TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED) |
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
| BACnet | BACnet |
|
|
|
|
|
|
| Read/ | Object | Object |
|
|
|
|
|
|
| Write | Type | Inst | Descriptor | Default | Min | Max | Point Description |
|
| R | (5) BV | 19 | LOW_AMB_OVRD | – | – | – | Low Ambient Temperature (0=comps not | |
|
|
|
|
|
|
|
| overridden by LAT, 1=comps overridden) |
|
| R | (5) BV | 20 | POP_ENABLED | – | – | – |
| |
| R | (5) BV | 21 | FAN_ON_W_SEN | – | – | – | CV - Indoor Fan Operates with Space | |
|
|
|
|
|
|
|
| Sensor Present Option Enabled |
|
| R | (5) BV | 22 | SAT_COOLING | – | – | – | Supply Air Temperature Limit for Cooling | |
|
|
|
|
|
|
|
| Enabled |
|
| R | (5) BV | 23 | COOLING_ENA | – | – | – | Cooling Mode Enabled |
|
| R | (5) BV | 24 | SAT_HEATING | – | – | – | Supply Air Temperature Limit for Heating | |
|
|
|
|
|
|
|
| Enabled |
|
| R | (5) BV | 25 | HEATING_ENA | – | – | – | Heating Mode Enabled |
|
| R | (5) BV | 26 | SEN_FAULT_EN | – | – | – | Space Sensor Fault Override (Construction | |
|
|
|
|
|
|
|
| Mode) Enabled |
|
| R | (5) BV | 28 | – | – | – |
| ||
| R | (5) BV | 29 | BP_SENS_INST | – | – | – | Building Static Pressure Sensor Installed |
|
| R | (5) BV | 30 | EX_FAN_STAT | – | – | – | Exhaust Fan Output Status (0=output is OFF, | |
|
|
|
|
|
|
|
| 1=output is ON) |
|
| R | (5) BV | 31 | ECONO_STATUS | – | – | – | Economizer Output Status (0=not Free | |
|
|
|
|
|
|
|
| Cooling, 1= Free Cooling) |
|
| R | (5) BV | 32 | FRECOOL_STAT | – | – | – | Free Cooling Mode Status (0=comps not | |
|
|
|
|
|
|
|
| overridden by Econo, 1=comps overridden) |
|
| R | (5) BV | 33 | COM_VENT_STA | – | – | – | Comfort Ventilation Mode Status (1=control | |
|
|
|
|
|
|
|
| is in Comfort Vent mode, 0= it is not) |
|
| R | (5) BV | 34 | CVM_COOLING | – | – | – | Comfort Ventilation Mode for Cooling | |
|
|
|
|
|
|
|
| Enabled |
|
| R | (5) BV | 35 | CVM_HEATING | – | – | – | Comfort Ventilation Mode for Heating | |
|
|
|
|
|
|
|
| Enabled |
|
| R | (5) BV | 36 | ECO_L_TO_SAT | – | – | – | Economizer Loading to Control Supply Air | |
|
|
|
|
|
|
|
| Temperature Enabled |
|
| R | (5) BV | 37 | OAH_SENSOR | – | – | – | Outside Air Humidity Sensor Enabled |
|
| R | (5) BV | 38 | RAH_SENSOR | – | – | – | Return/Inside Air Humidity Sensor Enabled |
|
| R | (5) BV | 39 | DEMAND_VENT | – | – | – | Demand Ventilation (using Inside Sensor) | |
|
|
|
|
|
|
|
| Enabled |
|
| R | (5) BV | 40 | E_IFAN_STAT | – | – | – | Elite Indoor Fan Output Status (0=output is | |
|
|
|
|
|
|
|
| OFF, 1=output is ON) |
|
| R | (5) BV | 41 | E_FAN_ OVER | – | – | – | Elite Fan Overload Switch Input Status | |
|
|
|
|
|
|
|
| (1=closed, 0=open/fault) |
|
| R | (5) BV | 42 | E_COMP1_STAT | – | – | – | Elite Compressor #1 Output Status (0=output | |
|
|
|
|
|
|
|
| is OFF, 1=output is ON) |
|
| R | (5) BV | 43 | E_LPS1 | – | – | – | Elite Low Pressure Switch for Compressor | |
|
|
|
|
|
|
|
| #1 Input Status (1=closed, 0=open/fault) |
|
| R | (5) BV | 44 | E_HPS1 | – | – | – | Elite High Pressure Switch for Compressor | |
|
|
|
|
|
|
|
| #1 Input Status (1=closed, 0=open/fault) |
|
| R | (5) BV | 45 | E_C1_OVRLOAD | – | – | – | Elite Compressor #1 Overload Switch Input | |
|
|
|
|
|
|
|
| Status (1=closed, 0=open/fault) |
|
| R | (5) BV | 46 | E_COMP2_STAT | – | – | – | Elite Compressor #2 Output Status (0=output | |
|
|
|
|
|
|
|
| is OFF, 1=output is ON) |
|
Johnson Controls Unitary Products | 13 |