External Connection - Connecting the UPS
Mounting the Conduit Box:
1.Open UPS front door.
2.Remove cover from the input/output section.
1 | 1 |
| S001 |
| S002 |
0 | 0 |
In order to remove the cover from the in- and output section, please remove all 8 M6×12 torx screws.
3.Place Conduit Box under UPS and align it with hole in UPS bottom plate.
4.Take out Conduit Box and make holes in Conduit Box according to below table.
Conduit sizes (mm):
| Input Conduit | Output/Bypass | Battery | Alarm Conduit |
| Conduit | Conduit | ||
|
|
| ||
|
|
|
|
|
10 kVA | 12.7 | 12.7 | 12.7 | 12.7 |
|
|
|
|
|
20 kVA | 19.05 | 12.7 | 25.4 | 12.7 |
|
|
|
|
|
30 kVA | 25.4 | 19.05 | 31.75 | 12.7 |
|
|
|
|
|
40 kVA | 25.4 | 25.4 | 38.1 | 12.7 |
|
|
|
|
|
60 kVA | 31.75 | 25.4 | 63.5 | 12.7 |
|
|
|
|
|
80 kVA | 38.1 | 31.75 | 2 × 38.1 | 12.7 |
|
|
|
|
|
100 kVA | 38.1 | 31.75 | 2 × 50 | 12.7 |
|
|
|
|
|