Simplicity 514067-UAD-A-0509 manual Default Min Max Point Description, Read Object Write

Page 9

 

 

 

 

 

 

 

 

 

514067-UAD-A-0509

 

 

 

 

 

 

 

 

 

 

 

TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BACnet

BACnet

 

 

 

 

 

 

 

 

Read/

Object

Object

 

 

 

 

 

 

 

 

Write

Type

Inst

Descriptor

Default

Min

Max

Point Description

 

 

 

R/W

(2) AV

71

SPCE_ALM_TMP

0

0

25

Space Sensor Alarm Temperature (degrees

 

 

 

 

 

 

 

 

 

F, 0 = disabled)

 

 

 

R/W

(2) AV

72

SPCE_ALM_TIM

0

0

120

Space Sensor Alarm Time (minutes F, 0 =

 

 

 

 

 

 

 

 

 

disabled)

 

 

 

R

(5) BV

26

SEN_FAULT_EN

Space Sensor Fault Override (Construction

 

 

 

 

 

 

 

 

 

Mode) Enabled

 

 

 

R/W

(2) AV

73

SP_OFF_RANGE

3

0

5

Space Temprature Sensor Offset Range

 

 

 

 

 

 

 

 

 

(0-5 degrees)

 

 

 

R

(2) AV

4

SUP_AIR_TEMP

Supply Air Temperature

 

 

 

R/W

(2) AV

70

SAT_ALM_COOL

0

0

80

Supply Air Temperature Alarm Setpoint for

 

 

 

 

 

 

 

 

 

Cooling

 

 

 

R/W

(2) AV

53

SAT_ALM_HEAT

0

0

120

Supply Air Temperature Alarm Setpoint for

 

 

 

 

 

 

 

 

 

Heating

 

 

 

R

(5) BV

22

SAT_COOLING

Supply Air Temperature Limit for Cooling

 

 

 

 

 

 

 

 

 

Enabled

 

 

 

R/W

(2) AV

3

SAT_COOL_SP

50

40

65

Supply Air Temperature Limit for Cooling

 

 

 

 

 

 

 

 

 

Setpoint (degrees F)

 

 

 

R

(5) BV

24

SAT_HEATING

Supply Air Temperature Limit for Heating

 

 

 

 

 

 

 

 

 

Enabled

 

 

 

R/W

(2) AV

52

SAT_HEAT_SP

135

100

180

Supply Air Temperature Limit for Heating

 

 

 

 

 

 

 

 

 

Setpoint (degrees F)

 

 

 

R

(2) AV

34

SFAN_VFD_OUT

Supply Fan VFD Output Status (0-100%)

 

 

 

R

(2) AV

36

ALARM_1

System Alarm #1

 

 

 

R

(2) AV

37

ALARM_2

System Alarm #2

 

 

 

R

(2) AV

38

ALARM_3

System Alarm #3

 

 

 

R

(2) AV

39

ALARM_4

System Alarm #4

 

 

 

R

(2) AV

40

ALARM_5

System Alarm #5

 

 

 

R/W

(2) AV

29

TH_OFFSET

5

1

10

Temperature/Humidity % Humidity that =

 

 

 

 

 

 

 

 

 

1°F of Offset

 

 

 

R/W

(2) AV

26

TEM_HUM_STPT

50

20

80

Temperature/Humidity Setpoint (percent

 

 

 

 

 

 

 

 

 

Humidity)

 

 

 

R

(5) BV

67

FAN_HEAT

Turn OFF Continuous Fan when Starting

 

 

 

 

 

 

 

 

 

Heat Enabled (0=Continuous Fan ON)

 

 

 

R/W

(2) AV

2

UNOC_COOL_SP

85

45

99

Un-Occupied Cooling Setpoint

 

 

 

R/W

(2) AV

51

UNOC_HEAT_SP

60

45

99

Un-Occupied Heating Setpoint

 

 

 

R/W

(2) AV

75

UNOC_OVR_TP

60

0

240

Unoccupied Override Time Period

 

 

 

R/W

(2) AV

65

VAV_CL_LO_SP

55

40

70

VAV Cooling Supply Air Temperature: Lower

 

 

 

 

 

 

 

 

 

Setpoint (degrees F)

 

 

 

R/W

(2) AV

66

VAV_SAT_RSET

72

40

85

VAV Cooling Supply Air Temperature: Reset

 

 

 

 

 

 

 

 

 

Setpoint (Space Temperature)(degrees F)

 

 

 

R/W

(2) AV

64

VAV_CL_HI_SP

60

40

70

VAV Cooling Supply Air Temperature: Upper

 

 

 

 

 

 

 

 

 

Setpoint (degrees F)

 

 

 

R

(5) BV

5

VAV_OCC_HEAT

VAV Occupied Heating Enabled

 

 

 

R/W

(2) AV

60

VAV_OHEAT_SP

68

40

85

VAV Occupied Heating Setpoint (degrees F)

 

Johnson Controls Unitary Products

9

Image 9
Contents Overview Wire ConnectionsBaud Rate Selection Settings ConnectionModbus Connection Flash Memory Management Modbus Communication AlarmPoints List in Description Order Default Min Max Point DescriptionBACnet Read Object InstBACnet Read Object Write Inst Descriptor Default Min Max Point Description Max Point Description Efreezest Lowsupvolt Read Object Write Default Min Max Point DescriptionPoints List in Object Order ALARM3 Spcealmtim Points List in Object Order Descriptor Default Min Max Point Description Iifanstat Simplicitylinc Gateway TroubleshootingSimplicitylinc Gateway LED Location PWRJohnson Controls Unitary Products York Drive Norman, OK