5 Operation
5.1. Description
The MX06 is designed for years of operation with no user input. the factory with all parameters needed for normal operation. alarm output relays, indicate the general health of the unit.
The power system is
Voltage adjustments or changes to switch settings on the system Controller Board are only required under the follow conditions:
Rectifiers are added or removed from the original configuration shipped from the factory. Modifications are required to the User Alarm Input settings (alarm priority or input contact sense).
Voltage threshold levels for alarm conditions or motorized breaker control need to be changed from the factory default settings.
5.2. MX06 Operation
The control card for the
MX06 Voltage Adjustments
Power plant voltage level is the only adjustment required on a standard MX06. This is performed using the “V ADJ” potentiometer on the front panel of the Control / Distribution module. The voltage level should be set to accommodate the float voltage required by the battery being used in the power system. Consult the battery manufacturer’s data sheet to get the operating voltage information.
MX06 Power Plant User’s Manual | Page 21 |