3.6. Load Protection Installation

Circuit Breaker Installation

Standard circuit breaker output boards are available with two 30 Amp breakers or one 60 Amp breaker. Output boards are installed at the factory and are not field replaceable units. Contact APC if the output configuration is not suitable for your needs. Other breaker sizes are not available.

GMT Fuse Installation

Fuse holders that accommodate GMT fuses are located on the front panel on the left side of the unit. Insert the fuse in the holder; observing the tripped indicator is correctly oriented. Use the chart shown in Figure 3.6-1 to help determine what size fuses will carry the desired current. When using several of the larger GMT fuses in one shelf, better heat dissipation will be achieved if the fuses are spaced out evenly within the output panel. A list of GMT type fuses available from APC is provided in Figure 3.6-2.

 

 

 

AMBIENT TEMPERATURE

 

 

 

 

 

 

 

 

 

20° C

50° C

60° C

 

 

 

 

 

 

 

FUSE SIZE

7.5 Amp

5 Amp

4.5 Amp

4 Amp

 

 

 

 

 

 

10 Amp

7 Amp

6 Amp

5 Amp

 

 

 

 

 

 

 

 

 

 

15 Amp

10 Amp

9 Amp

8 Amp

 

 

 

 

 

 

Figure 3.6-1 GMT Fuse Temperature De-rating Chart

GMT Fuses

FUSE RATING

PART NUMBER

 

FUSE RATING

PART NUMBER

 

 

 

 

 

¼ Amp

FFA-0030

 

3 Amp

FFA-0036

 

 

 

 

 

½ Amp

FFA-0031

 

5 Amp

FFA-0037

 

 

 

 

 

3/4 Amp

FFA-0032

 

7½ Amp

FFA-0029

 

 

 

 

 

1 Amp

FFA-0033

 

10 Amp

FFA-0038

 

 

 

 

 

1¼ Amp

FFA-0039

 

15 Amp

FFA-0040

 

 

 

 

 

1½ Amp

FFA-0035

 

 

 

 

 

 

 

 

Figure 3.6-2 GMT fuses available from APC

MX06 Power Plant User’s Manual

Page 11

Image 15
Contents VDC Power Systems Table of Contents APC Worldwide Customer Support Limited Product Warranty Revision Revision HistoryGeneral Precautions Safety FirstGeneral Information IntroductionPort How to Use This Manual Room / Location InstallationMechanical Installation Unpacking EquipmentVentilation AC Power ConnectionsBattery Connections Planning the Battery installationConnecting the Battery Cables Multiple Battery Strings Battery LVD ConnectionBattery LVD DC System Grounding Battery Temperature Probe InstallationLoad Protection Installation Circuit Breaker InstallationGMT Fuse Installation Load Connections Cable Size ConsiderationsCircuit Breaker Protected Load Connections 30 or 60 Amps Input / Output Connections GMT Fuse protected Load ConnectionsRelay Output Connections External Alarm Input Connections Relay J2 Connector Output Relay Notes DesignationsInitial Power-Up and Checkout Rectifier Module InstallationBattery and Load Power up Rectifier Management Technical DescriptionDisplays Alarm FunctionsSystem Management Control FunctionsLoad Management Battery ManagementBattery Charging Battery Temperature CompensationBattery Low Voltage Disconnect MX06 Operation MX06 Voltage AdjustmentsOperation DescriptionMX06-50 Configuration Settings MX06 External Alarm Input ConfigurationAlarm No Setting NC Setting Major Minor Factory Major Minor No Alarm Factory MX06-50 Rectifier ConfigurationMX06-50 Programmable Alarms AlarmMX06-100 Configuration Settings MX06-50 Temperature Probe SelectionMX06-100 Rectifier Configuration MX06-100 Temperature Probe Selection MX06-100 Programmable AlarmsTWF0500H5401 Rectifier SpecificationsMX06 50 Power System AC InputDC Output MX06 100 Power SystemVDC Controls and Indicators MechanicalMX06 Controller Magnum VS 50 Power System Magnum VS 100 Power SystemEnvironmental EMC ComplianceAPC Worldwide Customer Support Limited Product Warranty