American Power Conversion AIS 5000 manual 10kVA 400V UPS

Page 30

10kVA 400V UPS

IS10KH

Performance - Linear Load

DC to AC Efficiency [%]

87.0

AC to AC Efficiency [%]

83.0

Heat Dissipation [BTU/h] [W]

6,003/1,758

 

 

Electrical Input

 

 

 

 

 

Mains

 

Voltage

400 V 3 Wire + G

P Nom.

10.3 kW

I Nom.

17.7 A

(Nominal input current based on nominal mains

 

voltage and batteries fully charged at 100% ohmic

 

load)

 

I Max.

19.9 A

(Maximum input current based on full battery

 

recharge and nominal mains voltage at 100% ohmic

 

load)

 

Over-Current protection [A]

20 A

(Based on continuous full load)

 

Input Voltage Range

+ 10%, -15% programmable

Input Frequency

50 Hz + 6% programmable

Current Distortion

< 12%

Power Factor

0.8 - 0.9

Bypass

 

Voltage

400 V 3 Wire + N + G

I Nom

14.4 A

Over-Current protection [A]

15 A

(Based on continuous full load)

 

Bypass Voltage Range

+ 10% programmable

 

 

Electrical Output

 

 

 

 

 

Voltage

400 V 3 Wire + N + G

Nominal Current

14.4 A

(The output Current is based on the nominal apparent

 

power of the UPS)

 

Frequency Range

50Hz (adjustable 0.25, 0.50, 1-8%)

 

 

990-2440

AIS 5000 400V Installation Manual

24

Image 30
Contents AIS Page Contents Options Operation Modes Page Safety Symbols used in this manualUser Safety Disconnect all sources of AC and DC powerGeneral Information About this manualSite Requirements Receiving and inspecting the UPSMoving the equipment to site Air Filter Fitting the air filterAir filter sizes Enclosure dimensions and footprint Enclosure dimensionsTop and bottom view of 10-30kVA UPS Top and bottom view of 40-60kVA UPS Top and bottom view of 80-100kVA UPS Connecting the UPS External connection boardInstalling Conduit Boxes  UPS Feet  Conduit Box  Front of Conduit BoxInput Conduit Output/Bypass Battery Alarm Conduit Access to Input/Output section Low-voltage section cover Communication Interface, EPO Connecting cables Input/Output -60 kVA Input/Output -100 kVA Grounding X090Emergency Power Off EPO Communication interfaceCommunication interface ports COM-PORTCOM Interface Overview of Communication interface10kVA 400V UPS Nominal Voltage 240 Max. Discharge Current a 46 aEmergency Power Off EPO Yes Approvals IEC 62040/EN 50091 Class A, VFI-SS-112Options 20kVA 400V UPS Mains Voltage 400 V 3 Wire + G Nom 19.88 kW 33.79 aVoltage 400 V 3 Wire + N + G Nominal Current 28.9 a Max 39.4 aMax. Discharge Current a 91 a External Connection 20kVA 400V UPS Options 30kVA 400V UPS Mains Voltage 400 V 3 Wire + G Nom 28.35 kW 47.86 aVoltage 400 V 3 Wire + N + G Nominal current 43.3 a Max 59.9 aMax. Discharge Current a 135 a External Connection 30kVA 400V UPS Options 40kVA 400V UPS Mains Voltage 400 V 3 Wire + G Nom 36.9 kW 61.93 aVoltage 400 V 3 Wire + N + G Nominal current 57.7 a Max 77.8 aMax. Discharge Current a 179 External Connection 40kVA 400V UPS Options 60kVA 400V UPS Mains Voltage 400 V 3 Wire + G Nom 54.42 kW 90.08 aVoltage 400 V 3 Wire + N + G Nominal current 86.6 a Max 117 aMax. Discharge Current a 266 External Connection 60kVA 400V UPS Options 80kVA 400V UPS Mains Voltage 400 V 3 Wire + G Nom 72.33 kW 118.23 aVoltage 400 V 3 Wire + N + G Nominal current 115.5 a Max 152.8 aMax. Discharge Current a 353 External Connection 80kVA 400V UPS Options 100kVA 400V UPS Max. Discharge Current a 442 External Connection 100kVA 400V UPS Options Options IP32 Drip Shield Mounting the drip shield Drip shield sizes Relay Board MessageMessage Communication Cards Cards and slotsDisplay Display introductionDisplay functions Display messages Programming the UPS User stackKeys Until the display shows Programming and Set-Up Programming the UPS Bypass Operation Push Cursor keysAuto Boost Charge OFF Battery Capacity Test ??? Battery Monitor Alarm Settings for redundant systems Enter new time HH.MM.SS Setting stack Minutes10 kVA 20 kVA 30 kVA 40 kVA 60 kVA 80 kVA 100 kVA How to change factory settings Operation mode descriptions Operation ModesNormal to Bypass Operation Bypass to Normal OperationPress Normal to Manual Bypass Operation Load is now supported by the UPS Page 990-2440