American Power Conversion AP9604S Action, Display shows, Lamp indication, On Service Bypass Panel

Page 44

Options/Accessories

6.1.3 Operating The External Service Bypass Switch

Action

1.

Press

on the keyboard

Display shows

2.

Press

or

on the keyboard until

Bypass operation

:NO

 

 

 

 

3.

Press

on the keyboard

Bypass operation

 

 

 

 

:YES

 

 

 

 

4.

Press

on the keyboard

Lamp indication

 

 

 

 

 

 

 

 

 

 

 

 

on Service Bypass Panel

5.

Check lamp indication on the Service Bypass Panel

The Green lamp (H003)

 

 

 

 

above the bypass switch

 

 

 

 

handle (Q003) lights

6.Turn the external bypass switch (Q003) to position ”1“

7.Turn the output switch (Q002) to position ”0“

8.Open the front door and press both the green ”ON“ and the red ”OFF“ keys simultaneously

The Green lamp (H002) above the output switch handle (Q002) lights

Only the lamp (H002) above the output switch handle (Q002) lights now

Display shows

** System OFF **

The acoustic alarm sounds for 30 sec.*

9.Turn the input switch to position ”0“

The red alarm LED below the display lights and the acoustic alarm sounds for 30 sec.

* The acoustic alarm can be reset by the

key

EMERGENCY (UPS not alive)

1.Turn the input switch (Q001) to position ”0“.

2.Turn the output switch (Q002) to position ”0“.

3.Change any released system input fuse(s).

4.Turn the bypass switch (Q003) to position ”1“.

990-4056

44

Installation Guide APC Silcon 240-320kW 400V UPS

Image 44
Contents 240-320kW 400V UPS Installation Guide Thank You Installation Guide APC Silcon 240-320kW 400V UPSSafety Symbols used in this manual Introduction IntroductionTools and Equipment ToolsUnpacking UnpackingInstallation InstallationRequirements on Site Height mm Width mm Depth mm1 1600mm Cabinet for 240-320kW UPS 2 825mm Cabinet for Isolation Transformer or Switch GearFootprint 3 1600mm Cabinet for 320kW Isolation Transformer Connecting the UPS External ConnectionExternal Connection Right side viewExternal External PE Maximum Input Cable ExternalFuses* FM OutputSystem Integration Interface Connections Terminal Blocks X003/X004 Anxiliary Contacts X005 Output RelaysParallel Board Parallel BoardPower Cables External Control CablesRelay Board RelaysRelay Number Message Alarm-trigging Events Relay Board/Relay FunctionsSee .2 System configuration Communication Interface Board Connecting of APC Silcon Tripel Chassis Safety Warnings APC Silcon Triple ChassisProduct Description Monitoring PortOptional Power Input Installing Management PeripheralsLEDs If the LED is… Then the Silcon Triple Chassis…Installing Management Peripheral Cards Order of Management Peripheral CardsManagement Peripheral Priority Position Card Daisy-chaining the APC Silcon Triple ChassisManagement Peripheral Draw mA If Problems Persist TroubleshootingProblem Possible Cause Solution Product Specifications Monitoring Port Pin Assignments External Connection Power, Physical, and Environmental Specifications SpecificationAPC Silcon Battery Cabinets Important Safety InstructionsSilcon Battery Breaker Box/Fuse-boxInstallation of Batteries Battery Breaker Box Ampere Connection Max Dimensions Weight Rating Cable APC Battery Breaker Box Connection Diagram 120-480kWHxWxD mm CircuitExternal Connection Parameter Setting Comments Programming ParametersProgramming Parameters ParametersProgramming Keys System Configuration Programming Example Switch to Bypass OperationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Programming Parameters Description of Settings Programming Parameters for Advanced Parallel OperationBattery Monitor Programming example Programming Parameters Service Bypass Panel for Single Operation Options/AccessoriesOptions/Accessories Options/Accessories On Service Bypass Panel ActionDisplay shows Lamp indicationSwitching from External Bypass to Normal UPS Operation Lamp indication On Servive Bypass PanelService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories Options/Accessories Display shows H002a Lamp indication On Service Bypass Panel Following can be carried out on any UPS Isolating One UPS for Service/Maintenance Switching Back to Normal Parallel/Redundant OperationIntersystem Synchronization Unit ISU Intersystem Synchronization UnitIntersystem Synchronization Unit System ISU System Standard Short-haul RS232 Modem Async Remote DisplayExtension of Remote Display Communication Distance Connections Without Converter Host DTE Remote Display DTEConnections With Converter Pin Connections for cable from host to ME800A-R2 HostRemote Display Power Supply Remote Display CablesCommunication Fault Remote Display SettingAlarms Remote Display UseIsolation Height Width Depth WeightIsolation Transformer Example of Transformer Configuration Yyno Connecting Isolation Transformer PE Cable370kW 630 200 150Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories System Specifications System SpecificationsTechnical Data Dimensions / WeightAPC Silcon Series Limited Factory Warranty WarrantyWarranty Appendix Installation Planning DataAppendix Appendix How to Contact APC How to Contact APCAPC Corporate APC Denmark