Simplicity 514067-UAD-A-0509 manual BACnet Read Object Write

Page 5

 

 

 

 

 

 

 

 

514067-UAD-A-0509

 

 

 

 

 

 

 

 

 

 

TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BACnet

BACnet

 

 

 

 

 

 

 

Read/

Object

Object

 

 

 

 

 

 

 

Write

Type

Inst

Descriptor

Default

Min

Max

Point Description

 

 

R/W

(2) AV

20

ECO_1ST_STPT

55

40

65

Economizer First Stage Setpoint

 

 

R

(5) BV

7

ECONO_INST

Economizer Installed

 

 

R

(5) BV

36

ECO_L_TO_SAT

Economizer Loading to Control Supply Air

 

 

 

 

 

 

 

 

Temperature Enabled

 

 

R/W

(2) AV

19

ECON_MIN_POS

20

0

100

Economizer Minimum Position

 

 

R

(5) BV

31

ECONO_STATUS

Economizer Output Status (0=not Free

 

 

 

 

 

 

 

 

Cooling, 1= Free Cooling)

 

 

R/W

(2) AV

22

ECON_OAEN_SP

27

10

50

Economizer Outside Air Enthalpy Setpoint

 

 

R/W

(2) AV

23

ECON_OAT_ENA

55

40

80

Economizer Outside Air Temperature

 

 

 

 

 

 

 

 

Enable Setpoint

 

 

R/W

(2) AV

84

ECON_RAEN_SP

27

10

50

Economizer Return Air Enthalpy Setpoint

 

 

R/W

(2) AV

21

ECO_2ND_STPT

50

40

65

Economizer Second Stage Setpoint

 

 

R

(2) AV

41

E_C1_ACM_HRS

Elite Compressor #1 Accumulated Run

 

 

 

 

 

 

 

 

Time (in hours)

 

 

R

(5) BV

42

E_COMP1_STAT

Elite Compressor #1 Output Status (0=out-

 

 

 

 

 

 

 

 

put is OFF, 1=output is ON)

 

 

R

(5) BV

45

E_C1_OVRLOAD

Elite Compressor #1 Overload Switch Input

 

 

 

 

 

 

 

 

Status (1=closed, 0=open/fault)

 

 

R

(2) AV

42

E_C2_ACM_HRS

Elite Compressor #2 Accumulated Run

 

 

 

 

 

 

 

 

Time (in hours)

 

 

R

(5) BV

46

E_COMP2_STAT

Elite Compressor #2 Output Status (0=out-

 

 

 

 

 

 

 

 

put is OFF, 1=output is ON)

 

 

R

(5) BV

49

E_C2_OVRLOAD

Elite Compressor #2 Overload Switch Input

 

 

 

 

 

 

 

 

Status (1=closed, 0=open/fault)

 

 

R

(2) AV

43

E_C3_ACM_HRS

Elite Compressor #3 Accumulated Run

 

 

 

 

 

 

 

 

Time (in hours)

 

 

R

(5) BV

51

E_COMP3_STAT

Elite Compressor #3 Output Status (0=out-

 

 

 

 

 

 

 

 

put is OFF, 1=output is ON)

 

 

R

(5) BV

54

E_C3_OVRLOAD

Elite Compressor #3 Overload Switch Input

 

 

 

 

 

 

 

 

Status (1=closed, 0=open/fault)

 

 

R

(2) AV

44

E_C4_ACM_HRS

Elite Compressor #4 Accumulated Run

 

 

 

 

 

 

 

 

Time (in hours)

 

 

R

(5) BV

55

E_COMP4_STAT

Elite Compressor #4 Output Status (0=out-

 

 

 

 

 

 

 

 

put is OFF, 1=output is ON)

 

 

R

(5) BV

58

E_C4_OVRLOAD

Elite Compressor #4 Overload Switch Input

 

 

 

 

 

 

 

 

Status (1=closed, 0=open/fault)

 

 

R

(5) BV

50

E_CFAN1_STAT

Elite Condenser Fan #1 Output Status

 

 

 

 

 

 

 

 

(0=output is OFF, 1=output is ON)

 

 

R

(5) BV

59

E_CFAN2_STAT

Elite Condenser Fan #2 Output Status Input

 

 

 

 

 

 

 

 

Status (0=output is OFF, 1=output is ON)

 

 

R

(5) BV

41

E_FAN_ OVER

Elite Fan Overload Switch Input Status

 

 

 

 

 

 

 

 

(1=closed, 0=open/fault)

 

 

R

(5) BV

60

E_GAS_VLVE1

Elite Gas Valve #1 Input Status (1=ener-

 

 

 

 

 

 

 

 

gized, 0=not energized)

 

 

R

(5) BV

62

E_GAS_VLVE2

Elite Gas Valve #2 Input Status (1=ener-

 

 

 

 

 

 

 

 

gized, 0=not energized)

 

 

R

(5) BV

64

E_GAS_VLVE3

Elite Gas Valve #3 Input Status (1=ener-

 

 

 

 

 

 

 

 

gized, 0=not energized)

 

Johnson Controls Unitary Products

5

Image 5
Contents Overview Wire ConnectionsModbus Connection Baud Rate Selection SettingsConnection Flash Memory Management Modbus Communication AlarmPoints List in Description Order Default Min Max Point DescriptionBACnet Read Object InstBACnet Read Object Write Inst Descriptor Default Min Max Point DescriptionMax Point Description Efreezest Lowsupvolt Read Object Write Default Min Max Point DescriptionPoints List in Object Order ALARM3 Spcealmtim Points List in Object Order Descriptor Default Min Max Point Description Iifanstat Simplicitylinc Gateway TroubleshootingSimplicitylinc Gateway LED Location PWRJohnson Controls Unitary Products York Drive Norman, OK