American Power Conversion AP9604S manual Options/Accessories

Page 63

Options/Accessories

NOTICE!

If an MCCB is used in stead of external input fuses, the MCCB load capacity must be 8xIn (nominal current) for minimum 10 ms.

NOTICE!

Check correct phase rotation of mains input voltage! Maximum input/output cables: 3//300 mm2. If input neutral is not available, an optional Dzn0 or Dyn11 input isolation transformer must be used.

NOTICE!

All external cable dimensions are recommended sizes only. Refer to local legal regulations.

NOTICE!

Make sure that gland plate is installed in bottom of cabinet.

CAUTION!

At 100% switch mode load, neutral must be rated for 200% phase current.

990-4056

Installation Guide APC Silcon 240-320kW 400V UPS

63

Image 63
Contents 240-320kW 400V UPS Installation Guide Installation Guide APC Silcon 240-320kW 400V UPS Safety Symbols used in this manualThank You Tools IntroductionIntroduction Tools and EquipmentUnpacking UnpackingHeight mm Width mm Depth mm InstallationInstallation Requirements on Site2 825mm Cabinet for Isolation Transformer or Switch Gear Footprint1 1600mm Cabinet for 240-320kW UPS 3 1600mm Cabinet for 320kW Isolation Transformer Right side view Connecting the UPSExternal Connection External ConnectionOutput External External PE MaximumInput Cable External Fuses* FMSystem Integration Interface Connections X005 Output Relays Terminal Blocks X003/X004 Anxiliary ContactsParallel Board Parallel BoardExternal Control Cables Power CablesRelays Relay BoardRelay Board/Relay Functions Relay Number Message Alarm-trigging EventsSee .2 System configuration Communication Interface Board Connecting of APC Silcon Tripel Chassis Monitoring Port Safety WarningsAPC Silcon Triple Chassis Product DescriptionIf the LED is… Then the Silcon Triple Chassis… Optional Power InputInstalling Management Peripherals LEDsDaisy-chaining the APC Silcon Triple Chassis Installing Management Peripheral CardsOrder of Management Peripheral Cards Management Peripheral Priority Position CardManagement Peripheral Draw mA Troubleshooting Problem Possible Cause SolutionIf Problems Persist Product Specifications Monitoring Port Pin Assignments External Connection Specification Power, Physical, and Environmental SpecificationsImportant Safety Instructions APC Silcon Battery CabinetsBattery Breaker Box/Fuse-box Installation of BatteriesSilcon Battery Breaker Box Circuit Ampere Connection Max Dimensions Weight Rating CableAPC Battery Breaker Box Connection Diagram 120-480kW HxWxD mmExternal Connection Parameters Parameter Setting CommentsProgramming Parameters Programming ParametersProgramming Keys Programming Example Switch to Bypass Operation System ConfigurationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Programming Parameters Programming Parameters for Advanced Parallel Operation Description of SettingsProgramming example Battery MonitorProgramming Parameters Options/Accessories Options/AccessoriesService Bypass Panel for Single Operation Options/Accessories Lamp indication On Service Bypass PanelAction Display showsLamp indication On Servive Bypass Panel Switching from External Bypass to Normal UPS OperationService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories Options/Accessories Display shows H002a Lamp indication On Service Bypass Panel Following can be carried out on any UPS Switching Back to Normal Parallel/Redundant Operation Isolating One UPS for Service/MaintenanceIntersystem Synchronization Unit Intersystem Synchronization Unit System ISU SystemIntersystem Synchronization Unit ISU Remote Display Extension of Remote Display Communication DistanceStandard Short-haul RS232 Modem Async Pin Connections for cable from host to ME800A-R2 Host Connections Without ConverterHost DTE Remote Display DTE Connections With ConverterRemote Display Cables Remote Display Power SupplyRemote Display Use Communication FaultRemote Display Setting AlarmsHeight Width Depth Weight Isolation TransformerIsolation Example of Transformer Configuration Yyno 630 200 150 Connecting Isolation TransformerPE Cable 370kWOptions/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Dimensions / Weight System SpecificationsSystem Specifications Technical DataWarranty WarrantyAPC Silcon Series Limited Factory Warranty Installation Planning Data AppendixAppendix Appendix APC Denmark How to Contact APCHow to Contact APC APC Corporate