American Power Conversion AP9604S manual Programming Parameters for Advanced Parallel Operation

Page 39

Programming Parameters

5.3Programming Parameters for Advanced Parallel Operation

To use the advanced parallel functions, the following parameters must be programmed:

1.“Station number”

2.“Highest station address”

3.“Advanced power management”

4.“APM test mode active”

5.“Battery connection”

5.3.1 Description of Settings

1.“Station number”

Valid station numbers: 1-9 stating the UPS parallel address in system.

2.“Highest station number”

Valid station numbers: 2-9 stating the number of UPSs in system.

3.“Advanced power management”

“Disabled”: Advanced Power Management is inactive.

“PARALLEL+1”: Advanced Power Management is activated when the system operates as PARALLEL N+1, meaning that one system can be isolated without overloading the remaining systems (N systems/UPSs).

“REDUNDANT+1”: Advanced power management is activated when the system operates as REDUNDANT N+1, meaning that one system can be isolated without overloading the remaining systems (N systems/UPSs) with one spare system.

4.“APM test mode active”

“No”: Stand-by-time will be 24 hours - on-line time will be 48 hours (xN systems).

“Yes”: Stand-by-time will be 1 min. - on-line time will be 2 min (xN systems).

5.“Battery connection”

“Separate”: Separate battery for this UPS.

“Common”: Common battery in a parallel system.

NOTICE!

“Common”: Common battery in a parallel system. When this setting is chosen, the highest battery temperature that can be found in the parallelled systems (for charge voltage compensation).

NOTICE!

Common battery pack is a technical possibility.

However, APC recommend separate battery pack due to a higher safety degree in connection with redundant/parallel operation.

The UPS system is designed for both situations.

990-4056

Installation Guide APC Silcon 240-320kW 400V UPS

39

Image 39
Contents 240-320kW 400V UPS Installation Guide Installation Guide APC Silcon 240-320kW 400V UPS Safety Symbols used in this manualThank You Tools IntroductionIntroduction Tools and EquipmentUnpacking UnpackingHeight mm Width mm Depth mm InstallationInstallation Requirements on Site2 825mm Cabinet for Isolation Transformer or Switch Gear Footprint1 1600mm Cabinet for 240-320kW UPS 3 1600mm Cabinet for 320kW Isolation Transformer Right side view Connecting the UPSExternal Connection External ConnectionOutput External External PE MaximumInput Cable External Fuses* FMSystem Integration Interface Connections X005 Output Relays Terminal Blocks X003/X004 Anxiliary ContactsParallel Board Parallel BoardExternal Control Cables Power CablesRelays Relay BoardRelay Board/Relay Functions Relay Number Message Alarm-trigging EventsSee .2 System configuration Communication Interface Board Connecting of APC Silcon Tripel Chassis Monitoring Port Safety WarningsAPC Silcon Triple Chassis Product DescriptionIf the LED is… Then the Silcon Triple Chassis… Optional Power InputInstalling Management Peripherals LEDsDaisy-chaining the APC Silcon Triple Chassis Installing Management Peripheral CardsOrder of Management Peripheral Cards Management Peripheral Priority Position CardManagement Peripheral Draw mA Troubleshooting Problem Possible Cause SolutionIf Problems Persist Product Specifications Monitoring Port Pin Assignments External Connection Specification Power, Physical, and Environmental SpecificationsImportant Safety Instructions APC Silcon Battery CabinetsBattery Breaker Box/Fuse-box Installation of BatteriesSilcon Battery Breaker Box Circuit Ampere Connection Max Dimensions Weight Rating CableAPC Battery Breaker Box Connection Diagram 120-480kW HxWxD mmExternal Connection Parameters Parameter Setting CommentsProgramming Parameters Programming ParametersProgramming Keys Programming Example Switch to Bypass Operation System ConfigurationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Programming Parameters Programming Parameters for Advanced Parallel Operation Description of SettingsProgramming example Battery MonitorProgramming Parameters Options/Accessories Options/AccessoriesService Bypass Panel for Single Operation Options/Accessories Lamp indication On Service Bypass PanelAction Display showsLamp indication On Servive Bypass Panel Switching from External Bypass to Normal UPS OperationService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories Options/Accessories Display shows H002a Lamp indication On Service Bypass Panel Following can be carried out on any UPS Switching Back to Normal Parallel/Redundant Operation Isolating One UPS for Service/MaintenanceIntersystem Synchronization Unit Intersystem Synchronization Unit System ISU SystemIntersystem Synchronization Unit ISU Remote Display Extension of Remote Display Communication DistanceStandard Short-haul RS232 Modem Async Pin Connections for cable from host to ME800A-R2 Host Connections Without ConverterHost DTE Remote Display DTE Connections With ConverterRemote Display Cables Remote Display Power SupplyRemote Display Use Communication FaultRemote Display Setting AlarmsHeight Width Depth Weight Isolation TransformerIsolation Example of Transformer Configuration Yyno 630 200 150 Connecting Isolation TransformerPE Cable 370kWOptions/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Dimensions / Weight System SpecificationsSystem Specifications Technical DataWarranty WarrantyAPC Silcon Series Limited Factory Warranty Installation Planning Data AppendixAppendix Appendix APC Denmark How to Contact APCHow to Contact APC APC Corporate