TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BACnet

BACnet

 

 

 

 

 

 

 

 

 

 

Read/

Object

Object

 

 

 

 

 

 

 

 

 

 

Write

Type

Inst

Descriptor

Default

Min

Max

Point Description

 

 

R

(5) BV

71

I_IFAN_STAT

Intelli-Comfort Indoor Fan Output Status

 

 

 

 

 

 

 

 

(0=output is OFF, 1=output is ON)

 

 

R

(5) BV

72

I_FAN_OVER

Intelli-Comfort Fan Overload Switch Input

 

 

 

 

 

 

 

 

Status (0=open,1=closed)

 

 

R

(5) BV

73

I_COMP1_STAT

Intelli-Comfort Compressor #1 Input Status

 

 

 

 

 

 

 

 

(0=output is OFF, 1=output is ON)

 

 

R

(5) BV

74

I_LPS1

Intelli-Comfort Low Pressure Switch for

 

 

 

 

 

 

 

 

Compressor #1 Input Status (1=closed,

 

 

 

 

 

 

 

 

0=open/fault)

 

 

R

(5) BV

75

I_HPS1

Intelli-Comfort High Pressure Switch for

 

 

 

 

 

 

 

 

Compressor #1 Input Status (1=closed,

 

 

 

 

 

 

 

 

0=open/fault)

 

 

R

(5) BV

76

I_COMP2_STAT

Intelli-Comfort Compressor #2 Input Status

 

 

 

 

 

 

 

 

(0=output is OFF, 1=output is ON)

 

 

R

(5) BV

77

I_LPS2

Intelli-Comfort Low Pressure Switch for

 

 

 

 

 

 

 

 

Compressor #2 Input Status (1=closed,

 

 

 

 

 

 

 

 

0=open/fault)

 

 

R

(5) BV

78

I_HPS2

Intelli-Comfort High Pressure Switch for

 

 

 

 

 

 

 

 

Compressor #2 Input Status (1=closed,

 

 

 

 

 

 

 

 

0=open/fault)

 

 

R

(5) BV

79

I_CFAN_STAT

Intelli-Comfort Condenser Fan #1 Input

 

 

 

 

 

 

 

 

Status (0=output is OFF, 1=output is ON)

 

 

R

(5) BV

80

I_GAS_VLVE1

Intelli-Comfort Gas Valve #1 Input Status

 

 

R

(5) BV

81

I_LIMIT_1

Intelli-Comfort Limit Switch #1 Input Status

 

 

R

(5) BV

82

I_FREEZE_1

Intelli-Comfort Freeze Thermostat Switch #1

 

 

 

 

 

 

 

 

Input Status (0=open,1=closed)

 

 

R

(5) BV

83

I_FREEZE_2

Intelli-Comfort Freeze Thermostat Switch #2

 

 

 

 

 

 

 

 

Input Status (0=open,1=closed)

 

 

R

(5) BV

85

ALARM_1_ON

Alarm Buffer #1 (0=Alarm has cleared,

 

 

 

 

 

 

 

 

1=Alarm is still active)

 

 

R

(5) BV

86

ALARM_2_ON

Alarm Buffer #2 (0=Alarm has cleared,

 

 

 

 

 

 

 

 

1=Alarm is still active)

 

 

R

(5) BV

87

ALARM_3_ON

Alarm Buffer #3 (0=Alarm has cleared,

 

 

 

 

 

 

 

 

1=Alarm is still active)

 

 

R

(5) BV

88

ALARM_4_ON

Alarm Buffer #4 (0=Alarm has cleared,

 

 

 

 

 

 

 

 

1=Alarm is still active)

 

 

R

(5) BV

89

ALARM_5_ON

Alarm Buffer #5 (0=Alarm has cleared,

 

 

 

 

 

 

 

 

1=Alarm is still active)

 

 

R

(5) BV

90

DF_SW_INST

Dirty Filter Switch Installed

 

 

R

(5) BV

93

OCC_COMS_ENA

Occupied Thermostat or Communication

 

 

 

 

 

 

 

 

Input Enabled

 

 

R/W

(5) BV

96

MANUAL_WRITE

Manual Write Command to ModlINC

 

Johnson Controls Unitary Products

15

Image 15
Contents Overview Wire ConnectionsBaud Rate Selection Settings ConnectionModbus Connection Flash Memory Management Modbus Communication AlarmInst Default Min Max Point DescriptionPoints List in Description Order BACnet Read ObjectBACnet Read Object Write Inst Descriptor Default Min Max Point DescriptionMax Point Description Efreezest Lowsupvolt Read Object Write Default Min Max Point DescriptionPoints List in Object Order ALARM3 Spcealmtim Points List in Object Order Descriptor Default Min Max Point Description Iifanstat Simplicitylinc Gateway TroubleshootingSimplicitylinc Gateway LED Location PWRJohnson Controls Unitary Products York Drive Norman, OK