Programming Parameters

5.0 Programming Parameters

Below table shows operating parameters programmable from keyboard. Only qualified users should re-set programming parameters.

5.1Parameters

Parameter

Setting*

Comments

 

 

 

 

 

 

 

 

 

 

Bypass operation

YES, NO

YES will switch the system into bypass mode

 

 

 

 

 

 

 

 

 

GB, D, F

 

 

 

 

 

 

Language

DK, S, SF

Language of text in display

NL, PL, CZ

 

 

 

 

 

 

 

 

E, P, SK, H

 

 

 

 

 

 

 

 

 

 

 

 

Autostart

YES, NO

Automatic restart by mains return

(1 min.delay). Ensures quick battery recharge

 

 

 

 

 

 

 

 

Remote shutdown active

YES, NO

Shutdown of UPS by remote signal when in

battery operation. Saves battery energy

 

 

 

 

 

 

 

 

Remote shutdown

HIGH, LOW

Nature of remote shutdown signal level

 

 

 

 

 

 

 

 

 

0, 1, 2, 3, 4

 

 

 

 

 

 

Remote shutdown time

5, 6, 7, 8, 9

Time delay on remote shutdown of UPS

 

10 min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Initiates back-up time check.

Battery capacity test

---

Time measured from start until it reaches low

DC warning level.

 

 

 

 

 

 

(See User Guide section 6 )

 

 

 

 

 

 

Battery monitor test**

---

Initiates checks of battery condition by 25%

discharging

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Automatic battery test**

OFF, 3, 6 months

Activates the battery monitor test in cyclic

intervals

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery monitor reset**

---

Press the

 

and

 

 

key

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to resets alarm (flashing light)!

 

 

 

 

 

 

 

 

Boost charge

YES, NO

YES results in boost charge (10 hours)

 

 

 

 

 

 

Autoboost charge

YES, NO

YES results in boost charge after battery

operation. (10 hours)

 

 

 

 

 

 

 

 

 

 

 

Enter new date

YYMMDD

Set tolocal date

 

 

 

 

 

 

 

Enter new time

HHMMSS

Set to local time (24 hour clock)

 

 

 

 

 

 

 

 

*Factory settings in bold

**Only for systems with Battery Monitor active

***Do not leave system running in bypass mode (Static bypass) for extended periodes of time, as batteries are not recharged in bypass mode.

990-4056

Installation Guide APC Silcon 240-320kW 400V UPS

33

Image 33
Contents 240-320kW 400V UPS Installation Guide Installation Guide APC Silcon 240-320kW 400V UPS Safety Symbols used in this manualThank You Introduction IntroductionTools and Equipment ToolsUnpacking UnpackingInstallation InstallationRequirements on Site Height mm Width mm Depth mm2 825mm Cabinet for Isolation Transformer or Switch Gear Footprint1 1600mm Cabinet for 240-320kW UPS 3 1600mm Cabinet for 320kW Isolation Transformer External Connection Connecting the UPSExternal Connection Right side viewInput Cable External External External PE MaximumFuses* FM OutputSystem Integration Interface Connections X005 Output Relays Terminal Blocks X003/X004 Anxiliary ContactsParallel Board Parallel BoardExternal Control Cables Power CablesRelays Relay BoardRelay Board/Relay Functions Relay Number Message Alarm-trigging EventsSee .2 System configuration Communication Interface Board Connecting of APC Silcon Tripel Chassis APC Silcon Triple Chassis Safety WarningsProduct Description Monitoring PortInstalling Management Peripherals Optional Power InputLEDs If the LED is… Then the Silcon Triple Chassis…Order of Management Peripheral Cards Installing Management Peripheral CardsManagement Peripheral Priority Position Card Daisy-chaining the APC Silcon Triple ChassisManagement Peripheral Draw mA Troubleshooting Problem Possible Cause SolutionIf Problems Persist Product Specifications Monitoring Port Pin Assignments External Connection Specification Power, Physical, and Environmental SpecificationsImportant Safety Instructions APC Silcon Battery CabinetsBattery Breaker Box/Fuse-box Installation of BatteriesSilcon Battery Breaker Box APC Battery Breaker Box Connection Diagram 120-480kW Ampere Connection Max Dimensions Weight Rating CableHxWxD mm CircuitExternal Connection Programming Parameters Parameter Setting CommentsProgramming Parameters ParametersProgramming Keys Programming Example Switch to Bypass Operation System ConfigurationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Programming Parameters Programming Parameters for Advanced Parallel Operation Description of SettingsProgramming example Battery MonitorProgramming Parameters Options/Accessories Options/AccessoriesService Bypass Panel for Single Operation Options/Accessories Action On Service Bypass PanelDisplay shows Lamp indicationLamp indication On Servive Bypass Panel Switching from External Bypass to Normal UPS OperationService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories Options/Accessories Display shows H002a Lamp indication On Service Bypass Panel Following can be carried out on any UPS Switching Back to Normal Parallel/Redundant Operation Isolating One UPS for Service/MaintenanceIntersystem Synchronization Unit Intersystem Synchronization Unit System ISU SystemIntersystem Synchronization Unit ISU Remote Display Extension of Remote Display Communication DistanceStandard Short-haul RS232 Modem Async Host DTE Remote Display DTE Connections Without ConverterConnections With Converter Pin Connections for cable from host to ME800A-R2 HostRemote Display Cables Remote Display Power SupplyRemote Display Setting Communication FaultAlarms Remote Display UseHeight Width Depth Weight Isolation TransformerIsolation Example of Transformer Configuration Yyno PE Cable Connecting Isolation Transformer370kW 630 200 150Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories System Specifications System SpecificationsTechnical Data Dimensions / WeightWarranty WarrantyAPC Silcon Series Limited Factory Warranty Installation Planning Data AppendixAppendix Appendix How to Contact APC How to Contact APCAPC Corporate APC Denmark