Simplicity 514067-UAD-A-0509 manual Efreezest

Page 7

 

 

 

 

 

 

 

 

514067-UAD-A-0509

 

 

 

 

 

 

 

 

 

 

 

TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BACnet

BACnet

 

 

 

 

 

 

 

 

Read/

Object

Object

 

 

 

 

 

 

 

 

Write

Type

Inst

Descriptor

Default

Min

Max

Point Description

 

 

R

(5) BV

66

E_FREEZE_ST

Hot H2O Freeze Thermostat Switch #1

 

 

 

 

 

 

 

 

Input Status (1=closed, 0=open/fault)

 

 

R

(2) AV

55

HW_VLV_OUT

Hot Water Valve Output Status (0-100%)

 

 

R

(5) BV

2

HYDRONC_HEAT

Hydronic Heat Enabled

 

 

R

(5) BV

3

HH_REVER_VLV

Hydronic Heat Reverse Actuated Valve

 

 

 

 

 

 

 

 

Installed

 

 

R/W

(2) AV

62

HYD_S1_SA_SP

120

80

180

Hydronic Heating Stage #1 Supply Air

 

 

 

 

 

 

 

 

Setpoint (degrees F)

 

 

R/W

(2) AV

63

HYD_S2_SA_SP

150

80

180

Hydronic Heating Stage #2 Supply Air

 

 

 

 

 

 

 

 

Setpoint (degrees F)

 

 

R/W

(2) AV

80

IO_DVNT_STPT

700

0

2000

Indoor/Outdoor Demand Ventilation

 

 

 

 

 

 

 

 

Setpoint

 

 

R

(2) AV

45

I_C1_ACM_HRS

Intelli-Comfort Compressor #1 Accumulated

 

 

 

 

 

 

 

 

Run Time (in hours)

 

 

R

(5) BV

73

I_COMP1_STAT

Intelli-Comfort Compressor #1 Input Status

 

 

 

 

 

 

 

 

(0=output is OFF, 1=output is ON)

 

 

R

(2) AV

46

I_C2_ACM_HRS

Intelli-Comfort Compressor #2 Accumulated

 

 

 

 

 

 

 

 

Run Time (in hours)

 

 

R

(5) BV

76

I_COMP2_STAT

Intelli-Comfort Compressor #2 Input Status

 

 

 

 

 

 

 

 

(0=output is OFF, 1=output is ON)

 

 

R

(5) BV

79

I_CFAN_STAT

Intelli-Comfort Condenser Fan #1 Input

 

 

 

 

 

 

 

 

Status (0=output is OFF, 1=output is ON)

 

 

R

(5) BV

72

I_FAN_OVER

Intelli-Comfort Fan Overload Switch Input

 

 

 

 

 

 

 

 

Status (0=open,1=closed)

 

 

R

(5) BV

82

I_FREEZE_1

Intelli-Comfort Freeze Thermostat Switch #1

 

 

 

 

 

 

 

 

Input Status (0=open,1=closed)

 

 

R

(5) BV

83

I_FREEZE_2

Intelli-Comfort Freeze Thermostat Switch #2

 

 

 

 

 

 

 

 

Input Status (0=open,1=closed)

 

 

R

(5) BV

80

I_GAS_VLVE1

Intelli-Comfort Gas Valve #1 Input Status

 

 

R

(5) BV

75

I_HPS1

Intelli-Comfort High Pressure Switch for

 

 

 

 

 

 

 

 

Compressor #1 Input Status (1=closed,

 

 

 

 

 

 

 

 

0=open/fault)

 

 

R

(5) BV

78

I_HPS2

Intelli-Comfort High Pressure Switch for

 

 

 

 

 

 

 

 

Compressor #2 Input Status (1=closed,

 

 

 

 

 

 

 

 

0=open/fault)

 

 

R

(5) BV

71

I_IFAN_STAT

Intelli-Comfort Indoor Fan Output Status

 

 

 

 

 

 

 

 

(0=output is OFF, 1=output is ON)

 

 

R

(5) BV

81

I_LIMIT_1

Intelli-Comfort Limit Switch #1 Input Status

 

 

R

(5) BV

74

I_LPS1

Intelli-Comfort Low Pressure Switch for

 

 

 

 

 

 

 

 

Compressor #1 Input Status (1=closed,

 

 

 

 

 

 

 

 

0=open/fault)

 

 

R

(5) BV

77

I_LPS2

Intelli-Comfort Low Pressure Switch for

 

 

 

 

 

 

 

 

Compressor #2 Input Status (1=closed,

 

 

 

 

 

 

 

 

0=open/fault)

 

 

R

(5) BV

28

INTELLI-STRT

Intelli-Start Enabled

 

 

R/W

(5) BV

13

LOADSHED

Loadshed (0=clear loadshed, 1=set load-

 

 

 

 

 

 

 

 

shed operation)

 

 

R

(5) BV

19

LOW_AMB_OVRD

Low Ambient Temperature (0=comps not

 

 

 

 

 

 

 

 

overridden by LAT, 1=comps overridden)

 

Johnson Controls Unitary Products

7

Image 7
Contents Overview Wire ConnectionsConnection Baud Rate Selection SettingsModbus Connection Flash Memory Management Modbus Communication Alarm Inst Default Min Max Point Description Points List in Description Order BACnet Read ObjectBACnet Read Object Write Inst Descriptor Default Min Max Point DescriptionMax Point Description Efreezest Lowsupvolt Read Object Write Default Min Max Point DescriptionPoints List in Object Order ALARM3 Spcealmtim Points List in Object Order Descriptor Default Min Max Point Description Iifanstat Simplicitylinc Gateway TroubleshootingSimplicitylinc Gateway LED Location PWRJohnson Controls Unitary Products York Drive Norman, OK