TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)

 

BACnet

BACnet

 

 

 

 

 

Read/

Object

Object

 

 

 

 

 

Write

Type

Inst

Descriptor

Default

Min

Max

Point Description

R/W

(2) AV

69

OP_STPT_DIF

1

1

5

Operating Setpoint Differential

R/W

(2) AV

70

SAT_ALM_COOL

0

0

80

Supply Air Temperature Alarm Setpoint for

 

 

 

 

 

 

 

Cooling

R/W

(2) AV

71

SPCE_ALM_TMP

0

0

25

Space Sensor Alarm Temperature

 

 

 

 

 

 

 

(degrees F, 0 = disabled)

R/W

(2) AV

72

SPCE_ALM_TIM

0

0

120

Space Sensor Alarm Time (minutes F,

 

 

 

 

 

 

 

0 = disabled)

R/W

(2) AV

73

SP_OFF_RANGE

3

0

5

Space Temprature Sensor Offset Range

 

 

 

 

 

 

 

(0-5 degrees)

R/W

(2) AV

74

OAT_COOL_L_O

45

0

100

Outdoor Air Temperature Cooling Lockout

 

 

 

 

 

 

 

Temperature

R/W

(2) AV

75

UNOC_OVR_TP

60

0

240

Unoccupied Override Time Period

R

(2) AV

76

H1_ACCUM_HRS

Heating #1 Accumulated Run Time (in hours)

R

(2) AV

77

H2_ACCUM_HRS

Heating #2 Accumulated Run Time (in hours)

R

(2) AV

78

H3_ACCUM_HRS

Heating #3 Accumulated Run Time (in hours)

R/W

(2) AV

79

OAQ_STPT

1000

0

5000

Air Quality Setpoint Outside

R/W

(2) AV

80

IO_DVNT_STPT

700

0

2000

Indoor/Outdoor Demand Ventilation Setpoint

R/W

(2) AV

81

POP_HOURS

4

0

23

Pre-Occupancy Purge Time (hours)

R/W

(2) AV

82

POP_MINUTES

0

0

59

Pre-Occupancy Purge Time (minutes)

R/W

(2) AV

84

ECON_RAEN_SP

27

10

50

Economizer Return Air Enthalpy Setpoint

R/W

(5) BV

1

OCCUPIED_ENA

Occupied Enabled

R

(5) BV

2

HYDRONC_HEAT

Hydronic Heat Enabled

R

(5) BV

3

HH_REVER_VLV

Hydronic Heat Reverse Actuated Valve

 

 

 

 

 

 

 

Installed

R

(5) BV

4

REM_CONT_ENA

Remote Control Enabled

R

(5) BV

5

VAV_OCC_HEAT

VAV Occupied Heating Enabled

R

(5) BV

6

MORN_WARM-UP

Morning Warm-Up Enabled

R

(5) BV

7

ECONO_INST

Economizer Installed

R

(5) BV

8

PWR_EX_INST

Power Exhaust Installed

R

(5) BV

9

MOD_EX_INST

Modulating Exhaust Installed

R

(5) BV

10

EX_VFD_INST

Exhaust VFD Installed

R

(5) BV

11

MODBUS_ALARM

Modbus Communication Alarm

R/W

(5) BV

12

REDLINE

Redline (0=clear redline, 1=set redline

 

 

 

 

 

 

 

operation)

R/W

(5) BV

13

LOADSHED

Loadshed (0=clear loadshed, 1=set loadshed

 

 

 

 

 

 

 

operation)

R

(5) BV

14

LOW_SUP_VOLT

Low Supply Voltage (0=comps not

 

 

 

 

 

 

 

overridden by LSV, 1=comps overridden)

R

(5) BV

15

DIRT_FILT_SW

Dirty Filter Switch Status (0=open,1=closed/

 

 

 

 

 

 

 

fault)

R

(5) BV

16

AIR_PROOF_SW

Air Proving Switch Status (1=closed,

 

 

 

 

 

 

 

0=open/no air flow)

R

(5) BV

17

PURGE_SWITCH

Purge Switch Status (0=open,1=closed)

R

(5) BV

18

HGR_STAT

Hot Gas Reheat Output Status (0=output is

 

 

 

 

 

 

 

OFF, 1=output is ON)

12

Johnson Controls Unitary Products

Image 12
Contents Wire Connections OverviewBaud Rate Selection Settings ConnectionModbus Connection Modbus Communication Alarm Flash Memory ManagementDefault Min Max Point Description Points List in Description OrderBACnet Read Object InstInst Descriptor Default Min Max Point Description BACnet Read Object WriteMax Point Description Efreezest Lowsupvolt Default Min Max Point Description Read Object WritePoints List in Object Order ALARM3 Spcealmtim Points List in Object Order Descriptor Default Min Max Point Description Iifanstat Troubleshooting Simplicitylinc GatewayPWR Simplicitylinc Gateway LED LocationJohnson Controls Unitary Products York Drive Norman, OK