TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED) |
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
| BACnet | BACnet |
|
|
|
|
|
|
| Read/ | Object | Object |
|
|
|
|
|
|
| Write | Type | Inst | Descriptor | Default | Min | Max | Point Description |
|
| R/W | (2) AV | 20 | ECO_1ST_STPT | 55 | 40 | 65 | Economizer First Stage Setpoint |
|
| R | (5) BV | 7 | ECONO_INST | – | – | – | Economizer Installed |
|
| R | (5) BV | 36 | ECO_L_TO_SAT | – | – | – | Economizer Loading to Control Supply Air | |
|
|
|
|
|
|
|
| Temperature Enabled |
|
| R/W | (2) AV | 19 | ECON_MIN_POS | 20 | 0 | 100 | Economizer Minimum Position |
|
| R | (5) BV | 31 | ECONO_STATUS | – | – | – | Economizer Output Status (0=not Free | |
|
|
|
|
|
|
|
| Cooling, 1= Free Cooling) |
|
| R/W | (2) AV | 22 | ECON_OAEN_SP | 27 | 10 | 50 | Economizer Outside Air Enthalpy Setpoint |
|
| R/W | (2) AV | 23 | ECON_OAT_ENA | 55 | 40 | 80 | Economizer Outside Air Temperature | |
|
|
|
|
|
|
|
| Enable Setpoint |
|
| R/W | (2) AV | 84 | ECON_RAEN_SP | 27 | 10 | 50 | Economizer Return Air Enthalpy Setpoint |
|
| R/W | (2) AV | 21 | ECO_2ND_STPT | 50 | 40 | 65 | Economizer Second Stage Setpoint |
|
| R | (2) AV | 41 | E_C1_ACM_HRS | – | – | – | Elite Compressor #1 Accumulated Run | |
|
|
|
|
|
|
|
| Time (in hours) |
|
| R | (5) BV | 42 | E_COMP1_STAT | – | – | – | Elite Compressor #1 Output Status (0=out- | |
|
|
|
|
|
|
|
| put is OFF, 1=output is ON) |
|
| R | (5) BV | 45 | E_C1_OVRLOAD | – | – | – | Elite Compressor #1 Overload Switch Input | |
|
|
|
|
|
|
|
| Status (1=closed, 0=open/fault) |
|
| R | (2) AV | 42 | E_C2_ACM_HRS | – | – | – | Elite Compressor #2 Accumulated Run | |
|
|
|
|
|
|
|
| Time (in hours) |
|
| R | (5) BV | 46 | E_COMP2_STAT | – | – | – | Elite Compressor #2 Output Status (0=out- | |
|
|
|
|
|
|
|
| put is OFF, 1=output is ON) |
|
| R | (5) BV | 49 | E_C2_OVRLOAD | – | – | – | Elite Compressor #2 Overload Switch Input | |
|
|
|
|
|
|
|
| Status (1=closed, 0=open/fault) |
|
| R | (2) AV | 43 | E_C3_ACM_HRS | – | – | – | Elite Compressor #3 Accumulated Run | |
|
|
|
|
|
|
|
| Time (in hours) |
|
| R | (5) BV | 51 | E_COMP3_STAT | – | – | – | Elite Compressor #3 Output Status (0=out- | |
|
|
|
|
|
|
|
| put is OFF, 1=output is ON) |
|
| R | (5) BV | 54 | E_C3_OVRLOAD | – | – | – | Elite Compressor #3 Overload Switch Input | |
|
|
|
|
|
|
|
| Status (1=closed, 0=open/fault) |
|
| R | (2) AV | 44 | E_C4_ACM_HRS | – | – | – | Elite Compressor #4 Accumulated Run | |
|
|
|
|
|
|
|
| Time (in hours) |
|
| R | (5) BV | 55 | E_COMP4_STAT | – | – | – | Elite Compressor #4 Output Status (0=out- | |
|
|
|
|
|
|
|
| put is OFF, 1=output is ON) |
|
| R | (5) BV | 58 | E_C4_OVRLOAD | – | – | – | Elite Compressor #4 Overload Switch Input | |
|
|
|
|
|
|
|
| Status (1=closed, 0=open/fault) |
|
| R | (5) BV | 50 | E_CFAN1_STAT | – | – | – | Elite Condenser Fan #1 Output Status | |
|
|
|
|
|
|
|
| (0=output is OFF, 1=output is ON) |
|
| R | (5) BV | 59 | E_CFAN2_STAT | – | – | – | Elite Condenser Fan #2 Output Status Input | |
|
|
|
|
|
|
|
| Status (0=output is OFF, 1=output is ON) |
|
| R | (5) BV | 41 | E_FAN_ OVER | – | – | – | Elite Fan Overload Switch Input Status | |
|
|
|
|
|
|
|
| (1=closed, 0=open/fault) |
|
| R | (5) BV | 60 | E_GAS_VLVE1 | – | – | – | Elite Gas Valve #1 Input Status (1=ener- | |
|
|
|
|
|
|
|
| gized, 0=not energized) |
|
| R | (5) BV | 62 | E_GAS_VLVE2 | – | – | – | Elite Gas Valve #2 Input Status (1=ener- | |
|
|
|
|
|
|
|
| gized, 0=not energized) |
|
| R | (5) BV | 64 | E_GAS_VLVE3 | – | – | – | Elite Gas Valve #3 Input Status (1=ener- | |
|
|
|
|
|
|
|
| gized, 0=not energized) |
|
Johnson Controls Unitary Products | 5 |