TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)
| BACnet | BACnet |
|
|
|
|
|
Read/ | Object | Object |
|
|
|
|
|
Write | Type | Inst | Descriptor | Default | Min | Max | Point Description |
R | (5) BV | 44 | E_HPS1 | – | – | – | Elite High Pressure Switch for Compressor |
|
|
|
|
|
|
| #1 Input Status (1=closed, 0=open/fault) |
R | (5) BV | 48 | E_HPS2 | – | – | – | Elite High Pressure Switch for Compressor |
|
|
|
|
|
|
| #2 Input Status (1=closed, 0=open/fault) |
R | (5) BV | 53 | E_HPS3 | – | – | – | Elite High Pressure Switch for Compressor |
|
|
|
|
|
|
| #3 Input Status (1=closed, 0=open/fault) |
R | (5) BV | 57 | E_HPS4 | – | – | – | Elite High Pressure Switch for Compressor |
|
|
|
|
|
|
| #4 Input Status (1=closed, 0=open/fault) |
R | (5) BV | 40 | E_IFAN_STAT | – | – | – | Elite Indoor Fan Output Status (0=output is |
|
|
|
|
|
|
| OFF, 1=output is ON) |
R | (5) BV | 61 | E_LIMIT_ 1 | – | – | – | Elite Limit Switch #1 Input Status (1=closed, |
|
|
|
|
|
|
| 0=open/fault) |
R | (5) BV | 63 | E_LIMIT_ 2 | – | – | – | Elite Limit Switch #2 Input Status (1=closed, |
|
|
|
|
|
|
| 0=open/fault) |
R | (5) BV | 65 | E_LIMIT_ 3 | – | – | – | Elite Limit Switch #3 Input Status (1=closed, |
|
|
|
|
|
|
| 0=open/fault) |
R | (5) BV | 43 | E_LPS1 | – | – | – | Elite Low Pressure Switch for Compressor |
|
|
|
|
|
|
| #1 Input Status (1=closed, 0=open/fault) |
R | (5) BV | 47 | E_LPS2 | – | – | – | Elite Low Pressure Switch for Compressor |
|
|
|
|
|
|
| #2 Input Status (1=closed, 0=open/fault) |
R | (5) BV | 52 | E_LPS3 | – | – | – | Elite Low Pressure Switch for Compressor |
|
|
|
|
|
|
| #3 Input Status (1=closed, 0=open/fault) |
R | (5) BV | 56 | E_LPS4 | – | – | – | Elite Low Pressure Switch for Compressor |
|
|
|
|
|
|
| #4 Input Status (1=closed, 0=open/fault) |
R | (2) AV | 32 | EXH_DAMP_OUT | – | – | – | Exhaust Damper Output Status |
R | (5) BV | 30 | EX_FAN_STAT | – | – | – | Exhaust Fan Output Status (0=output is |
|
|
|
|
|
|
| OFF, 1=output is ON) |
R | (5) BV | 10 | EX_VFD_INST | – | – | – | Exhaust VFD Installed |
R | (5) BV | 32 | FRECOOL_STAT | – | – | – | Free Cooling Mode Status (0=comps not |
|
|
|
|
|
|
| overridden by Econo, 1=comps overridden) |
R | (5) BV | 68 | HEAT_1_STAT | – | – | – | H1 Heating Output #1 Status (0=output is |
|
|
|
|
|
|
| OFF, 1=output is ON) |
R | (5) BV | 69 | HEAT_2_STAT | – | – | – | H2 Heating Output #2 Status (0=output is |
|
|
|
|
|
|
| OFF, 1=output is ON) |
R | (5) BV | 70 | HEAT_3_STAT | – | – | – | H3 Heating Output #3 Status (0=output is |
|
|
|
|
|
|
| OFF, 1=output is ON) |
R | (2) AV | 76 | H1_ACCUM_HRS | – | – | – | Heating #1 Accumulated Run Time |
|
|
|
|
|
|
| (in hours) |
R | (2) AV | 77 | H2_ACCUM_HRS | – | – | – | Heating #2 Accumulated Run Time |
|
|
|
|
|
|
| (in hours) |
R | (2) AV | 78 | H3_ACCUM_HRS | – | – | – | Heating #3 Accumulated Run Time |
|
|
|
|
|
|
| (in hours) |
R | (5) BV | 25 | HEATING_ENA | – | – | – | Heating Mode Enabled |
R/W | (2) AV | 27 | HGR_HUM_STPT | 50 | 0 | 100 | Hot Gas Reheat Humidity Setpoint (percent |
|
|
|
|
|
|
| Humidity) |
R | (5) BV | 18 | HGR_STAT | – | – | – | Hot Gas Reheat Output Status (0=output is |
|
|
|
|
|
|
| OFF, 1=output is ON) |
R | (2) AV | 47 | HGR_VLV_OUT | – | – | – | Hot Gas Reheat Valve Output Status |
|
|
|
|
|
|
|
6 | Johnson Controls Unitary Products |