American Power Conversion Comprehensive Guide to 320kW 400V Diesel Genset Factory Programming Parameters

Page 36

Programming Parameters

System Configuration Parameters (password protected)

Parameter

Setting*

Comments

 

 

 

Enter System no.

380, 400, 415

Optional selection of voltage

Voltage L-L

 

 

 

 

 

System Frequency

50/60

Optional selection of frequency

 

 

 

Isolation Transformer Input

YES, NO

YES if optional input isolation transformer is available

 

 

 

IsolationTransformer

YES, NO

YES if optional output isolation transformer is available

Output

 

 

 

 

 

Delta Soft Start Time

1, 10, 20, 40 sec.

Input current switching in ramp function. Use higher

 

 

values for smaller/unstable diesel generators

 

 

 

External SSW present

YES, NO

YES for systems with external static bypass switch

 

 

 

Normal Charge Voltage

410-460V

Setting of float charge voltage at 20°C

 

438V

(Automatic compensation for temperature deviations)

 

 

 

Boost Charge Voltage

438-460V

Setting of boost charge voltage at 20°C

 

438V

(Automatic compensation for temperature deviations)

 

 

 

Low Battery warning

336-384V

Discharged Battery warning

 

336V

 

 

 

 

Low Battery shut-down

310-336V

Switches off system at min. permissible battery

 

326V

voltage

 

 

 

Synchronization

0.25, 0.5, 1, 2, 4

Syncronization speed.

 

Hz/sec.

 

 

 

 

High Battery Temperature

15-40°C

Alarm - Ambient temperature for battery too high

 

35°C

 

 

 

 

Common fault delay

0, 10, 20,

Delay before common fault alarm relay is activated

 

30 sec.

 

 

 

 

Reset operation mode lock

YES, NO

YES resets system locked in bypass or battery

 

 

operation mode caused by system failures (only

 

 

applicable for service personnel)

 

 

 

Expected back-up time

0.1-999.9

Expected UPS back-up time in minutes when running

(min.)

5.0

at 100% ohmic load. Time used by ABM**

 

 

 

Battery Capacity in (Ah)

0.1-999.9

Total Battery capacity in Ah.

 

7.0

Setting used by ABM**.

 

 

 

Highest Station Address

2-9

Highest station address in parallel system

 

 

 

Station Address

1-9

Station address in parallel system

 

 

 

APM Mode Active

Disabled

Use only in parallel systems.

(Advanced Power

Redundant +1

Disabled: Advanced power management off.

Management)

Parallel +1

Redundant +1: Redundant operation with one unit

 

 

being inactive in parallel system

 

 

Parallel +1: Redundant operation with all units in

 

 

operation.

 

 

 

APM Test Mode Active

YES, NO

YES, if APM test mode is active

 

 

 

Battery Connection

Common,

Common: if common battery is used in parallel system.

 

Separate

Separate: if separate battery is used

 

 

 

*Bold text refers to factory standard setting **Advanced Battery Monitor

990-4056

36

Installation Guide APC Silcon 240-320kW 400V UPS

Image 36
Contents 240-320kW 400V UPS Installation Guide Installation Guide APC Silcon 240-320kW 400V UPS Safety Symbols used in this manualThank You Introduction IntroductionTools and Equipment ToolsUnpacking UnpackingInstallation InstallationRequirements on Site Height mm Width mm Depth mm2 825mm Cabinet for Isolation Transformer or Switch Gear Footprint1 1600mm Cabinet for 240-320kW UPS 3 1600mm Cabinet for 320kW Isolation Transformer Connecting the UPS External ConnectionExternal Connection Right side viewExternal External PE Maximum Input Cable ExternalFuses* FM OutputSystem Integration Interface Connections Terminal Blocks X003/X004 Anxiliary Contacts X005 Output RelaysParallel Board Parallel BoardPower Cables External Control CablesRelay Board RelaysRelay Number Message Alarm-trigging Events Relay Board/Relay FunctionsSee .2 System configuration Communication Interface Board Connecting of APC Silcon Tripel Chassis Safety Warnings APC Silcon Triple ChassisProduct Description Monitoring PortOptional Power Input Installing Management PeripheralsLEDs If the LED is… Then the Silcon Triple Chassis…Installing Management Peripheral Cards Order of Management Peripheral CardsManagement Peripheral Priority Position Card Daisy-chaining the APC Silcon Triple ChassisManagement Peripheral Draw mA Troubleshooting Problem Possible Cause SolutionIf Problems Persist Product Specifications Monitoring Port Pin Assignments External Connection Power, Physical, and Environmental Specifications SpecificationAPC Silcon Battery Cabinets Important Safety InstructionsBattery Breaker Box/Fuse-box Installation of BatteriesSilcon Battery Breaker Box Ampere Connection Max Dimensions Weight Rating Cable APC Battery Breaker Box Connection Diagram 120-480kWHxWxD mm CircuitExternal Connection Parameter Setting Comments Programming ParametersProgramming Parameters ParametersProgramming Keys System Configuration Programming Example Switch to Bypass OperationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Programming Parameters Description of Settings Programming Parameters for Advanced Parallel OperationBattery Monitor Programming exampleProgramming Parameters Options/Accessories Options/AccessoriesService Bypass Panel for Single Operation Options/Accessories On Service Bypass Panel ActionDisplay shows Lamp indicationSwitching from External Bypass to Normal UPS Operation Lamp indication On Servive Bypass PanelService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories Options/Accessories Display shows H002a Lamp indication On Service Bypass Panel Following can be carried out on any UPS Isolating One UPS for Service/Maintenance Switching Back to Normal Parallel/Redundant OperationIntersystem Synchronization Unit Intersystem Synchronization Unit System ISU SystemIntersystem Synchronization Unit ISU Remote Display Extension of Remote Display Communication DistanceStandard Short-haul RS232 Modem Async Connections Without Converter Host DTE Remote Display DTEConnections With Converter Pin Connections for cable from host to ME800A-R2 HostRemote Display Power Supply Remote Display CablesCommunication Fault Remote Display SettingAlarms Remote Display UseHeight Width Depth Weight Isolation TransformerIsolation Example of Transformer Configuration Yyno Connecting Isolation Transformer PE Cable370kW 630 200 150Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories System Specifications System SpecificationsTechnical Data Dimensions / WeightWarranty WarrantyAPC Silcon Series Limited Factory Warranty Installation Planning Data AppendixAppendix Appendix How to Contact APC How to Contact APCAPC Corporate APC Denmark