TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)
| BACnet | BACnet |
|
|
|
|
|
Read/ | Object | Object |
|
|
|
|
|
Write | Type | Inst | Descriptor | Default | Min | Max | Point Description |
R/W | (2) AV | 69 | OP_STPT_DIF | 1 | 1 | 5 | Operating Setpoint Differential |
R/W | (2) AV | 70 | SAT_ALM_COOL | 0 | 0 | 80 | Supply Air Temperature Alarm Setpoint for |
|
|
|
|
|
|
| Cooling |
R/W | (2) AV | 71 | SPCE_ALM_TMP | 0 | 0 | 25 | Space Sensor Alarm Temperature |
|
|
|
|
|
|
| (degrees F, 0 = disabled) |
R/W | (2) AV | 72 | SPCE_ALM_TIM | 0 | 0 | 120 | Space Sensor Alarm Time (minutes F, |
|
|
|
|
|
|
| 0 = disabled) |
R/W | (2) AV | 73 | SP_OFF_RANGE | 3 | 0 | 5 | Space Temprature Sensor Offset Range |
|
|
|
|
|
|
| |
R/W | (2) AV | 74 | OAT_COOL_L_O | 45 | 0 | 100 | Outdoor Air Temperature Cooling Lockout |
|
|
|
|
|
|
| Temperature |
R/W | (2) AV | 75 | UNOC_OVR_TP | 60 | 0 | 240 | Unoccupied Override Time Period |
R | (2) AV | 76 | H1_ACCUM_HRS | – | – | – | Heating #1 Accumulated Run Time (in hours) |
R | (2) AV | 77 | H2_ACCUM_HRS | – | – | – | Heating #2 Accumulated Run Time (in hours) |
R | (2) AV | 78 | H3_ACCUM_HRS | – | – | – | Heating #3 Accumulated Run Time (in hours) |
R/W | (2) AV | 79 | OAQ_STPT | 1000 | 0 | 5000 | Air Quality Setpoint Outside |
R/W | (2) AV | 80 | IO_DVNT_STPT | 700 | 0 | 2000 | Indoor/Outdoor Demand Ventilation Setpoint |
R/W | (2) AV | 81 | POP_HOURS | 4 | 0 | 23 | |
R/W | (2) AV | 82 | POP_MINUTES | 0 | 0 | 59 | |
R/W | (2) AV | 84 | ECON_RAEN_SP | 27 | 10 | 50 | Economizer Return Air Enthalpy Setpoint |
R/W | (5) BV | 1 | OCCUPIED_ENA | – | – | – | Occupied Enabled |
R | (5) BV | 2 | HYDRONC_HEAT | – | – | – | Hydronic Heat Enabled |
R | (5) BV | 3 | HH_REVER_VLV | – | – | – | Hydronic Heat Reverse Actuated Valve |
|
|
|
|
|
|
| Installed |
R | (5) BV | 4 | REM_CONT_ENA | – | – | – | Remote Control Enabled |
R | (5) BV | 5 | VAV_OCC_HEAT | – | – | – | VAV Occupied Heating Enabled |
R | (5) BV | 6 | – | – | – | Morning | |
R | (5) BV | 7 | ECONO_INST | – | – | – | Economizer Installed |
R | (5) BV | 8 | PWR_EX_INST | – | – | – | Power Exhaust Installed |
R | (5) BV | 9 | MOD_EX_INST | – | – | – | Modulating Exhaust Installed |
R | (5) BV | 10 | EX_VFD_INST | – | – | – | Exhaust VFD Installed |
R | (5) BV | 11 | MODBUS_ALARM | – | – | – | Modbus Communication Alarm |
R/W | (5) BV | 12 | REDLINE | – | – | – | Redline (0=clear redline, 1=set redline |
|
|
|
|
|
|
| operation) |
R/W | (5) BV | 13 | LOADSHED | – | – | – | Loadshed (0=clear loadshed, 1=set loadshed |
|
|
|
|
|
|
| operation) |
R | (5) BV | 14 | LOW_SUP_VOLT | – | – | – | Low Supply Voltage (0=comps not |
|
|
|
|
|
|
| overridden by LSV, 1=comps overridden) |
R | (5) BV | 15 | DIRT_FILT_SW | – | – | – | Dirty Filter Switch Status (0=open,1=closed/ |
|
|
|
|
|
|
| fault) |
R | (5) BV | 16 | AIR_PROOF_SW | – | – | – | Air Proving Switch Status (1=closed, |
|
|
|
|
|
|
| 0=open/no air flow) |
R | (5) BV | 17 | PURGE_SWITCH | – | – | – | Purge Switch Status (0=open,1=closed) |
R | (5) BV | 18 | HGR_STAT | – | – | – | Hot Gas Reheat Output Status (0=output is |
|
|
|
|
|
|
| OFF, 1=output is ON) |