American Power Conversion AP9604S manual Relay Board/Relay Functions

Page 16

External Connection

4.4.1 Relay Board/Relay Functions

NOTICE

If alarm mode “Communication to controller lost” is active, ALL relays will indicate failure

Relay Number

Message

Alarm-trigging Events

 

 

 

1 ## (X002)

Mains outside limits

Mains voltage RMS outside limits

 

 

 

Mains wave form (fast detector) outside limits

 

 

 

Mains frequency outside limits

 

 

 

2 ## (X003)

Bypass outside limits

Bypass voltage RMS outside limits

 

 

 

Bypass wave form (fast detector) outside limits

 

 

 

Bypass frequency outside limits

 

 

 

 

3 ##

(X004)

Output outside limits

Output voltage RMS value outside limits

 

 

 

Output wave form (fast detector) outside limits

 

 

 

Output frequency outside limits

 

 

 

 

4

(X005)

System overload

Output load exceeding 100%

 

 

 

Delta inverter current limiter active

 

 

 

Main inverter current limiter active

 

 

 

 

5

(X006)

Fan fault

Blocked or faulty fan

 

 

 

 

6

(X007)

High Equipment

Static switch temperature too high

 

 

Temperature or

Main inverter failure (temperature too high or fuse blown)

 

 

Inverter Fuse Blown

Delta inverter temperature too high

 

 

 

Magnetic temperature too high

 

 

 

Isolation transformer (option) temperature too high

 

 

 

Battery temperature too high

 

 

 

 

7

(X008)

MCCB battery off

Battery MCCB/Fuse not closed or released

 

 

 

 

8

(X009)

Normal operation

UPS running in normal operation mode

 

 

 

(status)

 

 

 

9 ## (X010)

Battery operation

UPS running in battery operation mode

 

 

 

(status)

 

 

 

10 ## (X011)

Bypass operation

UPS running in bypass operation mode

 

 

 

(status)

 

 

 

11 ## (X012)

Stand-by operation

UPS in stand-by mode

 

 

 

(Hot stand-by - parallel systems only)

 

 

 

 

12

(X013)

Service bypass

Service bypass switch active

 

 

operation

 

 

 

 

13 ## (X014)

Boost charge

UPS boost-charging on battery

 

 

operation

 

 

 

 

 

14

(X015)

Battery voltage

DC voltage too high (shut down)

 

 

outside limits

DC voltage below warning level

 

 

 

DC voltage too low (shut down)

 

 

 

 

15

(X016)

Battery condition

ABM has detected weak battery condition

 

 

fault

ABM has detected defect battery

 

 

 

(ABM = Advanced Battery Monitor)

 

 

 

16 ## (X017)

Common fault

All alarms as mentioned above

 

 

 

(except relays 8+9+10+11)

 

 

 

Internal power supply fault

 

 

 

System locked in operation mode

 

 

 

Internal memory fault

 

 

 

Internal communication fault

 

 

 

 

##Delay programmable in configuration stack : “Common fault delay”. Settings 0,10,20,30 seconds.

990-4056

16

Installation Guide APC Silcon 240-320kW 400V UPS

Image 16
Contents 240-320kW 400V UPS Installation Guide Safety Symbols used in this manual Installation Guide APC Silcon 240-320kW 400V UPSThank You Introduction IntroductionTools and Equipment ToolsUnpacking UnpackingInstallation InstallationRequirements on Site Height mm Width mm Depth mmFootprint 2 825mm Cabinet for Isolation Transformer or Switch Gear1 1600mm Cabinet for 240-320kW UPS 3 1600mm Cabinet for 320kW Isolation Transformer Connecting the UPS External ConnectionExternal Connection Right side viewExternal External PE Maximum Input Cable ExternalFuses* FM OutputSystem Integration Interface Connections Terminal Blocks X003/X004 Anxiliary Contacts X005 Output Relays Parallel Board Parallel BoardPower Cables External Control CablesRelay Board RelaysRelay Number Message Alarm-trigging Events Relay Board/Relay FunctionsSee .2 System configuration Communication Interface Board Connecting of APC Silcon Tripel Chassis Safety Warnings APC Silcon Triple ChassisProduct Description Monitoring PortOptional Power Input Installing Management PeripheralsLEDs If the LED is… Then the Silcon Triple Chassis…Installing Management Peripheral Cards Order of Management Peripheral CardsManagement Peripheral Priority Position Card Daisy-chaining the APC Silcon Triple ChassisManagement Peripheral Draw mA Problem Possible Cause Solution TroubleshootingIf Problems Persist Product Specifications Monitoring Port Pin Assignments External Connection Power, Physical, and Environmental Specifications SpecificationAPC Silcon Battery Cabinets Important Safety InstructionsInstallation of Batteries Battery Breaker Box/Fuse-boxSilcon Battery Breaker Box Ampere Connection Max Dimensions Weight Rating Cable APC Battery Breaker Box Connection Diagram 120-480kWHxWxD mm CircuitExternal Connection Parameter Setting Comments Programming ParametersProgramming Parameters ParametersProgramming Keys System Configuration Programming Example Switch to Bypass OperationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Programming Parameters Description of Settings Programming Parameters for Advanced Parallel OperationBattery Monitor Programming exampleProgramming Parameters Options/Accessories Options/AccessoriesService Bypass Panel for Single Operation Options/Accessories On Service Bypass Panel ActionDisplay shows Lamp indicationSwitching from External Bypass to Normal UPS Operation Lamp indication On Servive Bypass PanelService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories Options/Accessories Display shows H002a Lamp indication On Service Bypass Panel Following can be carried out on any UPS Isolating One UPS for Service/Maintenance Switching Back to Normal Parallel/Redundant OperationIntersystem Synchronization Unit System ISU System Intersystem Synchronization UnitIntersystem Synchronization Unit ISU Extension of Remote Display Communication Distance Remote DisplayStandard Short-haul RS232 Modem Async Connections Without Converter Host DTE Remote Display DTEConnections With Converter Pin Connections for cable from host to ME800A-R2 HostRemote Display Power Supply Remote Display CablesCommunication Fault Remote Display SettingAlarms Remote Display UseIsolation Transformer Height Width Depth WeightIsolation Example of Transformer Configuration Yyno Connecting Isolation Transformer PE Cable370kW 630 200 150Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories System Specifications System SpecificationsTechnical Data Dimensions / WeightWarranty WarrantyAPC Silcon Series Limited Factory Warranty Appendix Installation Planning DataAppendix Appendix How to Contact APC How to Contact APCAPC Corporate APC Denmark