Simplicity 514067-UAD-A-0509 manual Troubleshooting, Simplicitylinc Gateway

Page 16

514067-UAD-A-0509

TROUBLESHOOTING

The Simplicity®LINC Gateway consists of two printed circuit boards.

TABLE 4: SIMPLICITY®LINC GATEWAY

 

RS485 BOARD (Bottom)

BacNET Board (Top)

Normal Board Operation

Normal Board Operation

The PWR LED should be on during operation. The RX and TX

LEDs LA and LB flash about once per second. LED GP105 will

LEDs should flash when a signal is either received or sent.

remain on within 45-60 seconds after power up, signifying normal

 

operation. The PWR LED should be on during operation. The RX

 

and TX LEDs should flash when a signal is either received or

 

sent.

Faulty Board Operation

Faulty Board Operation

If the PWR LED does not come on but the RX and TX flash, then

If the PWR LED does not come on but the RX and TX flash, then

the PWR LED is broken.

the PWR LED is broken.

If the TX and / or RX LEDs do not flash, it may represent a problem

If the TX and / or RX LEDs do not flash, it may represent a

with the field wiring or configuration problems in the field side of

problem with the field wiring or confguration problems in the field

the BacNET board. It may also indicate incorrect polling

side of the BacNet board. It may also indicate incorrect polling

parameters such as baud rate or parity.

parameters such as baud rate or parity.

 

If the PWR LED does not come on and LA and LB do not flash,

 

call UP Tech Services at 1-877-874-7378.

 

If GP105 never comes on, call UP Tech Services at

 

1-877-874-7378.

General

Power Source

24 ± 15% VAC (Obtained from the Roof Top Unit)

Frequency

45 to 65 HZ

Power Consumption

Nominal >2 VA

Operating Environment

-40 to 160° F (-40 to 70° C) 10 to 95% non-condensing

Size (H x W x D)

5.0 x 2.4 x 1.8 in. (128 x 61 x 45.75 cm)

Weight

0.2 lb. (0.09 kg)

Processor

Type

Microchip

SDRAM Memory

2048 bytes

FLASH Memory

1024 bytes w/1,000,000 write cycle capability

Interface

Port 1 Type

BACnet MS/TP

Port 1 Speeds

9.6, 19.2, 38.4, 76.8 kbaud

Port 1 Connector

3-pin screw terminals

Port 2 Type

Modbus RTU (RS485)

Port 2 Speeds

9.6, 19,2 kbaud

Port 2 Connector

6-pin screw terminals

LAN Cable

Screened Twisted-Pair (Belden 9272 or 89272)

LEDs

Controller Status; BACnet; Modbus

Switch Selections

MAC Address (1-99), Baud Rate

16

Johnson Controls Unitary Products

Image 16
Contents Wire Connections OverviewConnection Baud Rate Selection SettingsModbus Connection Modbus Communication Alarm Flash Memory ManagementDefault Min Max Point Description Points List in Description OrderBACnet Read Object InstInst Descriptor Default Min Max Point Description BACnet Read Object WriteMax Point Description Efreezest Lowsupvolt Default Min Max Point Description Read Object WritePoints List in Object Order ALARM3 Spcealmtim Points List in Object Order Descriptor Default Min Max Point Description Iifanstat Troubleshooting Simplicitylinc GatewayPWR Simplicitylinc Gateway LED LocationJohnson Controls Unitary Products York Drive Norman, OK