American Power Conversion MX06 100, MX06 50 Load Management, Battery Management, User Inputs

Page 23

User Inputs

t)Temperature Probe: Provides input for battery voltage temperature compensation. This feature operates only when the probe is attached.

u)User Alarm Inputs: Four inputs are provided for user alarm inputs. The inputs are designed for isolated contacts tied from the alarm input to a corresponding “-BAT” pin on the same connector. The input can be defined as “Normally Open” or “Normally Closed” through dipswitch settings on Control Board (Factory default: Normally open).

4.3. Load Management

Distribution is included for up to 2 circuit breakers or 12 GMT fuses per 50 Amp shelf. The circuit breakers can be 2 X 30 Amps or 1 X 60 Amps in each shelf. The GMT fuses are 8 X ¼ to 15 Amps in each shelf. When a circuit breaker trips, a normally open switch closes and the controller reports a CB alarm. Alarms are reported when a breaker is tripped or is manually turned off.

When a GMT fuse trips, a fuse element burns out allowing the indicator to connect DC power to the alarm contact and the controller reports a fuse alarm.

4.4. Battery Management

Battery Charging

Battery charging and protection are integrated into the DC power system to support the primary function of providing power to the load.

Battery Temperature Compensation

The Battery Float Voltage is based on the value recommended by the battery manufacturer in order to maintain correct battery charge at 25ºC. As temperature rises, electrochemical activity in a battery increases. Similarly, as temperature falls, electrochemical activity in a battery decreases. As temperature rises, charging voltage should be reduced to prevent overcharge and increased as temperature falls to prevent undercharge. The DC power system uses Battery Temperature compensation to change output voltage to compensate for temperature changes.

The circuitry is designed to produce a temperature compensation slope of -3.1 mV / °C / cell, (-1.7 mV / °F / cell) which is typical for most lead acid batteries used for industrial purposes. The operational range on the compensation circuit is from about 4 °F to about 150 °F. Below 2 to 4 °F, the probe detection circuit is non-operational and the float voltage goes to the value set for 25 °C (77 °F).

MX06 Power Plant User’s Manual

Page 19

Image 23
Contents VDC Power Systems Table of Contents APC Worldwide Customer Support Limited Product Warranty Revision Revision HistoryGeneral Precautions Safety FirstGeneral Information IntroductionPort How to Use This Manual Room / Location InstallationMechanical Installation Unpacking EquipmentVentilation AC Power ConnectionsConnecting the Battery Cables Battery ConnectionsPlanning the Battery installation Multiple Battery Strings Battery LVD ConnectionBattery LVD DC System Grounding Battery Temperature Probe InstallationGMT Fuse Installation Load Protection InstallationCircuit Breaker Installation Circuit Breaker Protected Load Connections 30 or 60 Amps Load ConnectionsCable Size Considerations Relay Output Connections Input / Output ConnectionsGMT Fuse protected Load Connections External Alarm Input Connections Relay J2 Connector Output Relay Notes DesignationsInitial Power-Up and Checkout Rectifier Module Installation Battery and Load Power up Rectifier Management Technical DescriptionDisplays Alarm FunctionsSystem Management Control FunctionsLoad Management Battery ManagementBattery Charging Battery Temperature CompensationBattery Low Voltage Disconnect MX06 Operation MX06 Voltage AdjustmentsOperation DescriptionAlarm No Setting NC Setting Major Minor Factory MX06-50 Configuration SettingsMX06 External Alarm Input Configuration Major Minor No Alarm Factory MX06-50 Rectifier ConfigurationMX06-50 Programmable Alarms AlarmMX06-100 Rectifier Configuration MX06-100 Configuration SettingsMX06-50 Temperature Probe Selection MX06-100 Temperature Probe Selection MX06-100 Programmable AlarmsTWF0500H5401 Rectifier SpecificationsMX06 50 Power System AC InputDC Output MX06 100 Power SystemVDC MX06 Controller Controls and IndicatorsMechanical Environmental Magnum VS 50 Power SystemMagnum VS 100 Power System EMC ComplianceAPC Worldwide Customer Support Limited Product Warranty