American Power Conversion AIS 5000 manual Input/Output -60 kVA

Page 24

External Connection - Connecting the UPS

Input/Output section 40–60 kVA

Q090

 

Q050

 

Q100

1

on

 

1

on

 

1

on

0

off

 

0

 

 

0

off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Q001

Q004

 

 

 

 

 

1

 

 

on

on

 

 

 

 

 

1

0

 

 

off

 

0

off

Battery

 

B+ B-

X001

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L1

L2

L3

 

 

 

 

 

X090

X004

 

 

 

 

N

 

Grounding Busbar

X001 Mains Input (L1, L2, L3)

X090 Bypass Input (L1, L2, L3, N)

X004 Output (L1, L2, L3, N)

Q004 Battery (+, –)

18

AIS 5000 400V Installation Manual

990-2440

Image 24
Contents AIS Page Contents Options Operation Modes Page Safety Symbols used in this manualUser Safety Disconnect all sources of AC and DC powerGeneral Information About this manualSite Requirements Receiving and inspecting the UPSMoving the equipment to site Air Filter Fitting the air filterAir filter sizes Enclosure dimensions and footprint Enclosure dimensionsTop and bottom view of 10-30kVA UPS Top and bottom view of 40-60kVA UPS Top and bottom view of 80-100kVA UPS Connecting the UPS External connection boardInstalling Conduit Boxes  UPS Feet  Conduit Box  Front of Conduit BoxInput Conduit Output/Bypass Battery Alarm Conduit Access to Input/Output section Low-voltage section cover Communication Interface, EPO Connecting cables Input/Output -60 kVA Input/Output -100 kVA Grounding X090Emergency Power Off EPO Communication interfaceCommunication interface ports COM-PORTCOM Interface Overview of Communication interface10kVA 400V UPS Nominal Voltage 240 Max. Discharge Current a 46 aEmergency Power Off EPO Yes Approvals IEC 62040/EN 50091 Class A, VFI-SS-112Options Mains Voltage 400 V 3 Wire + G Nom 19.88 kW 33.79 a Voltage 400 V 3 Wire + N + G Nominal Current 28.9 a20kVA 400V UPS Max 39.4 aMax. Discharge Current a 91 a External Connection 20kVA 400V UPS Options Mains Voltage 400 V 3 Wire + G Nom 28.35 kW 47.86 a Voltage 400 V 3 Wire + N + G Nominal current 43.3 a30kVA 400V UPS Max 59.9 aMax. Discharge Current a 135 a External Connection 30kVA 400V UPS Options Mains Voltage 400 V 3 Wire + G Nom 36.9 kW 61.93 a Voltage 400 V 3 Wire + N + G Nominal current 57.7 a40kVA 400V UPS Max 77.8 aMax. Discharge Current a 179 External Connection 40kVA 400V UPS Options Mains Voltage 400 V 3 Wire + G Nom 54.42 kW 90.08 a Voltage 400 V 3 Wire + N + G Nominal current 86.6 a60kVA 400V UPS Max 117 aMax. Discharge Current a 266 External Connection 60kVA 400V UPS Options Mains Voltage 400 V 3 Wire + G Nom 72.33 kW 118.23 a Voltage 400 V 3 Wire + N + G Nominal current 115.5 a80kVA 400V UPS Max 152.8 aMax. Discharge Current a 353 External Connection 80kVA 400V UPS Options 100kVA 400V UPS Max. Discharge Current a 442 External Connection 100kVA 400V UPS Options Options IP32 Drip Shield Mounting the drip shield Drip shield sizes Relay Board MessageMessage Communication Cards Cards and slotsDisplay Display introductionDisplay functions Display messages Programming the UPS User stackKeys Until the display shows Programming and Set-Up Programming the UPS Bypass Operation Push Cursor keysAuto Boost Charge OFF Battery Capacity Test ??? Battery Monitor Alarm Settings for redundant systems Enter new time HH.MM.SS Setting stack Minutes10 kVA 20 kVA 30 kVA 40 kVA 60 kVA 80 kVA 100 kVA How to change factory settings Operation mode descriptions Operation ModesNormal to Bypass Operation Bypass to Normal OperationPress Normal to Manual Bypass Operation Load is now supported by the UPS Page 990-2440