(2) AV

79

OAQ_STPT

1000

0

5000

Air Quality Setpoint Outside

R

(5) BV

85

ALARM_1_ON

Alarm Buffer #1 (0=Alarm has cleared,

 

 

 

 

 

 

 

1=Alarm is still active)

R

(5) BV

86

ALARM_2_ON

Alarm Buffer #2 (0=Alarm has cleared,

 

 

 

 

 

 

 

1=Alarm is still active)

R

(5) BV

87

ALARM_3_ON

Alarm Buffer #3 (0=Alarm has cleared,

 

 

 

 

 

 

 

1=Alarm is still active)

R

(5) BV

88

ALARM_4_ON

Alarm Buffer #4 (0=Alarm has cleared,

 

 

 

 

 

 

 

1=Alarm is still active)

R

(5) BV

89

ALARM_5_ON

Alarm Buffer #5 (0=Alarm has cleared,

 

 

 

 

 

 

 

1=Alarm is still active)

R

(2) AV

33

BLDG_STATIC

Building Static Pressure

R

(5) BV

29

BP_SENS_INST

Building Static Pressure Sensor Installed

R/W

(2) AV

57

BLDG_SP_STPT

0.1

-0.25

0.25

Building Static Pressure Setpoint

R/W

(2) AV

25

COM_V_LOW_SP

70

60

85

Comfort Ventilation LowerSetpoint

 

 

 

 

 

 

 

(degrees F)

R

(5) BV

34

CVM_COOLING

Comfort Ventilation Mode for Cooling

 

 

 

 

 

 

 

Enabled

R

(5) BV

35

CVM_HEATING

Comfort Ventilation Mode for Heating

 

 

 

 

 

 

 

Enabled

R

(5) BV

33

COM_VENT_STA

Comfort Ventilation Mode Status (1=control

 

 

 

 

 

 

 

is in Comfort Vent mode, 0= it is not)

R/W

(2) AV

24

COM_V_HI_SP

80

60

85

Comfort Ventilation Upper Setpoint

 

 

 

 

 

 

 

(degrees F)

R

(5) BV

23

COOLING_ENA

Cooling Mode Enabled

R

(5) BV

21

FAN_ON_W_SEN

CV - Indoor Fan Operates with Space

 

 

 

 

 

 

 

Sensor Present Option Enabled

R

(2) AV

56

CV_VAV_SELEC

CV/VAV Selected (0= Valid CV, 1=Valid

 

 

 

 

 

 

 

VAV, 2= Invalid Value)

R

(2) AV

8

IAQ_VALUE

Demand Ventilation (IAQ) Value (PPM)

R

(5) BV

39

DEMAND_VENT

Demand Ventilation (using Inside Sensor)

 

 

 

 

 

 

 

Enabled

R/W

(2) AV

18

DEMVENT_STPT

1000

0

5000

Demand Ventilation Setpoint

R

(2) AV

67

REVISION

xx

Device Revision

R

(5) BV

90

DF_SW_INST

Dirty Filter Switch Installed

R

(5) BV

15

DIRT_FILT_SW

Dirty Filter Switch Status (0=open,1=closed/

 

 

 

 

 

 

 

fault)

R

(2) AV

35

DUCT_STATIC

Duct Static Pressure

R/W

(2) AV

58

DUCT_SP_STPT

1.5

0

5

Duct Static Pressure Setpoint

R/W

(2) AV

59

DUCT_SD_STPT

4.5

0

5

Duct Static Pressure Shutdown Setpoint

R

(2) AV

31

ECO_DAMP_OUT

Economizer Damper Output Status

 

 

 

 

 

 

 

(0-100%)

4

Johnson Controls Unitary Products

Image 4
Contents Wire Connections OverviewConnection Baud Rate Selection SettingsModbus Connection Modbus Communication Alarm Flash Memory ManagementDefault Min Max Point Description Points List in Description OrderBACnet Read Object InstInst Descriptor Default Min Max Point Description BACnet Read Object WriteMax Point Description Efreezest Lowsupvolt Default Min Max Point Description Read Object WritePoints List in Object Order ALARM3 Spcealmtim Points List in Object Order Descriptor Default Min Max Point Description Iifanstat Troubleshooting Simplicitylinc GatewayPWR Simplicitylinc Gateway LED LocationJohnson Controls Unitary Products York Drive Norman, OK