American Power Conversion AP9604S manual Action, Lamp indication On Service Bypass Panel

Page 52

Options/Accessories

Action

1.Check that output switch (Q004) is in position “0”

2.Check that all output switches (Q002) are in position “0”

3.Turn input switches (Q001) to position “1”

4.Open the UPS front door and press the green “ON” push-botton

5.Press on the keyboard

6.Press or on the keyboard until

7.

Press

on the keyboard

8.

Press

on the keyboard

All systems will transfer to bypass operation

9.Check that all output switches (Q002) are in position “0”

10.Turn all output switches (Q002) to position ”1“

11.Turn the output switch (Q004) to position ”1“

12. Turn the bypass switch (Q003) to position “0”

990-4056

Display shows

** System OFF **

Normal operation load power 0%

Bypass operation :NO

Bypass operation

:YES

Bypass operation

Lamp indication

on Service Bypass Panel

The green lamps (H002) above all the output switch handles (Q002) lights.

The green lamp

(H004) above the output switch (Q004) handle also lights.

The green lamps (H002) above all the output switch handles (Q002) light. The green lamp (H004) above the output switch (Q004) handle and the green lamp (H003) above the bypass switch light.

The green lamps (H002) and (H004) do not light any longer. (H003) will light until normal operation.

52

Installation Guide APC Silcon 240-320kW 400V UPS

Image 52
Contents 240-320kW 400V UPS Installation Guide Safety Symbols used in this manual Installation Guide APC Silcon 240-320kW 400V UPSThank You Introduction IntroductionTools and Equipment ToolsUnpacking UnpackingInstallation InstallationRequirements on Site Height mm Width mm Depth mmFootprint 2 825mm Cabinet for Isolation Transformer or Switch Gear1 1600mm Cabinet for 240-320kW UPS 3 1600mm Cabinet for 320kW Isolation Transformer Connecting the UPS External ConnectionExternal Connection Right side viewExternal External PE Maximum Input Cable ExternalFuses* FM OutputSystem Integration Interface Connections Terminal Blocks X003/X004 Anxiliary Contacts X005 Output RelaysParallel Board Parallel BoardPower Cables External Control CablesRelay Board RelaysRelay Number Message Alarm-trigging Events Relay Board/Relay FunctionsSee .2 System configuration Communication Interface Board Connecting of APC Silcon Tripel Chassis Safety Warnings APC Silcon Triple ChassisProduct Description Monitoring PortOptional Power Input Installing Management PeripheralsLEDs If the LED is… Then the Silcon Triple Chassis…Installing Management Peripheral Cards Order of Management Peripheral CardsManagement Peripheral Priority Position Card Daisy-chaining the APC Silcon Triple ChassisManagement Peripheral Draw mA Problem Possible Cause Solution TroubleshootingIf Problems Persist Product Specifications Monitoring Port Pin Assignments External Connection Power, Physical, and Environmental Specifications SpecificationAPC Silcon Battery Cabinets Important Safety InstructionsInstallation of Batteries Battery Breaker Box/Fuse-boxSilcon Battery Breaker Box Ampere Connection Max Dimensions Weight Rating Cable APC Battery Breaker Box Connection Diagram 120-480kWHxWxD mm CircuitExternal Connection Parameter Setting Comments Programming ParametersProgramming Parameters ParametersProgramming Keys System Configuration Programming Example Switch to Bypass OperationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Programming Parameters Description of Settings Programming Parameters for Advanced Parallel OperationBattery Monitor Programming exampleProgramming Parameters Options/Accessories Options/AccessoriesService Bypass Panel for Single Operation Options/Accessories On Service Bypass Panel ActionDisplay shows Lamp indicationSwitching from External Bypass to Normal UPS Operation Lamp indication On Servive Bypass PanelService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories Options/Accessories Display shows H002a Lamp indication On Service Bypass Panel Following can be carried out on any UPS Isolating One UPS for Service/Maintenance Switching Back to Normal Parallel/Redundant OperationIntersystem Synchronization Unit System ISU System Intersystem Synchronization UnitIntersystem Synchronization Unit ISU Extension of Remote Display Communication Distance Remote DisplayStandard Short-haul RS232 Modem Async Connections Without Converter Host DTE Remote Display DTEConnections With Converter Pin Connections for cable from host to ME800A-R2 HostRemote Display Power Supply Remote Display CablesCommunication Fault Remote Display SettingAlarms Remote Display UseIsolation Transformer Height Width Depth WeightIsolation Example of Transformer Configuration Yyno Connecting Isolation Transformer PE Cable370kW 630 200 150Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories System Specifications System SpecificationsTechnical Data Dimensions / WeightWarranty WarrantyAPC Silcon Series Limited Factory Warranty Appendix Installation Planning DataAppendix Appendix How to Contact APC How to Contact APCAPC Corporate APC Denmark