TABLE 2: POINTS LIST IN DESCRIPTION ORDER
| BACnet | BACnet |
|
|
|
|
|
Read/ | Object | Object |
|
|
|
|
|
Write | Type | Inst | Descriptor | Default | Min | Max | Point Description |
R | (2) AV | 14 | ACC_OVER_TME | – | – | – | Accumulated Unoccupied Override Time |
|
|
|
|
|
|
| (in hours) |
R | (2) AV | 15 | ACTIVE_ALARM | – | – | – | Active Alarm |
R | (5) BV | 16 | AIR_PROOF_SW | – | – | – | Air Proving Switch Status (1=closed, |
|
|
|
|
|
|
| 0=open/no air flow) |
R/W | (2) AV | 79 | OAQ_STPT | 1000 | 0 | 5000 | Air Quality Setpoint Outside |
R | (5) BV | 85 | ALARM_1_ON | – | – | – | Alarm Buffer #1 (0=Alarm has cleared, |
|
|
|
|
|
|
| 1=Alarm is still active) |
R | (5) BV | 86 | ALARM_2_ON | – | – | – | Alarm Buffer #2 (0=Alarm has cleared, |
|
|
|
|
|
|
| 1=Alarm is still active) |
R | (5) BV | 87 | ALARM_3_ON | – | – | – | Alarm Buffer #3 (0=Alarm has cleared, |
|
|
|
|
|
|
| 1=Alarm is still active) |
R | (5) BV | 88 | ALARM_4_ON | – | – | – | Alarm Buffer #4 (0=Alarm has cleared, |
|
|
|
|
|
|
| 1=Alarm is still active) |
R | (5) BV | 89 | ALARM_5_ON | – | – | – | Alarm Buffer #5 (0=Alarm has cleared, |
|
|
|
|
|
|
| 1=Alarm is still active) |
R | (2) AV | 33 | BLDG_STATIC | – | – | – | Building Static Pressure |
R | (5) BV | 29 | BP_SENS_INST | – | – | – | Building Static Pressure Sensor Installed |
R/W | (2) AV | 57 | BLDG_SP_STPT | 0.1 | 0.25 | Building Static Pressure Setpoint | |
R/W | (2) AV | 25 | COM_V_LOW_SP | 70 | 60 | 85 | Comfort Ventilation LowerSetpoint |
|
|
|
|
|
|
| (degrees F) |
R | (5) BV | 34 | CVM_COOLING | – | – | – | Comfort Ventilation Mode for Cooling |
|
|
|
|
|
|
| Enabled |
R | (5) BV | 35 | CVM_HEATING | – | – | – | Comfort Ventilation Mode for Heating |
|
|
|
|
|
|
| Enabled |
R | (5) BV | 33 | COM_VENT_STA | – | – | – | Comfort Ventilation Mode Status (1=control |
|
|
|
|
|
|
| is in Comfort Vent mode, 0= it is not) |
R/W | (2) AV | 24 | COM_V_HI_SP | 80 | 60 | 85 | Comfort Ventilation Upper Setpoint |
|
|
|
|
|
|
| (degrees F) |
R | (5) BV | 23 | COOLING_ENA | – | – | – | Cooling Mode Enabled |
R | (5) BV | 21 | FAN_ON_W_SEN | – | – | – | CV - Indoor Fan Operates with Space |
|
|
|
|
|
|
| Sensor Present Option Enabled |
R | (2) AV | 56 | CV_VAV_SELEC | – | – | – | CV/VAV Selected (0= Valid CV, 1=Valid |
|
|
|
|
|
|
| VAV, 2= Invalid Value) |
R | (2) AV | 8 | IAQ_VALUE | – | – | – | Demand Ventilation (IAQ) Value (PPM) |
R | (5) BV | 39 | DEMAND_VENT | – | – | – | Demand Ventilation (using Inside Sensor) |
|
|
|
|
|
|
| Enabled |
R/W | (2) AV | 18 | DEMVENT_STPT | 1000 | 0 | 5000 | Demand Ventilation Setpoint |
R | (2) AV | 67 | REVISION | – | – | xx | Device Revision |
R | (5) BV | 90 | DF_SW_INST | – | – | – | Dirty Filter Switch Installed |
R | (5) BV | 15 | DIRT_FILT_SW | – | – | – | Dirty Filter Switch Status (0=open,1=closed/ |
|
|
|
|
|
|
| fault) |
R | (2) AV | 35 | DUCT_STATIC | – | – | – | Duct Static Pressure |
R/W | (2) AV | 58 | DUCT_SP_STPT | 1.5 | 0 | 5 | Duct Static Pressure Setpoint |
R/W | (2) AV | 59 | DUCT_SD_STPT | 4.5 | 0 | 5 | Duct Static Pressure Shutdown Setpoint |
R | (2) AV | 31 | ECO_DAMP_OUT | – | – | – | Economizer Damper Output Status |
|
|
|
|
|
|
|
4 | Johnson Controls Unitary Products |