TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)
| BACnet | BACnet |
|
|
|
|
|
Read/ | Object | Object |
|
|
|
|
|
Write | Type | Inst | Descriptor | Default | Min | Max | Point Description |
R | (2) AV | 38 | ALARM_3 | – | – | – | System Alarm #3 |
R | (2) AV | 39 | ALARM_4 | – | – | – | System Alarm #4 |
R | (2) AV | 40 | ALARM_5 | – | – | – | System Alarm #5 |
R | (2) AV | 41 | E_C1_ACM_HRS | – | – | – | Elite Compressor #1 Accumulated Run Time |
|
|
|
|
|
|
| (in hours) |
R | (2) AV | 42 | E_C2_ACM_HRS | – | – | – | Elite Compressor #2 Accumulated Run Time |
|
|
|
|
|
|
| (in hours) |
R | (2) AV | 43 | E_C3_ACM_HRS | – | – | – | Elite Compressor #3 Accumulated Run Time |
|
|
|
|
|
|
| (in hours) |
R | (2) AV | 44 | E_C4_ACM_HRS | – | – | – | Elite Compressor #4 Accumulated Run Time |
|
|
|
|
|
|
| (in hours) |
R | (2) AV | 45 | I_C1_ACM_HRS | – | – | – | |
|
|
|
|
|
|
| Run Time (in hours) |
R | (2) AV | 46 | I_C2_ACM_HRS | – | – | – | |
|
|
|
|
|
|
| Run Time (in hours) |
R | (2) AV | 47 | HGR_VLV_OUT | – | – | – | Hot Gas Reheat Valve Output Status |
|
|
|
|
|
|
| |
R | (2) AV | 48 | NUMBER_HEAT | – | – | – | Number of Heat Stages Available |
R | (2) AV | 49 | OP_HEAT_STPT | 68 | 45 | 99 | Operating Heating Setpoint |
R/W | (2) AV | 50 | OCC_HEAT_SP | 68 | 45 | 99 | Occupied Heating Setpoint |
R/W | (2) AV | 51 | UNOC_HEAT_SP | 60 | 45 | 99 | |
R/W | (2) AV | 52 | SAT_HEAT_SP | 135 | 100 | 180 | Supply Air Temperature Limit for Heating |
|
|
|
|
|
|
| Setpoint (degrees F) |
R/W | (2) AV | 53 | SAT_ALM_HEAT | 0 | 0 | 120 | Supply Air Temperature Alarm Setpoint for |
|
|
|
|
|
|
| Heating |
R/W | (2) AV | 54 | OAT_HEAT_L_O | 75 | 0 | 100 | Outdoor Air Temperature HeatingLockout |
|
|
|
|
|
|
| Temperature |
R | (2) AV | 55 | HW_VLV_OUT | – | – | – | Hot Water Valve Output Status |
R | (2) AV | 56 | CV_VAV_SELEC | – | – | – | CV/VAV Selected (0= Valid CV, 1=Valid VAV, |
|
|
|
|
|
|
| 2= Invalid Value) |
R/W | (2) AV | 57 | BLDG_SP_STPT | 0.1 | 0.25 | Building Static Pressure Setpoint | |
R/W | (2) AV | 58 | DUCT_SP_STPT | 1.5 | 0 | 5 | Duct Static Pressure Setpoint |
R/W | (2) AV | 59 | DUCT_SD_STPT | 4.5 | 0 | 5 | Duct Static Pressure Shutdown Setpoint |
R/W | (2) AV | 60 | VAV_OHEAT_SP | 68 | 40 | 85 | VAV Occupied Heating Setpoint (degrees F) |
R/W | (2) AV | 61 | MWU_RAT_STPT | 70 | 50 | 85 | Morning |
|
|
|
|
|
|
| Air Temperature Setpoint (degrees F) |
R/W | (2) AV | 62 | HYD_S1_SA_SP | 120 | 80 | 180 | Hydronic Heating Stage #1 Supply Air |
|
|
|
|
|
|
| Setpoint (degrees F) |
R/W | (2) AV | 63 | HYD_S2_SA_SP | 150 | 80 | 180 | Hydronic Heating Stage #2 Supply Air |
|
|
|
|
|
|
| Setpoint (degrees F) |
R/W | (2) AV | 64 | VAV_CL_HI_SP | 60 | 40 | 70 | VAV Cooling Supply Air Temperature: Upper |
|
|
|
|
|
|
| Setpoint (degrees F) |
R/W | (2) AV | 65 | VAV_CL_LO_SP | 55 | 40 | 70 | VAV Cooling Supply Air Temperature: Lower |
|
|
|
|
|
|
| Setpoint (degrees F) |
R/W | (2) AV | 66 | VAV_SAT_RSET | 72 | 40 | 85 | VAV Cooling Supply Air Temperature: Reset |
|
|
|
|
|
|
| Setpoint (Space Temperature) (degrees F) |
R | (2) AV | 67 | REVISION | 0 | 0 | xx | Device Revision |