American Power Conversion MX06 50, MX06 100 user manual MX06-50 Configuration Settings

Page 26

MX06 External Alarm Input Configuration

The MX06-50 and the MX06-100 alarm input circuitry is the same for both controllers. Refer to board layouts in the preceding sections to identify switch 1. The four User Input Alarms can be programmed for either a MAJOR or MINOR alarm upon activation and can be configured for either a Normally Open (NO) or a Normally Closed (NC) input contact from the alarm source. Set dipswitch S1 to program the User Input Alarms. Refer to Figure 5.2-1 for details. The factory settings reflect normally open inputs (closed for alarm) with a MAJOR alarm priority for each user alarm.

Alarm

NO Setting

NC Setting

Major

Minor

Factory

Setting

Setting

Setting

 

 

 

User 1

S1-1 Open

S1-1 Closed

S1-5 Open

S1-5 Closed

NO/Major

User 2

S1-2 Open

S1-2 Closed

S1-6 Open

S1-6 Closed

NO/Major

User 3

S1-3 Open

S1-3 Closed

S1-7 Open

S1-7 Closed

NO/Major

User 4

S1-4 Open

S1-4 Closed

S1-8 Open

S1-8 Closed

NO/Major

Figure 5.2-1 User Alarm Settings

5.3. MX06-50 Configuration Settings

The control card for the MX06-50 is different than the control card for the MX06-100 due to increased number of rectifiers in the MX06-100. The control card for the MX06 is the 0P9172 and for the MX06-100, the control card is the 0P9745. This section will deal with configurations applicable to the MX06-50 only.

E13 E2

E4

E7

E9

R14

R30

R31

E8

E1

J2 J3 J5

S2

1

R4

R21

RECT PRESENT

NO/NC INPUT

S1

MAJ /MIN

SELECT

USER ALARMS

+BAT -BAT

R56

 

J4

V Adj

 

E3

 

E11

 

E12

 

E10

Figure 5.3-1 MX06-50 Controller Layout

MX06 Power Plant User’s Manual

Page 22

Image 26
Contents VDC Power Systems Table of Contents APC Worldwide Customer Support Limited Product Warranty Revision History RevisionSafety First General PrecautionsIntroduction General InformationPort How to Use This Manual Unpacking Equipment InstallationMechanical Installation Room / LocationAC Power Connections VentilationConnecting the Battery Cables Battery ConnectionsPlanning the Battery installation Battery LVD Connection Multiple Battery StringsBattery LVD Battery Temperature Probe Installation DC System GroundingGMT Fuse Installation Load Protection InstallationCircuit Breaker Installation Circuit Breaker Protected Load Connections 30 or 60 Amps Load ConnectionsCable Size Considerations Relay Output Connections Input / Output ConnectionsGMT Fuse protected Load Connections Relay J2 Connector Output Relay Notes Designations External Alarm Input ConnectionsRectifier Module Installation Initial Power-Up and CheckoutBattery and Load Power up Technical Description Rectifier ManagementControl Functions Alarm FunctionsSystem Management Displays Battery Temperature Compensation Battery Management Battery Charging Load ManagementBattery Low Voltage Disconnect Description MX06 Voltage AdjustmentsOperation MX06 OperationAlarm No Setting NC Setting Major Minor Factory MX06-50 Configuration SettingsMX06 External Alarm Input Configuration Alarm MX06-50 Rectifier ConfigurationMX06-50 Programmable Alarms Major Minor No Alarm FactoryMX06-100 Rectifier Configuration MX06-100 Configuration SettingsMX06-50 Temperature Probe Selection MX06-100 Programmable Alarms MX06-100 Temperature Probe SelectionAC Input SpecificationsMX06 50 Power System TWF0500H5401 RectifierMX06 100 Power System DC OutputVDC MX06 Controller Controls and IndicatorsMechanical Environmental Magnum VS 50 Power SystemMagnum VS 100 Power System Compliance EMCAPC Worldwide Customer Support Limited Product Warranty