TABLE 3: POINTS LIST IN OBJECT ORDER
| BACnet | BACnet |
|
|
|
|
|
Read/ | Object | Object |
|
|
|
|
|
Write | Type | Inst | Descriptor | Default | Min | Max | Point Description |
R/W | (2) AV | 1 | OCC_COOL_SP | 72 | 45 | 99 | Occupied Cooling Setpoint |
R/W | (2) AV | 2 | UNOC_COOL_SP | 85 | 45 | 99 | |
R/W | (2) AV | 3 | SAT_COOL_SP | 50 | 40 | 65 | Supply Air Temperature Limit for Cooling |
|
|
|
|
|
|
| Setpoint (degrees F) |
R | (2) AV | 4 | SUP_AIR_TEMP | – | – | – | Supply Air Temperature |
R | (2) AV | 5 | RET_AIR_TEMP | – | – | – | Return Air Temperature |
R | (2) AV | 6 | SPACE_TEMP | – | – | – | Space (Indoor) Air Temperature |
R | (2) AV | 7 | AMB_TEMP | – | – | – | Outside Air Temperature |
R | (2) AV | 8 | IAQ_VALUE | – | – | – | Demand Ventilation (IAQ) Value (PPM) |
R | (2) AV | 9 | OAQ_VALUE | 1000 | 0 | 5000 | Outside Demand Ventilation (OAQ) Value |
|
|
|
|
|
|
| (PPM) |
R | (2) AV | 10 | AMB_AIR_HUM | – | – | – | Outside Air Humidity |
R | (2) AV | 11 | AMB_AIR_ENTH | – | – | – | Outside Air Enthalpy |
R | (2) AV | 12 | RET_AIR_HUM | – | – | – | Return Air Humidity |
R | (2) AV | 13 | RET_AIR_ENTH | – | – | – | Return Air Enthalpy |
R | (2) AV | 14 | ACC_OVER_TME | – | – | – | Accumulated Unoccupied Override Time (in |
|
|
|
|
|
|
| hours) |
R | (2) AV | 15 | ACTIVE_ALARM | – | – | – | Active Alarm |
R | (2) AV | 16 | NUMBER_COMPS | – | – | – | Number of Compressors Available |
R | (2) AV | 17 | OP_COOL_STPT | – | – | – | Operating Cooling Setpoint |
R/W | (2) AV | 18 | DEMVENT_STPT | 1000 | 0 | 5000 | Demand Ventilation Setpoint |
R/W | (2) AV | 19 | ECON_MIN_POS | 20 | 0 | 100 | Economizer Minimum Position |
R/W | (2) AV | 20 | ECO_1ST_STPT | 55 | 40 | 65 | Economizer First Stage Setpoint |
R/W | (2) AV | 21 | ECO_2ND_STPT | 50 | 40 | 65 | Economizer Second Stage Setpoint |
R/W | (2) AV | 22 | ECON_OAEN_SP | 27 | 10 | 50 | Economizer Outside Air Enthalpy Setpoint |
R/W | (2) AV | 23 | ECON_OAT_ENA | 55 | 40 | 80 | Economizer Outside Air Temperature Enable |
|
|
|
|
|
|
| Setpoint |
R/W | (2) AV | 24 | COM_V_HI_SP | 80 | 60 | 85 | Comfort Ventilation Upper Setpoint (degrees F) |
R/W | (2) AV | 25 | COM_V_LOW_SP | 70 | 60 | 85 | Comfort Ventilation LowerSetpoint (degrees F) |
R/W | (2) AV | 26 | TEM_HUM_STPT | 50 | 20 | 80 | Temperature/Humidity Setpoint (percent |
|
|
|
|
|
|
| Humidity) |
R/W | (2) AV | 27 | HGR_HUM_STPT | 50 | 0 | 100 | Hot Gas Reheat Humidity Setpoint (percent |
|
|
|
|
|
|
| Humidity) |
R/W | (2) AV | 28 | MAX_TH_OFSET | 3 | 0 | 5 | Max Temperature/Humidity Setpoint Offset |
R/W | (2) AV | 29 | TH_OFFSET | 5 | 1 | 10 | Temperature/Humidity % Humidity that = 1°F |
|
|
|
|
|
|
| of Offset |
R/W | (2) AV | 30 | MAX_DMV_ECON | 50 | 0 | 100 | Maximum Demand Ventillation Economizer |
|
|
|
|
|
|
| Position |
R | (2) AV | 31 | ECO_DAMP_OUT | – | – | – | Economizer Damper Output Status |
R | (2) AV | 32 | EXH_DAMP_OUT | – | – | – | Exhaust Damper Output Status |
R | (2) AV | 33 | BLDG_STATIC | – | – | – | Building Static Pressure |
R | (2) AV | 34 | SFAN_VFD_OUT | – | – | – | Supply Fan VFD Output Status |
R | (2) AV | 35 | DUCT_STATIC | – | – | – | Duct Static Pressure |
R | (2) AV | 36 | ALARM_1 | – | – | – | System Alarm #1 |
R | (2) AV | 37 | ALARM_2 | – | – | – | System Alarm #2 |
10 | Johnson Controls Unitary Products |