American Power Conversion AP9604S System Specifications, Technical Data, Dimensions / Weight

Page 69

System Specifications

7.0System Specifications

7.1Technical Data

 

Voltage

3x380/400/415V

 

 

 

Input

Voltage tolerance

±15%

 

Normal operation

±10% (standard)

 

Bypass operation

±4, 6, 8% (programmable)

 

 

 

 

Frequency

50Hz/60Hz

 

 

±6 standard

 

 

±0.5-8% (programmable)

 

 

 

 

Input power factor

load 25% minimum 0.97

 

 

load 100% minimum 0.99

 

 

 

 

Current distortion

Max. 5%

 

 

 

Output

Voltage

3x380/400/415V

 

 

 

 

Voltage tolerance

±1% static symmetrical load±

 

 

±3% static symmetrical load

 

 

±5% 0-100% load step

 

 

 

 

Voltage distortion

max. 3% linear load

 

 

max. 6% non-linear load

 

 

 

 

Load power factor

0.9 lead to 0.8 lag

 

 

 

 

Frequency

50Hz/60Hz (mains synchronized)

 

 

+0.1% free-running

 

 

 

 

Overload capacity

 

 

Mains operation

200% - 60 seconds

 

Mains operation

125% - 10 minutes

 

Battery operation

150% - 30 seconds

 

Bypass operation

125% - continuous

 

 

 

General

Ambient temperature

0-40°C (Temperatures above 25°C will

 

 

reduce battery lifetime)

 

 

 

 

Humidity

Max. 95% non-condensing

 

Protection class

IP30

 

Safety

EN 50091-1

 

 

CE Mark

 

Emission and Immunity

EN 50091-2

 

Static bypass switch

Built-in

 

Auto restart

Programmable

 

Economy mode

Programmable

 

 

 

7.2Dimensions / Weight

Type

Height [mm]

Width [mm]

Depth [mm]

Weight [kg]

 

 

 

 

 

240kW

1800

1600

800

1400

 

 

 

 

 

320kW

1800

1600

800

1400

 

 

 

 

 

990-4056

Installation Guide APC Silcon 240-320kW 400V UPS

69

Image 69
Contents 240-320kW 400V UPS Installation Guide Installation Guide APC Silcon 240-320kW 400V UPS Safety Symbols used in this manualThank You Introduction IntroductionTools and Equipment ToolsUnpacking UnpackingInstallation InstallationRequirements on Site Height mm Width mm Depth mm2 825mm Cabinet for Isolation Transformer or Switch Gear Footprint1 1600mm Cabinet for 240-320kW UPS 3 1600mm Cabinet for 320kW Isolation Transformer External Connection Connecting the UPSExternal Connection Right side viewInput Cable External External External PE MaximumFuses* FM OutputSystem Integration Interface Connections X005 Output Relays Terminal Blocks X003/X004 Anxiliary ContactsParallel Board Parallel BoardExternal Control Cables Power CablesRelays Relay BoardRelay Board/Relay Functions Relay Number Message Alarm-trigging EventsSee .2 System configuration Communication Interface Board Connecting of APC Silcon Tripel Chassis APC Silcon Triple Chassis Safety WarningsProduct Description Monitoring PortInstalling Management Peripherals Optional Power InputLEDs If the LED is… Then the Silcon Triple Chassis…Order of Management Peripheral Cards Installing Management Peripheral CardsManagement Peripheral Priority Position Card Daisy-chaining the APC Silcon Triple ChassisManagement Peripheral Draw mA Troubleshooting Problem Possible Cause SolutionIf Problems Persist Product Specifications Monitoring Port Pin Assignments External Connection Specification Power, Physical, and Environmental SpecificationsImportant Safety Instructions APC Silcon Battery CabinetsBattery Breaker Box/Fuse-box Installation of BatteriesSilcon Battery Breaker Box APC Battery Breaker Box Connection Diagram 120-480kW Ampere Connection Max Dimensions Weight Rating CableHxWxD mm CircuitExternal Connection Programming Parameters Parameter Setting CommentsProgramming Parameters ParametersProgramming Keys Programming Example Switch to Bypass Operation System ConfigurationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Programming Parameters Programming Parameters for Advanced Parallel Operation Description of SettingsProgramming example Battery MonitorProgramming Parameters Options/Accessories Options/AccessoriesService Bypass Panel for Single Operation Options/Accessories Action On Service Bypass PanelDisplay shows Lamp indicationLamp indication On Servive Bypass Panel Switching from External Bypass to Normal UPS OperationService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories Options/Accessories Display shows H002a Lamp indication On Service Bypass Panel Following can be carried out on any UPS Switching Back to Normal Parallel/Redundant Operation Isolating One UPS for Service/MaintenanceIntersystem Synchronization Unit Intersystem Synchronization Unit System ISU SystemIntersystem Synchronization Unit ISU Remote Display Extension of Remote Display Communication DistanceStandard Short-haul RS232 Modem Async Host DTE Remote Display DTE Connections Without ConverterConnections With Converter Pin Connections for cable from host to ME800A-R2 HostRemote Display Cables Remote Display Power SupplyRemote Display Setting Communication FaultAlarms Remote Display UseHeight Width Depth Weight Isolation TransformerIsolation Example of Transformer Configuration Yyno PE Cable Connecting Isolation Transformer370kW 630 200 150Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories System Specifications System SpecificationsTechnical Data Dimensions / WeightWarranty WarrantyAPC Silcon Series Limited Factory Warranty Installation Planning Data AppendixAppendix Appendix How to Contact APC How to Contact APCAPC Corporate APC Denmark